Specifications
A–4
975-0334-01-01
GT4.0
Input
Output
GT4.0N-NA-240/208 UL-05
GT4.0-NA-240/208 UL-05 GT4.0-NA-240/208-POS UL-05
Model number
864-1008
864-1007
864-1010
Input voltage, Maximum
Power Point range
Certified operating range:
240–480 Vdc. (Unit is operable
as low as 235 Vdc and as high as
550 Vdc.)
Certified operating range:
195–550 Vdc. (Unit is
operable as low as 193 Vdc.)
Certified operating range:
195–550 Vdc. (Unit is operable
as low as 193 Vdc.)
Absolute maximum array
open circuit voltage
600 Vdc
Maximum input current
18 Adc (240 V), 17 Adc (208 V)
22 Adc (240 V), 21 Adc (208 V)
Maximum array short
circuit current
24 Adc
Reverse polarity
protection
Short circuit diode
Ground fault protection
GF detection, I
DIF
> 1 A
Nominal output voltage
240 V
208 V
Maximum output power
4000 W
3800 W
Operating range, utility voltage (phase to phase)*
*
Factory settings can be adjusted with the approval of the utility. This unit is provided with adjustable trip limits
and may be aggregated above 30 kW on a single Point of Common Coupling. See “Adjustable Voltage, Frequency
and Reconnection Settings” on page A–10.
212–263 Vac
184–228 Vac
Operating range, utility voltage (phase to neutral)*
106.1–131.5 Vac
Nominal output frequency
60 Hz
Operating range, utility frequency*
59.3–60.5 Hz
Startup current
0 Aac
Maximum continuous output current
16.7 A
18.3 A
Maximum output fault current
25 A
Maximum output overcurrent protection
25 A RMS
Maximum utility backfeed current
0 A
Total Harmonic Distortion
<5%
Power factor
>0.99% (at rated power), >0.95% (full power range)
Utility monitoring— islanding protection
Vac, fac as per UL 1741 (2005)
Output characteristics
Current source
Output current waveform
Sine wave