background image

DIQ/S 181

Outputs

79

ba77083e01

02/2015

Characteristic curve

If a value for 

End value

 that is greater than the 

Start value

 is entered, 

the output has a positive characteristic curve.

In order to obtain a negative characteristic curve, a value for 

End value

 

must be entered that is smaller than the value for 

Start value

.

6.4.6

Pulse-width output

Function

The characteristic of the pulse width output is laid down in the 

Start 

value

End value

Pulse width (v) min.

 and 

Pulse width (v) max.

 

settings. The fundamentals of the function are described in the 
introductory chapter (see section 6.3.3).

In order to set up the 

Pulse-width output

 function for a relay output, the 

relay output must be linked with the sensor (see section 6.2.1).

Settings

Start value

within the 
measuring range 
(sensor-
dependent)

Minimum spacing: 
5 % of the 
measuring range

End value

Frequency (f) min.

0 to 120 1/min

Minimum spacing: 
10 1/min

Frequency (f) max.

Frequency with error

0 to 120 1/min

In case of system 
errors or sensor 
errors (see 
page 87), the relay 
switches with the 
frequency 
specified.

Action

Open
Close

Relay action

Setting

Selection/Values

Explanation

Setting

Selection/Values

Explanation

Measured variable

Main variable
Adjoining variable

Main variable

 

designates the 
actual measured 
parameter of the 
sensor (e.g. pH, 
oxygen, etc.).

Adjoining variable

 

designates an 
additional measured 
parameter (e.g. 
temperature).

Содержание DIQ/S 181

Страница 1: ...OPERATING MANUAL ba77083e01 02 2015 DIQ S 181 UNIVERSAL TRANSMITTER FOR ONE DIGITAL SENSOR...

Страница 2: ...Copyright 2016 Xylem Analytics Germany GmbH Printed in Germany...

Страница 3: ...ts of the electrical installation 11 3 4 Installation guidelines for lightning protection 12 3 5 Connecting the sensor 14 3 6 On site mounting of the DIQ S 181 16 3 6 1 General information 16 3 6 2 Mo...

Страница 4: ...59 5 The SETTINGS menu 60 5 1 Overview of the SETTINGS menu 60 5 2 Language 60 5 3 Sensor S01 61 5 4 Relay output R1 R2 R3 mA output C1 C2 62 5 5 System 63 6 Outputs 64 6 1 Outputs of the DIQ S 181 64...

Страница 5: ...case of error 87 6 6 2 Behavior in non operative condition 87 7 Maintenance and cleaning 88 7 1 Maintenance 88 7 2 Cleaning 88 8 What to do if 89 8 1 Information on errors 89 8 2 Error causes and rem...

Страница 6: ...List of contents DIQ S 181 6 ba77083e01 02 2015...

Страница 7: ...nected sensor Linked outputs can be used to monitor the connected sensor and for the output of measured values A relay output can be programmed as Monitoring relay Limit monitor Proportional output of...

Страница 8: ...e relay outputs Settings and links of the current outputs System settings display language air pressure altitude pass words etc Linked relay outputs switch to the non active condition open Linked curr...

Страница 9: ...bly dangerous situation that can lead to serious irreversible injury or death if the safety instruction is not fol lowed CAUTION indicates a possibly dangerous situation that can lead to slight revers...

Страница 10: ...ting manual The product may not be opened 2 2 3 Unauthorized use The product must not be put into operation if it is visibly damaged e g after being transported it was stored under adverse conditions...

Страница 11: ...owing requirements Compliance with national regulations e g NEC VDE and IEC Suitability for the electrical conditions at the place of installation Maximum operational voltage Maximum operational curre...

Страница 12: ...in the WTW online instrumentation as so called lightning protection see chapter 9 TECHNICAL DATA The external protective measures of the installation environment can be carried out with respect to the...

Страница 13: ...on system for the plant 6 One part of the safety and lightning protection concept is based on high grade protective insulation of the DIQ S 181 It does not have or require any protective ground conduc...

Страница 14: ...must always be installed separately at a minimum distance of 20 cm from other lines that carry a voltage greater than 60 V The free end of the sensor cable was stripped in the factory and all the wir...

Страница 15: ...cable gland no 029 212 pos 1 in Fig 3 1 with the sealing pos 2 into the enclosure at the mounting position for the SENSOR connection see label on the bottom of the enclo sure 3 Loosen the cap nut pos...

Страница 16: ...to the terminal strip When doing so look out for the designations of the terminals white brown shield green 6 Tighten the cap nut pos 3 in Fig 3 1 7 Close the enclosure The complete assignment of the...

