Installation
2–6
975-0131-01-01
Voltage and MPPT Requirements
MPPT operational
window
Ensure that the PV array used in the system operates within the MPPT operational
window (Table 2-1).
Voltage
requirements
The maximum power point voltage of a string connected to the GT Inverter should
be a minimum of 195 Vdc. If it is less than 195 Vdc, then the power point is
shifted and the PV voltage is regulated to 195 Vdc.
By regulating the operating voltage of the solar modules, the MPPT software
maximizes their output energy.
Effects of array voltages outside of the MPPT operational window are shown in
Table 2-1.
Maximum PV
Power
The solar array should be sized such that its maximum power output does not
exceed the limits of the MPPT operational window (195 to 550 Vdc). See
“Guidelines for Matching PV Array Size to Xantrex Grid Tie Solar Inverter
Input”.
Under no conditions should the array voltage exceed 600 V
OC
(open circuit
voltage).
Table 2-1
MPPT Operational Window
Voltage
Effect of Array Voltage
Inverter Mode
< 195 Vdc
Operating voltage will be shifted to 195 Vdc;
the array will not be at its maximum power
point
Low power
195 to 550 Vdc
Maximum harvest of solar energy
MPPT window
550 to 600 Vdc
Will not allow maximum harvest of solar
energy
Power derating
> 600
Will shut down and may cause damage to the
inverter; stops selling surplus energy
Shutdown
Содержание GT3.0
Страница 1: ...Xantrex Grid Tie Solar Inverter Owner s Manual GT3 0 ...
Страница 2: ......
Страница 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Страница 8: ...vi ...
Страница 12: ...x ...
Страница 16: ...xiv ...
Страница 18: ...xvi ...
Страница 20: ...xviii ...
Страница 65: ...Connecting Inverters in Parallel 975 0131 01 01 3 11 Figure 3 6 Parallel GT Inverter DC and AC Wiring ...
Страница 72: ...3 18 ...
Страница 108: ...IX 4 ...
Страница 109: ......