SECTION 3
INSTALLATION AND INITIAL TURN-ON
PV-15208 Photovoltaic Inverter
Operation and Maintenance Manual
Copyright 2000, Xantrex Technologies Inc./Trace Technologies Corp.
DOCUMENT: 150919
3-3
Figure 3-2
Figure 3-3
LIQUID TIGHT CONNECTORS
Array Grounding and Ground Fault Detection
If grounding the PV array is required for monopolar or
bipolar arrays, jumper TB1-2 to a (PV-) cabinet ground
stud. If ground fault detection is required, route this
jumper through CT1 located on the lower right hand
corner of the control board (see the system schematic
for further detail). This must be the only point of PV
grounding for the PV-15208 and the ground fault
detection system to function properly.
CONTROL BOARD & CT1
CT1
The input and output circuits are isolated from
the enclosure, and that system grounding, if re-
quired by sections 690-41 and 690-42 of the Na-
tional Electric Code, ANSI/NFPA 70, is the
responsibiliy of the installer.
CAUTION