Страница 17: ...d SD K 170 The sun shield SD K 170 provides room for the universal transmit ter The sun shield can be mounted to round or square section pipes e g rails with the aid of the MR SD 170 mounting kit sect...

Страница 18: ...ing the ISO blind nuts Fig 3 4 Mounting the sun shield Premounting the ISO blind nuts 1 Screw the sun shield pos 1 in Fig 3 3 with the four hexsocket head screws pos 2 the washers pos 3 and the clamps...

Страница 19: ...nd or railing Materials required SD K 170 sun shield see chapter 10 ACCESSORIES AND OPTIONS 3 Insert the cheese head screws pos 6 in Fig 3 4 with the plastic washers in the drilled mounting holes and...

Страница 20: ...g the DIQ S 181 with sun shield SD K 170 3 6 4 Top hat rail mounting Materials required THS IQ kit for top hat rail mounting see chapter 10 ACCESSORIES AND OPTIONS Tools Phillips screwdriver 1 Remove...

Страница 21: ...ed in the panel installation kit 1 Screw the clamping assembly pos 1 in Fig 3 7 on the back of the universal transmitter with the two plastic tapping screws pos 2 2 Attach the universal transmitter to...

Страница 22: ...dimensions in mm Mounting the DIQ S 181 in a switch panel Fig 3 9 Mounting the DIQ S 181 in Fig 3 9 138 138 Maximum thickness 10 mm 1 Insert the universal transmitter in the panel aperture from the f...

Страница 23: ...unting DIQ modules with the MS DIQ mounting set 3 7 Electrical connections General instructions Cable glands All electric cables are fed from below through openings prepared in the enclosure of the DI...

Страница 24: ...les earth cable after stripping the outer insulation see section 3 12 and sensor connection cables Big clamping range 7 to 13 mm no 021 339 This cable gland is required for cable sheaths with an outsi...

Страница 25: ...in use as closely as possible to the cable gland 3 8 Connecting the voltage supply The two following paragraphs describe how to connect both models of the DIQ S 181 universal transmitter to the voltag...

Страница 26: ...the DIQ S 181 Tools Cable stripping knife Wire stripper Phillips screwdriver Small screwdriver Preparing the power cable Fig 3 11 Prepared power cable NOTE The ground wire must not project into the en...

Страница 27: ...crew a cable gland pos 1 in Fig 3 12 with sealing ring pos 2 into the enclosure below the power supply connection 7 Loosen the coupling ring pos 3 8 Feed the power line through the cable gland into th...

Страница 28: ...ut off any wires that are not in use as closely as possible to the cable gland The complete assignment of the terminal strip is shown in section 3 11 9 Connect phases L and N to the terminal strip Mak...

Страница 29: ...provided as an interrupt facility for the universal transmitter DIQ S 181 The interrupt facility must be installed in the vicinity of the DIQ S 181 universal transmitter easily accessible by the user...

Страница 30: ...side of the DIQ S 181 remove the two coun tersunk screws and open the enclosure 5 Screw a cable gland pos 1 in Fig 3 15 with sealing ring pos 2 into the enclosure below the 24 V AC DC connection 6 Lo...

Страница 31: ...that are not in use as closely as possible to the cable gland The complete assignment of the terminal strip is shown in section 3 11 8 Connect wires 1 and 2 to the terminal strip Make sure that the c...

Страница 32: ...ot subject to this danger e g the DIQ CHV module may be operated on the fur ther relays Switching voltages and switching currents on the relay con tacts must not exceed the values specified in chapter...

Страница 33: ...Always cut off any wires that are not in use as closely as possible to the cable gland The complete assignment of the terminal strip is shown in section 3 11 2 Screw a cable gland pos 1 in Fig 3 17 w...

Страница 34: ...in the DIQ CHV in series Bridge a terminal of the auxiliary voltage output with a terminal of a relay output and run a control line from the remaining terminals to the valve module NOTE The auxiliary...

Страница 35: ...successfully initialized the measured value display appears With a sensor not yet providing any measurement values Init appears tem porarily Relais contact Bridge Auxiliary voltage output Valve contro...

Страница 36: ...R1 L1 N 240V AC 2A AC 240V AC 2A AC 240V AC 2A AC HILFS SPANNUNG AUXILIARY VOLTAGE 0 4 20mA REC C2 0 4 20mA REC C1 WEI BRAUN WHITE BROWN SENSOR WEI BRAUN WHITE BROWN SCHIRM SHIELD GR N GREEN X3 X2 X1...

