Specifications
A–8
975-0334-01-01
GT2.8
Input
Output
GT2.8-NA-240/208 UL-05
GT2.8-NA-240/208-POS UL-05
Model number
864-1001
864-1002
Input voltage, Maximum Power Point range
Certified operating range: 195–550 Vdc.
(Unit is operable as low as 193 Vdc.)
Absolute maximum array open circuit voltage
600 Vdc
Maximum input current
15.4 Adc (240 V), 14.9 Adc (208 V)
Maximum array short circuit current
24 Adc
Reverse polarity protection
Short circuit diode
Ground fault protection
GF detection, I
DIF
> 1 A
Nominal output voltage
240 V
208 V
Maximum output power
2800 W
2700 W
Operating range, utility voltage (phase to phase)*
*
Factory settings can be adjusted with the approval of the utility. This unit is provided with adjustable trip
limits and may be aggregated above 30 kW on a single Point of Common Coupling. See “Adjustable Volt-
age, Frequency and Reconnection Settings” on page A–10.
212–263 Vac
184–228 Vac
Operating range, utility voltage (phase to neutral)*
106.1–131.5 Vac
Nominal output frequency
60 Hz
Operating range, utility frequency*
59.3–60.5 Hz
Startup current
0 Aac
Maximum continuous output current
11.7 A
13.0 A
Maximum output fault current
15 A
Maximum output overcurrent protection
20 A RMS
Maximum utility backfeed current
0 A
Total Harmonic Distortion
<5%
Power factor
>0.99% (at rated power), >0.95% (full power range)
Utility monitoring— islanding protection
Vac, fac as per UL 1741 (2005)
Output characteristics
Current source
Output current waveform
Sine wave