Worcester WM 12 Скачать руководство пользователя страница 28

WARNING: The appliance is serviced and repaired externally.
External equipment operated at 230volts should not be ser-
viced or repaired under adverse weather conditions.

14.1 

The following should be carried out at least once per year

to ensure efficient, trouble free operation.

NOTE:

The service engineer should have access to the property to

check for system faults and reset/replace electrical safety devices.

NOTE:

The service engineer should take any necessary precau-

tions to protect him/herself and any third party against hot sur-
faces on the appliance.

1. 

Carry out a pre-service check noting any operational faults.

2. 

Check and clean the burner.

3.

Check and clean the air intake inlets around the external cover and duct.

4. 

Check that the flue system is unobstructed and clean as necessary.

5. 

Check and clean the insulated box.

6. 

Check and clean the baffle.

7. 

Check and clean the heat exchanger surface.

8. 

If the appliance has been installed in a compartment check

that the ventilation areas are clear.

9.

Clean all oil filters.

Some of the servicing points are covered more fully in the following
instructions:-

14.2 Pre-Service Check
1. 

Remove the internal cabinet as described in Section 5.

2. 

Remove the external cover and switch the service switch to

the ‘OFF’ position (mid position) (see fig. 29).

3. 

Switch the service switch to the 'RUN' position (fully black)

(see fig. 29) to operate the appliance and system, noting any
faults which may need to be corrected during the service.

4. 

To override the programmer switch the service switch to the

service mode (fully red) (see fig. 29 and Section 10.11).

14.3 Cleaning the Burner
IMPORTANT – 

Disconnect the electrical supply at the mains

before commencing any servicing. Remove the burner electrical
plug lead by depressing the two locking ears and pulling the
plug downwards. Turn off the oil at the service cock.

1. 

Remove the burner.

(a)  

Isolate the oil supply at both the oil tank and the isolating

valve between the burner and oil filter.

(b) 

Remove the burner electrical plug lead by depressing the two

locking ears and pulling the plug downwards.

(c) 

Remove the burner from the boiler by slackening the 5 mm

retaining screw located to the left of the burner control box This
will require the use of a 4 mm hexagon driver.

(d) 

Hang the burner on the burner hanging bracket situated on

the bottom left hand side of the external duct (see fig. 30).

2. 

Clean the fan impeller using the following procedure:

Electro-oil Inter B9 Burner
(a) 

Remove the two screws holding the combustion head in posi-

tion and withdraw the combustion head.

(b) 

Remove the three remaining screws holding the front cover

plate in position and withdraw the cover to expose the fan impeller.

(c) 

Clean both sides of the fan impeller and remove any debris

from the burner housing.

(d) 

Check the impeller rotates freely.

(e) 

Clean the air inlet passage and check that the adjustment

mechanism operates freely.

(f)  

Re-assemble the components.

5. 

Remove the combustion head and thoroughly clean all

deposits.

6. Inspection of the Mechanical Shut-off Valve (See Fig. 31)
(a)  

Remove the nozzle.

(b) 

Fasten an M5 screw, with a minimum length of 30mm,  into

the threaded hole (A) and pull the screw to withdraw the check valve.

(c) 

Check the nozzle holder is clear of any debris and clean if necessary.

(d) 

Check the three holes in the check valve are clear of any

debris.  Discard the check valve if the holes cannot be cleared or
if the unit is defective and replace with a new one.

(e) 

Reassemble in reverse order.

7. 

It is strongly recommended that the oil atomising nozzle be

replaced at each service. If this is not possible then remove and
clean the integral filter, but under no circumstances should the
nozzle be stripped into its component parts and never attempt
to clean the nozzle tip.

8. 

Check and reset the electrodes, where necessary, as shown in fig. 28.

9. 

Replace the combustion head and check that the nozzle lies

central to the combustion head and the head settings are as
shown in fig. 28.

10. 

Withdraw the photocell from its housing and clean.

11. 

Remove and clean the oil pump internal filter using kerosene

or white spirit. The internal filter is accessed by removing the oil
pump cover on the Suntec AS47C and by unscrewing and with-
drawing the cartridge on the Danfoss BFP 41 as indicated in fig. 10.

