background image

PV-15208 Photovoltaic Inverter

Operation and Maintenance Manual

Copyright 2000, Xantrex Technologies/Trace Technologies Corp.

DOCUMENT:  150919

4-1

SECTION 4
OPERATION

DESCRIPTION OF SYSTEM OPERATION

     

Overview

The PV-15208 is a fully automated grid-tied photovoltaic inverter. Manual interaction or control of the
inverter is necessary only in the event of a system fault. The following conditions govern PV-15208
operation:

Stable utility voltage and frequency must be present for all states of operation.

Fault states are automatic from any state of operation. A fault will cause the PV-15208 to immedi-
ately stop processing all power. The fault condition will be reported to the operator interface.

The on/off switch, located on the front door of the PV-15208, must be switched to the on position
for all operating states.

Cycling the on/off switch attempts to clear any system faults and return the PV-15208 to normal
operation.

     Operating States
Control software governs the operation of the PV-15208. There are five main operating states. The
following descriptions depict the LED interface. Inverters configured with LCD displays will indicate
operating states on the display.

Standby: The amber LED is illuminated. The PCU monitors the status of the PV array and utility
grid, waiting until the PV array voltage is sufficient to export power to the utility.

Wake-Up: The amber LED is illuminated. Once the PV voltage is sufficient to export power to the
utility grid, the PV-15208 will wait 5 minutes before starting to insure the voltage is not transient in
nature. This keeps the system from cycling during unstable irradiance conditions.

Power Tracking: The green LED will illuminate while the PV-15208 delivers power to the utility.
This is the standard operating state of the PV-15208. The PV-15208 maximum power tracker will
optimize power output from the PV array. If available PV power is above the maximum power
rating of the PV-15208, the inverter will current limit, which will cause the PV voltage to rise
above the array peak power voltage. The minimum operating voltage of the PV-15208 is 330 VDC.
The power tracker will not track voltage below this point, regardless of the actual peak power
voltage of the PV array.

Sleep Test: The control system will begin a 5 minute sleep test. This normally indicates the PV
irradiance is declining as the sun sets. If the output power remains below 200 watts during the 5
minute sleep test, the system will transition to standby. The time delay allows the inverter to ride
through any temporary irradiance reductions.

Fault: The PV-15208 has encountered a fault condition. When this happens, regardless of the PV-

15208 state-of-operation, the PV-15208 will stop processing all power and execute an orderly sys-
tem shutdown. The red LED will illuminate while the yellow and green LED’s flash the fault code
(See section 5, Troubleshooting).

On early versions of the PV-15208, a push-pull Emergency Stop switch was used
instead of the on/off  switch. It functioned in the same manner described for the on/
off switch.

NOTE

OPERATOR INTERFACE (LED and LCD)

Содержание PV-15208

Страница 1: ...E INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR TRACE TECHNOLOGIES MODEL PV 15208 GRID TIED PHOTOVOLTAIC INVERTER THAT SHALL BE FOLLOWED DURING INSTALLATION AND MAINTENANCE OF THE PV 15...

Страница 2: ...nitialTurnOnProcedure Section 4 Operation DescriptionofSystemOperation Operator Interface Panel LED and LCD ExampleofNormalSystemOperation Section 5 Troubleshooting General FaultConditionsandTroublesh...

Страница 3: ...are provides for complete overall system control with a vari ety of protective and safety features MAJOR COMPONENTS The major components of the PV 15208 are identified in Drawing No 150921 Main Enclos...

Страница 4: ...trols the bus board The DSP module is designed to the industry standard PC 104 specification and is used to perform the majority of the calculations needed to control the bus board The most significan...

Страница 5: ...e i b m A m u m i x a M C 0 5 y t i d i m u H e v i t a l e R g n i s n e d n o c n o N 5 9 o T n o i t a v e l E t e e f 0 0 6 6 e v o b a d e t a r e D s e h c n i n i s n o i s n e m i D 4 1 X 5 2...

Страница 6: ...that the PV 15208 enclosure door be padlocked during normal operation Fault Reporting Any fault conditions are reported to the operator interface If the PV 15208 is equipped with LED s the red LED wil...

Страница 7: ...maining load resulting in an over under frequency or voltage condition The PV 15208 then performs an orderly shutdown The fault condition will remain until the utility voltage and frequency have retur...

Страница 8: ...utility it is not necessary to connect the neutral X0 to ground The PV 15208 is a balanced three phase current sourcing inverter and only operates with the presence of a stable utility voltage Single...

Страница 9: ...ing fan operation 2 Maintain a minimum 1 clearance to the left and right of the PV 15208 Installation 1 The unit must be mounted at least 3 off the ground and 12 above any horizontal surface 2 Screw t...