Страница 37: ...ods please specify length when ordering NOTE The sensor cable may only be connected to the SENSOR connections No wire of the cable may be connected with an external electrical po tential Otherwise mal...

Страница 38: ...uter insu lation 3 Only for the SNCIQ UG earth cable strip the outer insulation for a further 35 mm 4 Shorten the exposed shielding braid up to the cable sheath 5 Shorten the two fillers plastic inlay...

Страница 39: ...1 2 Screw a cable gland pos 1 in Fig 3 1 with the sealing pos 2 into the enclosure at the mounting position for the SENSOR connection see label on the bottom of the enclo sure 3 Loosen the cap nut pos...

Страница 40: ...ions of the terminals white brown shield green Connect the red cable to the terminal with the designation white brown 6 Tighten the cap nut pos 3 in Fig 3 1 7 Close the enclosure The complete assignme...

Страница 41: ...4 4 5 5 6 6 7 7 SNCIQ UG SNCIQ UG Maximum total cable length SNCIQ UG plus SACIQ 250 m DIQ S 181 24V DIQ S 181 Sensor DIQ JB M C S ESC OK DIQ S 181 green white brown green red X1 X4 X2 X5 X3 X6 X7 Ter...

Страница 42: ...omatic compressed air cleaning module DIQ CHV The valve module for the automatic relay driven compressed air clean ing of a sensor module DIQ CHV has four additional potential free ter minals for the...

Страница 43: ...ure Otherwise there is a danger that areas safe to contact could come into con tact with dangerous voltages Always cut off any wires that are not in use as closely as possible to the cable gland M C S...

Страница 44: ...10 X9 X2 X8 X1 Terminal strip DIQ S 181 Terminal strip DIQ CHV R1 HILFS SPANNUNG AUXILIARY VOLTAGE VENTIL VALVE R2 R3 a b c Valve control line X6 X5 X4 X3 VERTEILER DISTRUBUTION X1 X4 X2 X5 X3 X6 X7 T...

Страница 45: ...asured value display from all operating situations C Starts calibrating the connected sensor S Opens the SETTINGS menu in the measured value and status display ESC Switches to the higher menu level Ca...

Страница 46: ...and prompt for important data calibration data error messages operating states software versions etc Using S open the SETTINGS menu Special sensor conditions The following displays inform you of spec...

Страница 47: ...TTINGS menu main menu Operating notes In the main menu the lock symbol shows the current safety level for the settings a Settings not protected by password z Settings protected by password reading pos...

Страница 48: ...gle switch is used to highlight a setting displayed in reverse video and move the visible display range up or down To edit a setting highlight it and press OK The line below is high lighted and switch...

Страница 49: ...s OK The entry mark moves to the next position and indicates P Select the next character with the toggle switch When you have selected the required sequence of characters select P as the following cha...

Страница 50: ...maintenance condition of a sensor on and off Fig 4 7 PROPERTIES menu Submenus functions Maintenance S01 With this function you switch on and off the maintenance condition of a sensor see section 4 4...

Страница 51: ...ance con dition for the sensor should always be switched on In the maintenance condition except for the display the DIQ S 181 does not react to the current measured value or the condition of the selec...

Страница 52: ...nually Sensor cleaning active Sensor cleaning OFF automatic sequence Maintenance condition OFF e Switch Display message on the maintenance condition Continue Cancel 1 Switch on the maintenance conditi...

Страница 53: ...e calibrated Fig 4 8 SENSOR STATUS S01 Log book The log book is a list of messages related to the connected sensor If there is a new message the error symbol in the header of the measured value displa...

Страница 54: ...ssage code Fig 4 10 Message code 1 Message type error symbol of an unacknowledged mes sage or checkmark with an acknowledged message 2 Message code 3 Date and time of the message The log book shows th...

Страница 55: ...view detailed messages 2 Type Calibration C Installation and commissioning I Instructions for service and repair S Application instructions A 3 Type number Each type contains subtypes 0 9A Z Only the...

Страница 56: ...u acknowledge the message 6 Once again press OK This returns you to the log book where you can view and acknowledge further messages as necessary 7 To exit the log book press ESC Return directly to th...

Страница 57: ...ue display 3 Confirm with OK The maintenance condition is active The following proceeding is sensor type specific The display guides you through all steps Follow the instructions exactly A message of...

Страница 58: ...d password is entered calibration is blocked Configuring passwords Activating deactivating and changing passwords is carried out in the SETTINGS System menu Fig 4 11 SYSTEM SETTINGS menu Operating not...