12. 

It is recommended that the standard flexible oil lines are

replaced at each yearly service to prevent the possibility of a
leak due to ageing.

13. 

Re-assemble the burner components.

14. 

Check the sponge O-shaped gasket located around the com-

bustion head and replace if necessary. It is imperative that this
seal is in good condition since failure will cause the combustion
gases to be re-circulated into the burner inlet.

14.4 

Remove the paper element from the external oil filter and

replace. If the filter contains a washable element then thoroughly
clean in Kerosene or white spirit and re-assemble into the filter.

14.5 Clean the Boiler.

NOTE:

An electrical service lead can be fitted to the external con-

trol box enabling the service engineer to use a light or vacuum
cleaner.  The electrical service lead is available from Worcester,
Bosch Group as an optional extra, Part Number  7 716 192 301.

1. 

Remove the telescopic flue by releasing the two wing nuts

and washers, check and clean.

2. 

Check the condition of the seals on both the inlet and outlet of

the flue system and replace if necessary.

3. 

Remove the insulation box by releasing the four M8 wing nuts

and washers. Holding the burner-mounting flange, pull the insulation
box out far enough until you can get a hand underneath and remove.
Care must be taken when the insulation box is removed so as not to
cause damage to the insulating material or the external duct. 

4.  

Check the insulation box for any visible defects and replace if

necessary.

5.  

Check the three rope seals as shown in fig. 27 and replace if

necessary.

6.  

Vacuum the inside if the insulation box being careful not to

damage the surface of the insulation.

NOTE: When cleaning the inside of the insulation box it is
imperative that the surface of the insulation is not damaged,
therefore, do not use abrasive tools or cleaning fluids on this
component.

7. 

Remove the baffle, clean and check its condition. Replace baf-

fle if considered to be badly corroded.

8. 

Thoroughly clean all of the heat exchanger surfaces using a

stiff wire brush and vacuum clean all loose debris from the com-
bustion chamber. 

9.  

Replace the items in reverse order noting the baffle position

shown in fig. 26.

14.7 Fire Valve. 

Check that a fire valve is fitted to the incoming oil line with the
body located at a minimum distance of 1 metre away from the
appliance and the detection element is located within the exter-
nal duct next to the burner. Two inline fire valve clips are provided

14. Routine Cleaning and Inspection

28

Содержание WM 12

Страница 1: ...FIRED PRESSURE JET APPLIANCE INSTALLATION AND SERVICING INSTRUCTIONS BOILER OUTPUT Hot Water and Central Heating MINIMUM 12 kW 41 000 Btu h MAXIMUM 19 kW 65 000 Btu h THESE INSTRUCTIONS APPLY TO UK M...

Страница 2: ...all with wall thickness ranging from 102 mm 4 inches to 460 mm 18 inches When installing the appliance on a 102mm 4inch wall the 4inch Standoff Kit must be used The stand off kit reduces the distance...

Страница 3: ...5 1 76 2 23 230 11 5 9 21 1 72 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 12 19 Table 2 Electro Oil Inter B9C Burner See Fig 28 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate...

Страница 4: ...at Phial retaining spring Frost thermostat 4 Remote lockout reset button Internal control box Thermostat Knob Wall mounting duct Optional programmer position Cabinet 1 7 5 2 4 3 6 1 Wall mounting brac...

Страница 5: ...m locking screw Burner hanging bracket Burner mounting flange Burner O shaped gasket Burner Burner Electrical plug lead Burner retaining screw Flue splash plate seal Telescopic flue Flue gasket Telesc...

Страница 6: ...n 130mm 70mm 55mm 315mm 315mm 315mm 102mm 4 inch wall with stand off kit 229mm 9 inch wall 296mm 12 inch wall 460mm 18 inch wall NOTE For cabinets set at the optional 285mm position excluding 102 and...

Страница 7: ...the split pin from the thermostat phial pocket located in the front right hand side of the boiler Carefully withdraw the control and automatic high limit thermostats from the pocket noting their posit...

