The GT Inverter has complete on-board over-current, over-temperature and
anti-islanding protection, and meets U.S., Canadian and international safety operating
standards and code requirements:
•
UL 1741 1st Edition 2005 Revision – Standard for Inverters, Converters, Controllers
and Interconnection System Equipment for Use with Distributed Energy Resources
(Includes IEEE 1547 and 1547.1)
•
CSA C22.2 No. 107.1-01 General Use Power Supplies
•
IEEE C62.41.2 – IEEE Recommended Practice on the Characterization of surges in
Low-Voltage AC Power Circuits (Location Category B). Part of UL 1741-2005.
Refer to approval certificate for details.
Outdoor enclosure
NEMA 3R, Rainproof
Inverter dimensions
(H × W × D)
28 ½ × 16 × 5 ¾ inches (724 × 403 × 145 mm)
Shipping dimensions
(H × W × D)
34 × 20 ½ × 10
5/16
inches (866 × 518 × 262 mm)
Inverter weight
58 lb (26.3 kg)
Shipping weight
76 lb (34.5 kg)
Input and output
terminals
AC and DC terminals accept wire sizes of 2.5 to 16 mm
2
(#14 to #6 AWG)
Disconnect switch
Integrated switch, disconnects both AC and DC
(meets NEC Article 690), rated @ 600 Vdc
Note:
This inverter is compliant with IEEE 1547 for those requirements referenced in
UL1741 (2005), section 46.1.1.:
A utility interactive inverter and interconnection system equipment (ISE) shall comply with
the Standard for Interconnecting Distributed Resources With Electric Power Systems, IEEE
1547, and the Standard for Conformance Test Procedures for Equipment Interconnecting
Distributed Resources with Electric Power Systems, IEEE 1547.1, excluding the
requirements for Interconnection Installation Evaluation, Commissioning Tests, and Periodic
Interconnection Tests.
Содержание GT5.0-NA-240
Страница 2: ......
Страница 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Страница 8: ...vi ...
Страница 14: ...xii ...
Страница 48: ...4 6 ...
Страница 60: ...5 12 ...
Страница 70: ...6 10 ...
Страница 89: ......