Adjusting Feature Settings in Configuration Mode
975-0787-01-01
55
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Transfer Mode
11
APL
APL
(appliance)
UPS
(UPS)
Selecting
APL
- appliance sets the transfer time from line to battery
to 20 ms. Selecting
UPS
(uninterruptible power supply) sets the
transfer time from line to battery to 10 ms.
NOTE
: Do not connect
motor loads when in UPS transfer mode. See
Utility AC Under Voltage
Level
12
90
85
to
110
Inverter Shutdown
Recovery
13
MAT
At0
(auto-
restart)
MAT
(manual
restart)
The inverter shuts down when there is an over temperature,
overload, and short circuit condition. Selecting
ATO
(auto-restart)
will allow the inverter to recover automatically from a shutdown up
to three times maximum. Selecting
MAT
(manual restart) allows the
user to restart the inverter by performing a manual reset, that is, by
acknowledging the restart via the display panel.
Audible Alarm
14
bON
bON
Audible
BOF
(Mute)
The alarm beeps once every five seconds.
Reset all settings to their
default values
99
ndf
NDF
(as is)
DEF
(default)
ndF
refers to current settings.
Choose
def
to restore all settings to their default values.