Страница 59: ...t passwords In the default condition of the DIQ S 181 both passwords are set to 1000 4 6 2 Forgotten the password Procedure Prompt for the password 1 Open the SETTINGS menu with S 2 Depending on the p...

Страница 60: ...ollowing paragraphs 5 2 Language In this menu you can set the system language Proceeding selecting the language To view these menu items scroll down with 1 Open the SETTINGS menu with S 2 Using and OK...

Страница 61: ...r all displays of this sensor appear in the standard language English To activate the selected system language for this component a software update of the component is required Please contact WTW Gene...

Страница 62: ...et 5 4 Relay output R1 R2 R3 mA output C1 C2 These two menus can be used to link the sensor with the relay outputs and current outputs of the DIQ S 181 and to set the outputs The vari ous setting opti...

Страница 63: ...for optimum readability Delivery state Here you can reset all settings to the default values Only the date time and contrast setting for the display will remain stored If the set tings password is ac...

Страница 64: ...ed current value 6 2 Linking and adjusting general proceedings 6 2 1 Linking the outputs Linking options The following options of linking the outputs are available Sensor S01 The output is linked with...

Страница 65: ...t with all linking options is displayed 3 Select the required option with and confirm with OK The output is linked The link is displayed in the header when the setting of the output is edited 1 Open t...

Страница 66: ...e SETTINGS menu with S 2 Using and OK select and confirm the Relay output Rx menu item corresponding to relay 1 2 or 3 or mA output Cy menu item corresponding to current output 1 or 2 3 Confirm the se...

Страница 67: ...ceeded or undercut a relay switches The Open or Close relay actions are possible in each case see page 68 Monitoring two limiting values using two relays If the upper limiting value is exceeded or und...

Страница 68: ...d measured value range proportional range At the same time the relay switches with a duration of operation that corresponds to the measured value pulse width output see page 70 or 1 Upper limit value...

Страница 69: ...two relays An output range is defined for each relay with a Start value and an End value One relay outputs in the upper output range and a further relay in the lower output range see page 69 Output wi...

Страница 70: ...with it the pulse width v The pulse width can be set from 0 to 100 v ton T 100 v pulse width T cycle duration ton turn on duration If the measured value is at the end of the proportional range End va...

Страница 71: ...ching frequency is higher If the measured value is at the beginning of the proportional range Start value the switching frequency is low Characteristic curves Through the selection of the Start value...

Страница 72: ...eristic curve The proportional output range begins above the initial value If the proportional range is undercut or exceeded the selected behavior comes into force Measured value Switching frequency f...

Страница 73: ...omes into force 1 Start value Measured value with a minimum pulse width or switching frequency 2 End value Measured value with a maximum pulse width or switching frequency 0 10 50 90 100 Proportional...

Страница 74: ...easured value with a minimum pulse width or switching frequency 2 End value Measured value with a maximum pulse width or switching frequency 0 50 100 Measured value Proportional band 1 50 of maximum s...

Страница 75: ...rrors Settings Function Setting table No function The relay output is not used System monitoring see section 6 4 2 Sensor monitoring see section 6 4 3 Limit indicator see section 6 4 4 Frequency contr...

Страница 76: ...nsor is in the maintenance condition The sensor is being cleaned with the aid of a valve module compressed air operated cleaning system 6 4 3 Sensor monitoring Function The Sensor monitoring function...

Страница 77: ...th the sensor see section 6 2 1 Settings For monitoring functions preferably set up the relay output as an opener Init This can prompt a relay action for a short time depending on the starting behavio...

Страница 78: ...or at error Open Close Unchanged The relay opens closes or remains unchanged in the case of system errors or sensor errors see page 87 Action Open Close Relay action Switching delay 0 3600 s The time...

Страница 79: ...n order to set up the Pulse width output function for a relay output the relay output must be linked with the sensor see section 6 2 1 Settings Start value within the measuring range sensor dependent...

Страница 80: ...output must be linked with the sensor see section 6 2 1 The assigned relay always works as a closer The cleaning cycle consists of Cleaning duration and Adjustment time During the cleaning cycle the...

Страница 81: ...cle will start in a few minutes settings see following table Settings With short cleaning intervals the adjustable values for the Cleaning duration and Adjustment time are limited The following values...

Страница 82: ...n max 60 s max 120 s 20 min max 180 s max 300 s With this the cleaning times are fixed They only change when the reference time is changed The reference time and all further cleaning times relate to t...

