Basic Installation Procedures
28
Freedom X Owner's Guide
Color
AC Wire
Black/Red/Brown
Line
White/light blue
Neutral
Green, green/yellow, or bare
copper
Ground (Earth)
Table 9 Color codes for typical AC wiring
NOTICE
REVERSE POLARITY DAMAGE
Make sure the wires are connected properly. Improper connections
(connecting a line conductor to a neutral conductor, for example)
will cause the Freedom X to malfunction and may permanently
damage the inverter. Damage caused by a reverse polarity
connection is not covered by your warranty.
Failure to follow these instructions can result in equipment
damage.
Wiring Knockouts
When installing wires to the AC terminals, the AC input and output
holes are provided to accommodate ½" trade-size strain relief
clamps. If larger cables and strain relief clamps are needed,
remove the ¾" trade-size knockout rings
e
.
e
Available only to Freedom X 3000 120VAC 12VDC.
Make sure to seal the open ½" trade-size holes with the supplied
knockout plugs by placing the plugs and firmly pressing them into
the holes.
NOTICE
EQUIPMENT DAMAGE
Install the supplied AC knockout plugs over the knockout holes
when not used for wiring to prevent objects and other material from
entering the unit.
Failure to follow these instructions can result in equipment
damage.
AC Input Connections
To make a permanent connection to existing AC wiring:
1. Ensure AC and DC power sources are turned off.
2. Install the required circuit breaker in the AC distribution
panel supplying AC power to the unit.
3. Remove the wiring compartment cover by loosening the
captive nut panel screw [1] and lifting the cover up and out.
WARNING
ELECTRIC SHOCK HAZARD
Use a screwdriver to loosen the captive nut panel screw.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.