Страница 10: ...to a PV cabinet ground stud If ground fault detection is required route this jumper through CT1 located on the lower right hand corner of the control board see the system schematic for further detail...

Страница 11: ...and configures the modulator drivers accordingly 3 Phase 208 VAC inverter output main contactor see picture to terminals of the 208 VAC delta side of isolation transformer If the inverter side of the...

Страница 12: ...nual Copyright 2000 Xantrex Technologies Inc Trace Technologies Corp DOCUMENT 150919 3 5 Wiring Diagram Frame Ground Line Circuit Breaker Isolation Transformer PV 15208 Inverter To Single Point Electr...

Страница 13: ...URE The following procedures are intended to verify correct installation and proper operation of the PV 15208 These steps are to be followed sequentially Do not continue if any of the steps or results...

Страница 14: ...system faults Once all faults are cleared the amber indicator light will come on indicating the PV 15208 is in standby Close all PV array string disconnect switches if present Close the main PV discon...

Страница 15: ...to the utility grid the PV 15208 will wait 5 minutes before starting to insure the voltage is not transient in nature This keeps the system from cycling during unstable irradiance conditions Power Tr...

Страница 16: ...en LED will flash a sequence indicating the fault code See section 5 Troubleshooting The on off switch is used to enable or disable system operation The on off switch is also used to reset the inverte...

Страница 17: ...le and efficient operation of the PV 15208 connected with any PV array configured for a 330 500 VDC peak power voltage point Below is a list of the PV 15208 operating parameters showing valid ranges a...

Страница 18: ...6 n i M _ q e r F e l b a w o l l A m u m i n i M y c n e u q e r F y t i l i t U 0 3 6 0 7 5 z H 1 0 5 9 5 y a l e D _ x a M _ q e r F e l b a w o l l A m u m i x a M A o T e s n o p s e R e m i T y...

Страница 19: ...problem cannot be corrected contact your Xantrex Trace Technologies distributor for assis tance or service FAULT CONDITIONS AND TROUBLESHOOTING Fault Code Annunciation The PV 15208 will report faults...

Страница 20: ...e u q e r F r e v O e n i L C A 6 0 0 8 0 x 0 w o L e g a t l o V e n i L C A 7 0 0 1 0 x 0 h g i H e g a t l o V e n i L C A 8 0 0 2 0 x 0 e g a t l o V r e v O s u B C D 9 0 2 0 0 x 0 t l u a F m e...

Страница 21: ...grounded in more than one location If the PV array is grounded through CT1 it must not be grounded at any other location CT1 defective Contact your Xantrex Trace Technologies distributor for assistanc...

Страница 22: ...auses The utility voltage fell below the allowable limit 195 5 VAC by default Verify the utility voltage is stable and within allowable operating limits There is a problem with one or more of the AC s...

Страница 23: ...blem with the integrated bus board or DSP control board Emergency Stop Fault The on off switch located on the front door of the enclosure is disabled The contact block on the back of the switch must b...

Страница 24: ...eal If damaged replace with equivalent closed cell foam gasket Call your Xantrex Trace Technologies distributor for factory replacements or specifications Electrical Connections Inspect the condition...

Страница 25: ...move any lockout devices from the isolation transformer circuit breaker and PV disconnect switch 2 Close the isolation transformer circuit breaker 3 Close the AC disconnect if present 4 Close the PV a...

Страница 26: ...ter PV Series 150921 Rev B Assembly Main Enclosure Control Components 15 KVA PV 15208 Table of Components 150920 Rev B Envelope Drawing Grid Tied Inverter PV 15208 Underwriters Laboratories Listing Do...

Страница 27: ......

Страница 28: ......

Страница 29: ...15 25 3 1 1 151146 01 Fab Fan Shroud 4 1 T1 1 150438 01 Transformer 80VA 5 1 T2 1 150446 01 Transformer 40VA 6 1 K1 1 150668 65 Contactor 3P 24VDC Coil 65A 7 1 TB1 2 1 150410 01 Block Power Distribut...

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...ANGE OUTPUT WIRE RANGE CB 10H20 3R 14 to 8 6 to 2 CB 10HD8 3R 14 to 8 6 to 2 CB 12H20 3R 14 to 6 2 14 to 2 1 0 CB 12H20 4 14 to 6 2 14 to 2 1 0 For Model numbers CB 10H20 3R and CB 10HD8 3R reference...

Страница 36: ...Copyright Trace Technologies Document D07200 Rev B Sept 27 2000...

Страница 37: ......

Страница 38: ......

Отзывы: