Electrical Specifications
975-0131-01-01
A–3
Adjustable Disconnect Settings
The adjustable disconnect setting values vary depending on whether the inverter is
a 208 Vac/60 Hz, 240 Vac/60 Hz, or 230 Vac/50 Hz model. Utility permission is
required prior to changing the settings on the inverter.
The default values of these settings differ from the utility specifications on
page A–2. These differences take into account the accuracy ranges listed in the
table below, and are intended to ensure that utility specifications are always met.
Output Power Versus Ambient Temperature
Once the heat sink on the inverter reaches a maximum temperature limit, the GT
Inverter reduces its energy output to ensure maximum component ratings are not
exceeded.
Setting
Default Values
Adjustment Range
Accuracy
208 Vac/60 Hz 240 Vac/60 Hz 230 Vac/50 Hz
From...
To...
AC Low Voltage
186 Vac
214 Vac
205 Vac
180 Vac
269 Vac
+/– 3 Vac
AC High Voltage
225 Vac
261 Vac
250 Vac
AC Low Frequency
59.4 Hz
47.1 Hz
46.0 Hz
62.0 Hz
+/– 0.1 Hz
AC High Frequency
60.4 Hz
50.9 Hz
Reconnect Delay
305 sec.
60 sec.
600 sec.
+/– 5 sec.
Figure A-1
Output Power vs. Ambient Temperature
GT3.0 GRID TIE SOLAR INVERTER
Output Power versus Ambient Temperature
0
500
1000
1500
2000
2500
3000
3500
-25
-15
-5
5
15
25
35
45
55
65
Ambient Temperature (C)
P
o
w
e
r (W
a
tts
)
Standard Unit
w/ Optional Fan Kit
Содержание GT3.0
Страница 1: ...Xantrex Grid Tie Solar Inverter Owner s Manual GT3 0 ...
Страница 2: ......
Страница 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Страница 8: ...vi ...
Страница 12: ...x ...
Страница 16: ...xiv ...
Страница 18: ...xvi ...
Страница 20: ...xviii ...
Страница 65: ...Connecting Inverters in Parallel 975 0131 01 01 3 11 Figure 3 6 Parallel GT Inverter DC and AC Wiring ...
Страница 72: ...3 18 ...
Страница 108: ...IX 4 ...
Страница 109: ......