42
Freedom SW 3000 Owner’s Guide
Configuration
Configurable setting
This setting lets you adjust the voltage above
which the inverter/charger no longer qualifies AC as “good” and transfers
to Invert.
You can adjust Hi AC Volt settings as follows:
When to use
This setting lets you adjust the AC parameters when AC
supply is outside the upper voltage range required for electrical equipment.
Outcome
The upper limit of the voltage that will be qualified as “good”
by the inverter/charger can be varied.
Hi AC Freq
Full name
High AC transfer frequency (AC over frequency level)
Configurable setting
This setting lets you adjust the highest frequency at
which the Freedom SW 3000 no longer qualifies AC as “good” and
transfers to Invert.
You can adjust Hi AC Freq settings as follows:
When to use
This setting lets you adjust the AC parameters when the AC
supply is outside the higher frequency range required for electrical
equipment.
Outcome
The highest frequency of the AC supply that will be qualified
as “good” by the inverter/charger can be varied.
Hi AC Volt
[135V]
Range of values
Increment
Default
120 to 145 VAC
1 volt
135 VAC
Hi AC Freq
[65Hz]
Range of values
Increment
Default
62 to 70 Hz
1 Hz
65 Hz