AC/DC and GFCI Panel
975-0787-01-01
9
Feature
Description
5
Grounding lug
provides a ground path for the
Freedom X chassis to the DC system ground. See
WARNING.
6
DC terminal
opening for routing (–) negative DC
cable.
7
DC terminal
opening for routing (+) positive DC
cable.
8
LED indicator
for reverse DC polarity.
9
AC output terminal opening
for routing AC output
wiring.
10
AC input terminal opening
for routing AC input
wiring.
11
GFCI cover
is removed when installing a qualified
GFCI device such as the optional GFCI kit (sold
separately; order PN: 808-9817).
12
Mounting flanges
on both sides allow you to mount
the inverter permanently on deck or on a wall.
Feature
Description
13
Ventilation grille
(openings) must not be obstructed
for the proper operation of the cooling fan and
inverter. When the inverter is mounted, the
ventilation grille must not point up or down.
Cooling fans
turn on when the internal temperature
reaches a set point temperature.
14
20 A supplementary protector with reset button
provides overload protection for the Freedom X
GFCI Kit (PN: 808-9817) (sold separately) option.
Press to recover from an overload condition. In a
hard wired installation, the supplementary protector
does not protect output wiring.
WARNING
ELECTRICAL SHOCK HAZARD
l
Use a torque screwdriver to tighten the bolt on the DC ground
lug to a torque of 23 in-lb (2.6 N-m) of force.
l
Apply an anti-corrosion compound to the copper wire prior to
connecting to the DC ground lug.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.