Страница 8: ...gut ter or painted eaves then an aluminium or stainless steel shield at least 750mm long should be fitted to protect the surface 5 If a terminal is fitted less than 2 metres above a surface to which...

Страница 9: ...al facing the terminal 1200 K Vertically from a terminal on the same wall 1500 L Horizontally from a terminal on the same wall 750 NOTE Flue outlet is shown in fig 6 and7 9 L F F K G A E B C D H J NOT...

Страница 10: ...il tank is positioned below the burner An inlet and return loop should be created between the de aerator and oil pump De aerators should be fitted externally to the appliance 8 8 The oil supply pipe d...

Страница 11: ...5 Double pipe sub gravity feed system MAXIMUM ALLOWABLE PIPE RUN HEAD metres metres 8 mm inside dia pipe 10 mm inside dia pipe 10 mm O D copper 12 mm O D copper 0 35 100 0 5 30 100 1 0 25 100 1 5 20 8...

Страница 12: ...Expansion System The feed and expansion pipes must rise continuously from the appliance and must be of the minimum diameter shown in fig 12 The cistern must be arranged to provide a minimum static he...

Страница 13: ...t Domestic hot water cylinder Pressure gauge Safety valve To system filling device see fig 14 Fig 14 System filling and make up Heating return Non return valve Non return valve Test cock Temporary hos...

Страница 14: ...tor circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water cir cul...

Страница 15: ...w green yellow brown brown brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 green yellow brown orange brown brown green yellow blue white grey Time clock white connector brown orange violet 7 8 9...

Страница 16: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Страница 17: ...rmostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 brown E N N 1 10 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No 42002116 001 Wall mounting duct Control box earth rivet...

Страница 18: ...E E N 1 1 2 3 4 5 6 7 8 9 10 C 1 Boiler frost thermostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 orange E N 1 N 6 4 10 7 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No...

Страница 19: ...mount ed programmer do not wire in this time con troller Wire as shown in Fig 18 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 2 C white V4073A Mid position zone valve 1 N...

Страница 20: ...thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of the fa...

Страница 21: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Страница 22: ...time con troller Wire as shown in Fig 21 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 C V4043H Hot water zone valve 1 N E 4 5 6 7 8 9 10 L N HTG HW Optional frost thermo...

Страница 23: ...l box and wall mounting duct See fig 25 13 Remove the internal control box by undoing the two screws holding the facia to the internal control box and pivot the facia down 14 There is an earth loom th...

Страница 24: ...to pre vent oil or combustion gases entering the wall cavity in the event of a leakage 11 Slide the internal control box back into position ensuring the wall mounting duct earth lead is connected back...

Страница 25: ...n the wall mounting duct to the external duct 2 No 6 locking screws 3 Completely seal the joint on all four sides between the wall mounting duct and the external duct with the sealant provided 4 Exter...

Страница 26: ...en the main oil supply valve at the tank and check for any leaks 4 Remove the flexible oil line from the inlet of the oil pump and place in a suitable container Open the isolating valve between the oi...

Страница 27: ...equence is theninitiated Repeattheprocedureuntilaflameisestablished Note Persistent lockout when running indicates a fault and a Service Engineer should be consulted 12 12 Run the boiler for approxima...

Страница 28: ...alve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Reassemble in reverse order 7 It is strongly recommended th...

Страница 29: ...the inlet to the oil pump goes to the inlet on the connection block and the flexible oil line on the return of the oil pump goes to the return on the connection block 2 With the sponge O shaped gasket...

Страница 30: ...cal shut off valve Fig 29 Service switch positions Service Off Run Note Always set the switch to run after servicing Fig 30 Hanging of burner during commissioning service Fire valve clips Burner hangi...

Страница 31: ...nsformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical shut off valve 1 8 716 156 658 0 Flexible oil line kit Worcester 1 8 716 157 033 0 Main harness service switch assembly Worces...

Страница 32: ...ats Programmer open circuit Check by linking 7 and 9 on the connector Faulty control box Replace if necessary Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace...

Страница 33: ...33...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 114 741a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Wo...

Страница 37: ...37...

Отзывы: