Worcester WM 12 Скачать руководство пользователя страница 26

22.

Insert the baffle into the heat exchanger ensuring the baffle is

pushed hard against the back of the heat exchanger (see fig. 26).

23.

Check the three rope seals in the insulation box as shown in

fig. 27, adjust if necessary or replace if damaged. Push the insula-
tion box on to the heatexhanger and tighten up using the four
M8 wing nuts and washers provided.

24. 

Insert the burner into the burner-mounting flange. 

25.

Remove the wall trim and pack the gaps between the outside

wall and external duct with cement.  Refit the wall trim as described
previously making any necessary adjustments to ensure the trim is
a tight fit around the external duct before the cement sets. It is
recomended that a bead of silicone sealant is applied around the
duct to the cement joint before fitting the wall trim.  If required apply
silicone sealant to the back of the wall trim to aid fixing to the wall.

26.

Pack the gaps between the inside wall and the wall mounting

duct with cement. 

11.4 Heating system installation.

1.

Plumb the boiler into the central heating system. 

2.

Fill the system and vent all radiators and high points to

remove air from the system.

3.

Check the boiler and all pipework connections for leaks.

4.

The primary system should be flushed and treated in accordance

with the recommendations of BS 7593:1992.

11.5  Oil supply installation

(See figs. 9 to 11)

(a) Double pipe system

1.

Disconnect the two flexible lines from each other and remove

the 

1

/

4

inch nipple.  Connect the two 

1

/

4

inch nipples and copper

washers to the connection block.  Ensure the conical end pro-
trudes from the connection block. Connect the flexible oil line
that is connected to inlet on the oil pump to the 

1

/

4

inch male inlet

fitting on the connection block.  Connect the flexible oil line that
is connected to return on the oil pump to the 

1

/

4

inch male return

fitting on the  connection  block. (See fig. 11)

2.

The oil pipes from the oil supply tank should be routed tidily

up the external wall of the property and connected into the con-
nection block.  The connection block has two  female 

1

/

4

inch BSP

fittings for connection to either a 10mm or 12mm compression
to 

1

/

4

inch BSP mail fitting.  

Note:

On a double pipe system it generally not possible to check for

leaks due to the position of the oil supply tank,  therefore,  use the oil
pump as described in Section 12 and remove and clean the oil
pump filter to remove any debris collected as a result of installation.

(b) Single pipe system

1.

Disconnect the two flexible lines from each other and remove

the 

1

/

4

inch nipple.  Remove the flexible oil line which is connected

to the return on the oil pump and convert the burner to a single
pipe system, see fig. 10 (Section 8 Oil Supply).  Insert the 

1

/

4

inch

plug into the return port on the oil pump.  Connect the 

1

/

4

inch

nipple and copper washer to the inlet on the connection block.
Ensure the conical end protrudes from the connection block.
Connect the flexible oil line which is connected to inlet of the oil
pump to the 

1

/

4

inch male inlet fitting on the  connection  block.

2.

The oil pipe from the oil supply tank should be routed tidily  up

the external wall of the property and connected into the connec-
tion block.  The connection block has two female 

1

/

4

inch fittings

for connection to either 10mm or 12mm compression to 

1

/

4

inch

mail fitting.  Ensure the oil pipe from the oil supply tank is con-
nected to the inlet connection only on a single pipe system.

3.

Open the main oil supply valve at the tank and check for any leaks. 

4.

Remove the flexible oil line from the inlet of the oil pump and

place in a suitable container.  Open the isolating valve between
the oil filter and burner. 

5

.   Draw off at least 2.5 litres of oil until a steady flow of clear

uncontaminated oil can be seen and turn off the isolating valve.

Note:

never use soldered joints on oil supply pipes as this could

cause a hazard in the case of a fire.

11.6 Flue Installation

1.

Attach the telescopic flue to the insulation box with the two

wing nuts and washers.

2.

Set the approximate flue length by sliding the flue locating slot

onto the tab which protrudes from the external duct.

3.

Fit the external cover and insert two fixing screws and wash-

ers, do not tighten.

4.

Adjust the flue so the end protrudes through the external

cover ensuring the seal and splash plate are hard up against the
external cover to prevent water ingress (see fig. 7).

5.

Remove the external cover being careful not to knock the flue.

6.

Tighten the telescopic section of the flue and re-fit the external

cover onto the appliance.

7.

Check to see the flue protrudes through the cover, ensuring the

seal and splash plate are hard up against the external cover to pre-
vent water ingress and make any necessary adjustments (see fig. 7).

Note.

Ensure the splash plate/seal on the end of the flue is hard

up against the external cover. Ensure the tab on the external
duct protrudes through the locating slot.

8.

Remove the external cover and remove the complete flue sys-

tem by undoing the two wing nuts and washers holding the flue
to the insulation box.

9.

Using the sealant provided seal the two sections of flue togeth-

er all the way round to prevent the recirculation of flue gases
from the flue to the burner inlet.

10.

Attach the telescopic flue to the insulation box with two wing

nuts/washers and make any necessary adjustments before the sealant sets.

WARNING: This appliance is serviced and repaired externally.
External equipment operated at 230volts should not be ser-
viced or repaired under adverse weather conditions.

Ensure that no foreign matter is left in the system as this could

cause damage to the appliance.

12.1

Check that the electrical supply to the appliance is

switched off.

12.2

When commissioning the appliance after initial installation

follow the procedure from 12.3, otherwise remove the burner
first as described in Section 14.3. 

12.3 Prepare the heating system

1. After initial installation and checking for leaks, as previously
described, drain down the system sufficiently to add a flushing
agent. Flush the system in accordance with BS 7593:1992.

2.

Refill the system.

12.4 Check the installation

1.

Check the appliance is correctly wired as described in Section 10.

2.

Check the baffle is correctly located making sure it is pushed

hard up against the back of the heat exchanger as shown in fig. 26.

5.

Ensure the rope seals are in good condition (see fig. 27) and the insula-

tion box is mounted correctly onto the heat exchanger, as shown in fig. 3.

6.

Check the control thermostat and auto reset high limit ther-

mostat phials are correctly located in the boiler thermostat
pocket positioned in the top right hand side of the boiler (see fig. 2).

7.

Check the manual reset limit thermostat is located in the phial

retaining spring on the top left hand side of the heatexhanger (see fig. 2).

8.

Check the Duct thermostat is located in the phial retaining

spring on the top of the wall mounting duct as shown in fig. 2.

9.

Check the frost thermostat is located in the phial retaining

spring on the bottom left hand side of the heatexhanger (see fig. 2).

12. Commissioning the Appliance

26

Содержание WM 12

Страница 1: ...FIRED PRESSURE JET APPLIANCE INSTALLATION AND SERVICING INSTRUCTIONS BOILER OUTPUT Hot Water and Central Heating MINIMUM 12 kW 41 000 Btu h MAXIMUM 19 kW 65 000 Btu h THESE INSTRUCTIONS APPLY TO UK M...

Страница 2: ...all with wall thickness ranging from 102 mm 4 inches to 460 mm 18 inches When installing the appliance on a 102mm 4inch wall the 4inch Standoff Kit must be used The stand off kit reduces the distance...

Страница 3: ...5 1 76 2 23 230 11 5 9 21 1 72 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 12 19 Table 2 Electro Oil Inter B9C Burner See Fig 28 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate...

Страница 4: ...at Phial retaining spring Frost thermostat 4 Remote lockout reset button Internal control box Thermostat Knob Wall mounting duct Optional programmer position Cabinet 1 7 5 2 4 3 6 1 Wall mounting brac...

Страница 5: ...m locking screw Burner hanging bracket Burner mounting flange Burner O shaped gasket Burner Burner Electrical plug lead Burner retaining screw Flue splash plate seal Telescopic flue Flue gasket Telesc...

Страница 6: ...n 130mm 70mm 55mm 315mm 315mm 315mm 102mm 4 inch wall with stand off kit 229mm 9 inch wall 296mm 12 inch wall 460mm 18 inch wall NOTE For cabinets set at the optional 285mm position excluding 102 and...

Страница 7: ...the split pin from the thermostat phial pocket located in the front right hand side of the boiler Carefully withdraw the control and automatic high limit thermostats from the pocket noting their posit...

Страница 8: ...gut ter or painted eaves then an aluminium or stainless steel shield at least 750mm long should be fitted to protect the surface 5 If a terminal is fitted less than 2 metres above a surface to which...

Страница 9: ...al facing the terminal 1200 K Vertically from a terminal on the same wall 1500 L Horizontally from a terminal on the same wall 750 NOTE Flue outlet is shown in fig 6 and7 9 L F F K G A E B C D H J NOT...

Страница 10: ...il tank is positioned below the burner An inlet and return loop should be created between the de aerator and oil pump De aerators should be fitted externally to the appliance 8 8 The oil supply pipe d...

Страница 11: ...5 Double pipe sub gravity feed system MAXIMUM ALLOWABLE PIPE RUN HEAD metres metres 8 mm inside dia pipe 10 mm inside dia pipe 10 mm O D copper 12 mm O D copper 0 35 100 0 5 30 100 1 0 25 100 1 5 20 8...

Страница 12: ...Expansion System The feed and expansion pipes must rise continuously from the appliance and must be of the minimum diameter shown in fig 12 The cistern must be arranged to provide a minimum static he...

Страница 13: ...t Domestic hot water cylinder Pressure gauge Safety valve To system filling device see fig 14 Fig 14 System filling and make up Heating return Non return valve Non return valve Test cock Temporary hos...

Страница 14: ...tor circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water cir cul...

Страница 15: ...w green yellow brown brown brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 green yellow brown orange brown brown green yellow blue white grey Time clock white connector brown orange violet 7 8 9...

Страница 16: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Страница 17: ...rmostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 brown E N N 1 10 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No 42002116 001 Wall mounting duct Control box earth rivet...

Страница 18: ...E E N 1 1 2 3 4 5 6 7 8 9 10 C 1 Boiler frost thermostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 orange E N 1 N 6 4 10 7 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No...

Страница 19: ...mount ed programmer do not wire in this time con troller Wire as shown in Fig 18 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 2 C white V4073A Mid position zone valve 1 N...

Страница 20: ...thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of the fa...

Страница 21: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Страница 22: ...time con troller Wire as shown in Fig 21 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 C V4043H Hot water zone valve 1 N E 4 5 6 7 8 9 10 L N HTG HW Optional frost thermo...

Страница 23: ...l box and wall mounting duct See fig 25 13 Remove the internal control box by undoing the two screws holding the facia to the internal control box and pivot the facia down 14 There is an earth loom th...

Страница 24: ...to pre vent oil or combustion gases entering the wall cavity in the event of a leakage 11 Slide the internal control box back into position ensuring the wall mounting duct earth lead is connected back...

Страница 25: ...n the wall mounting duct to the external duct 2 No 6 locking screws 3 Completely seal the joint on all four sides between the wall mounting duct and the external duct with the sealant provided 4 Exter...

Страница 26: ...en the main oil supply valve at the tank and check for any leaks 4 Remove the flexible oil line from the inlet of the oil pump and place in a suitable container Open the isolating valve between the oi...

Страница 27: ...equence is theninitiated Repeattheprocedureuntilaflameisestablished Note Persistent lockout when running indicates a fault and a Service Engineer should be consulted 12 12 Run the boiler for approxima...

Страница 28: ...alve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Reassemble in reverse order 7 It is strongly recommended th...

Страница 29: ...the inlet to the oil pump goes to the inlet on the connection block and the flexible oil line on the return of the oil pump goes to the return on the connection block 2 With the sponge O shaped gasket...

Страница 30: ...cal shut off valve Fig 29 Service switch positions Service Off Run Note Always set the switch to run after servicing Fig 30 Hanging of burner during commissioning service Fire valve clips Burner hangi...

Страница 31: ...nsformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical shut off valve 1 8 716 156 658 0 Flexible oil line kit Worcester 1 8 716 157 033 0 Main harness service switch assembly Worces...

Страница 32: ...ats Programmer open circuit Check by linking 7 and 9 on the connector Faulty control box Replace if necessary Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace...

Страница 33: ...33...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 114 741a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Wo...

Страница 37: ...37...

Отзывы: