Operation
Command Summary
36
Operating Manual for GPIB for XPD Series Power Supply
Command Summary
Use these commands to control the operation of the supply. They are listed here
in order of function such as PROGRAMMING, QUERY, CALIBRATION, and
STATUS commands. See “Command Reference” on page 39 for more detailed
information about each command and its use.
Table 3.5
Programming Commands
Command
Description
AUXA
Selects the state of the AUXA output signal on the J21-7 connector.
AUXB
Selects the state of the AUXB output signal on the J21-8 connector.
CLR
Initializes the power supply to its Power ON (PON) state.
DLY
Sets a programmable time delay which is executed by the supply
before reporting fault conditions after a new output voltage or current is
specified.
FOLD
Sets foldback mode for the supply.
HOLD
Enables or disables voltage/current setting hold mode for the supply.
IMAX
Sets an upper soft limit on the programmed output current for the
supply.
ISET
Sets the output current of the supply in amps (default) or in milliamps.
OUT
Enables or disables voltage/current output for the supply.
OVSET
Sets the over voltage protection trip point for the supply in volts
(default) or in millivolts.
RST
Resets the supply to the present voltage and current settings if the
output is disabled by OVP or foldback protection.
SRQ
Enables or disables the power supply's ability to generate a service
request.
TRG
Implements programmed voltage and current settings which had been
in hold mode.
VMAX
Sets an upper soft limit on the supply’s programmed output voltage.
VSET
Sets the output voltage of the power supply in volts (default) or in
millivolts.
Содержание GPIB-XPD
Страница 1: ...Operating Manual Internal GPIB Interface for XPD Series Programmable DC Power Supply GPIB XPD...
Страница 2: ......
Страница 3: ...Operating Manual for Internal GPIB Interface for XPD 500 Watt Series Programmable DC Power Supply...
Страница 10: ...About This Manual viii Operating Manual for GPIB for XPD Series Power Supply...
Страница 16: ...Features and Specifications Specifications 14 Operating Manual for GPIB for XPD Series Power Supply...
Страница 57: ......