Страница 83: ...leaning cycle t1 Start of the specified Cleaning duration t1a 2 End of the specified Cleaning duration t1a Start of the specified Adjustment time t1b 3 End of the specified Adjustment time t1b End of...

Страница 84: ...6 4 8 Manual control Function The Manual control function can be used to test the operativeness of an instrument that is connected to the relay To do so close or open the relay manually and while doi...

Страница 85: ...Start value and End value settings Settings Function Setting table No function The current output is not used Recorder see section 6 5 2 Fixed current value see section 6 5 3 Setting Selection Values...

Страница 86: ...error see below Limitation The current at the output is limited to the Start value or End value Behavior at error Fixed current value In the case of system errors and sensor errors the current output...

Страница 87: ...er failure As soon as the supply voltage is sufficient again the non operative condition of the outputs ends The outputs function as specified by the user again Erasing the link with the sensor Changi...

Страница 88: ...e cloth If compressed air is available on site blow off the worst of the dirt beforehand Keep the enclosure closed while doing so NOTE Do not use high pressure water blasters for cleaning danger of wa...

Страница 89: ...s and remedies The DIQ S 181 no longer reacts to entries Error in the measured value display The selected system language was not activated for a sensor Information on possible errors of the sensor is...

Страница 90: ...components while the DIQ S 181 is switched off De fective components are removed in the reverse order to the installation see chapter 3 INSTALLATION 8 3 2 Replacing the sensor Inactive dataset of the...

Страница 91: ...te again Example Maintenance repairs replacement This mechanism ensures that all sensors retain their settings and links if a sensor was removed for maintenance or if the DIQ S 181 was temporarily swi...

Страница 92: ...1 Dimension drawing of the DIQ S 181 dimensions in mm Test certificates Mechanical structure Side view 144 0 115 0 70 0 144 0 45 0 72 0 52 2 43 0 11 0 16 5 Front view Rear view 137 0 137 0 M C S ESC O...

Страница 93: ...er 10 ACCESSORIES AND OPTIONS Temperature Operation 20 C 55 C 4 131 F Storage 25 C 65 C 13 149 F Relative humidity Yearly average 90 Dew formation Possible Site altitude Max 2000 m above sea level Pow...

Страница 94: ...5 X13 X7 X11 X5 X1 X16 X8 X14 X12 X6 X10 X4 100 240V AC NETZ MAINS AUXILIARY R3 R2 R1 L1 N 240V AC 2A AC 240V AC 2A AC 240V AC 2A AC HILFS SPANNUNG AUXILIARY VOLTAGE 0 4 20mA REC C2 0 4 20mA REC C1 WE...

Страница 95: ...e 0 40 mA s Error behavior can be set as required 0 21 mA Error behavior according to Namur NE43 can be selected Positive and negative characteristic curve Terminal type Screw type terminal strip acce...

Страница 96: ...ccessory products in a user specific system has the EMC characteristics listed Applicable norms EN 61010 1 UL 3111 1 CAN CSA C22 2 No 1010 1 94 94 ca 25 57 DIQ JB Enclosure material Polystyrene Weight...

Страница 97: ...lines Terminal strip inside the enclosure Connecting terminals Cable feeds Prepared openings for installing two screwed cable glands M16 x 1 5 both on the upper and underside 94 94 28 57 DIQ CHV Encl...

Страница 98: ...1 universal transmitter Compressed air Cable feeds Prepared openings for installing two screwed cable glands M16 x 1 5 on the upper side Switching voltage Approx 22 V Max switching current Approx 40 m...

Страница 99: ...S DIQ 472 009 Sun shield for the DIQ S 181 SSH IQ 109 295 Sun shield for the DIQ S 181 SD K 170 109 284 Mounting kit for the pipe installation of sun shields MR SD 170 109 286 Kit for wall mounting of...

Страница 100: ...Effects of the weather 17 Electrical data DIQ S 24 V version 94 DIQ S line power version 93 EMC characteristics 95 erasing a link 65 Error symbol 47 53 F Frequency output relay 78 I Inactive dataset 6...

Страница 101: ...passive components 90 of the sensor 90 S Sensor conditions special ones 46 SENSOR connection 16 40 SENSOR connection terminal strip 36 Sensor monitoring relay 76 Sensor status 53 SNCIQ cable 37 SNCIQ...

Страница 102: ...Index DIQ S 181 102 ba77083e01 02 2015...

Страница 103: ......

Страница 104: ...buildings factories and farms In more than 150 countries we have strong long standing relationships with customers who know us for our powerful combination of leading product brands and applications...

Отзывы: