Worcester WM 12 Скачать руководство пользователя страница 27

10.

Check all of the air-ways to the burner are clear of any

obstruction.

12.5  Check the Burner

1.

Hang the burner on the burner hanging bracket situated on

the bottom left hand side of the external duct (see fig. 30).

2.

Check the nozzle and electrode settings are correct for the

burner (see fig. 28).

3.

Check the nozzle lies central with the combustion head hole.

4.

Check for any visible defects.

12.6  Replace the burner

1.

Check the burner flexible oil lines are connected correctly to

the connection block,  as shown in figs 9 to 11and in Section
11.5 Oil supply installation.

2.

With the sponge O-shaped gasket around the burner blast

tube insert the burner into the burner mounting flange ensuring
the cut out in the gasket lines up with the burner retaining screw.
Push the burner firmly forward to compress the gasket and
tighten the burner retaining screw located to the left of the burn-
er control box using a 4mm hexagon driver.

Note:

It is important that a good seal is made between the burn-

er and the boiler to prevent re-circulation of flue gases from the
combustion chamber to the burner inlet.

3.

Re-connect the burner electrical plug lead into the external con-

trol box.

12.7

Fit a pressure gauge and manifold to the burner pump at

the point indicated in Fig. 10.

12.8

Switch the service switch to the ‘OFF’ position (see fig. 29).

12.9

Turn on the electricity to the appliance.

12.10 Bleed the burner

Two Pipe System

A two pipe system will automatically vent the air back to the oil
tank but it is recommended to use the single pipe system
method of bleeding the burner as descibed below to quicken the
removal of air from the inlet oil line. Set the programmer to

heating and hot water

and turn on the boiler thermostat.

Switch the service switch to ‘RUN’ position as shown in fig. 29
and allow the burner to run through to lockout. Reset the burner
control box and repeat the procedure until the burner fires and
runs in a steady state. This may take several attempts depending
on the oil pipe length and height.

Single pipe systems only

Release the fuel bleed port on the manifold and place a suitable
receptacle beneath.  Set the programmer to 

heating and hot

water

and turn on the boiler thermostat.  Switch the service switch

to ‘RUN’ position as shown in fig. 29 and allow the burner to run
through to lockout. Reset the burner control box and  repeat the
procedure at least three times or until a steady stream of oil, with-
out air, is exhausted from the bleed port. Re-lock the bleed port.

12.11

Adjust the air shutter and pump pressure to the settings recom-

mended in Table 2. After a pre-ignition period of approximately 15 sec-
onds the burner should ignite. Flame sensing is carried out by means of
a photocell mounted in the burner body. Should the boiler fail to estab-
lish a normal firing pattern (or should flame failure occur during run-
ning), the absence of a flame is sensed and the control box is monitored
to a safe lockout condition and the boiler is shut down. The lockout
indicator light in the boiler control panel will illuminate and the reset
button on the burner control box will continue flashing indicating that
the burner has gone to lockout. In this instance press the lockout reset
button mounted in the burner control box. Another start sequence is
then initiated. Repeat the procedure until a flame is established.

Note:

Persistent lockout when running indicates a fault and a

Service Engineer should be consulted.

12.12

Run the boiler for approximately 3 minutes and switch

off using the service switch checking that there is no after-spurt-
ing from the nozzle. This can be detected by oil saturation on
the blast tube. If after-spurting occurs remove the burner from
the boiler, unscrew the nozzle, and while holding the burner in a
vertical position, fill the nozzle holder with oil. Refit the burner
and continue to run the boiler for three minute periods until
after-spurting stops.

12.13

Run the boiler for a further 15 minute period and then final-

ly fine tune the air shutter setting to give the CO

2

level specified in

Table 2  less 0.5% CO

2

. During this period some smoke will be emit-

ted due to the burning of the organic binder in the insulation box.
Smoke readings will therefore be inaccurate at this point.

Note:

Flue gas sampling is taken with the probe or smoke pump

positioned in the flue centrally by approximately 150mm.

12.14

Check that the smoke reading is in the range 0-1. If this

cannot be achieved then check that the burner head is set cor-
rectly and the nozzle is in good condition.

12.15

Check that the flue temperature does not exceed the

value specified in Table 2. If this is the case then check that the
baffle is correctly located. If the baffle is correctly located then
reduce the pump pressure since nozzle variations of up
to+or–15% may occur.

12.16

Remove the oil pressure gauge and manifold and check

all oil system joints for any signs of leakage.

NOTE:

Check that the oil hoses do not touch hot surfaces.

12.17

Refit the external cover in reverse order to that described

in Section 5.

12.18

Allow the burner to run for a further five minutes and

then recheck the CO

2

level and adjust the air setting if required. 

12.19

When the heating circuit has reached full operating tem-

perature check the whole system for any leaks.

12.20

Refit the cabinet inside the property in reverse order to

that described in Section 5.

12.21 Locking the Boiler

Provision has been made to lock the external cover to the burn-
er hanging bracket using a padlock. A suitable padlock is the
P73 manufactured by Yale Security Products, or use a padlock
which has 20 to 22mm between the two centres on the shackle
and 15 to 20mm between the body and inside of the shackle. A
slot and hole have been provided underneath the external cover
to fasten the cover using a padlock.

NOTE:

After commissioning the appliance the engineer should

position the service switch in the 

RUN

position as shown in fig. 29.

13.1 

Hand the users instructions to the user or purchaser for

retention and instruct them in the efficient and safe operation of
the appliance and the heating/hot water system.

13.2 

Advise the user or purchaser of the precautions necessary

to prevent damage to the heating/hot water system and to the
building in the event of the heating system remaining inopera-
tive during frost conditions.

13.3 

Finally advise the user or purchaser that for continued efficient

and safe operation of the appliance it is important that adequate
servicing is carried out by a qualified engineer at least once per year.

13.4 

Worcester, Bosch Group will be pleased to discuss and

offer a comprehensive maintenance contract.

Set the system controls to the users requirements.

13. Instructions to the User

27

Содержание WM 12

Страница 1: ...FIRED PRESSURE JET APPLIANCE INSTALLATION AND SERVICING INSTRUCTIONS BOILER OUTPUT Hot Water and Central Heating MINIMUM 12 kW 41 000 Btu h MAXIMUM 19 kW 65 000 Btu h THESE INSTRUCTIONS APPLY TO UK M...

Страница 2: ...all with wall thickness ranging from 102 mm 4 inches to 460 mm 18 inches When installing the appliance on a 102mm 4inch wall the 4inch Standoff Kit must be used The stand off kit reduces the distance...

Страница 3: ...5 1 76 2 23 230 11 5 9 21 1 72 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 12 19 Table 2 Electro Oil Inter B9C Burner See Fig 28 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate...

Страница 4: ...at Phial retaining spring Frost thermostat 4 Remote lockout reset button Internal control box Thermostat Knob Wall mounting duct Optional programmer position Cabinet 1 7 5 2 4 3 6 1 Wall mounting brac...

Страница 5: ...m locking screw Burner hanging bracket Burner mounting flange Burner O shaped gasket Burner Burner Electrical plug lead Burner retaining screw Flue splash plate seal Telescopic flue Flue gasket Telesc...

Страница 6: ...n 130mm 70mm 55mm 315mm 315mm 315mm 102mm 4 inch wall with stand off kit 229mm 9 inch wall 296mm 12 inch wall 460mm 18 inch wall NOTE For cabinets set at the optional 285mm position excluding 102 and...

Страница 7: ...the split pin from the thermostat phial pocket located in the front right hand side of the boiler Carefully withdraw the control and automatic high limit thermostats from the pocket noting their posit...

Страница 8: ...gut ter or painted eaves then an aluminium or stainless steel shield at least 750mm long should be fitted to protect the surface 5 If a terminal is fitted less than 2 metres above a surface to which...

Страница 9: ...al facing the terminal 1200 K Vertically from a terminal on the same wall 1500 L Horizontally from a terminal on the same wall 750 NOTE Flue outlet is shown in fig 6 and7 9 L F F K G A E B C D H J NOT...

Страница 10: ...il tank is positioned below the burner An inlet and return loop should be created between the de aerator and oil pump De aerators should be fitted externally to the appliance 8 8 The oil supply pipe d...

Страница 11: ...5 Double pipe sub gravity feed system MAXIMUM ALLOWABLE PIPE RUN HEAD metres metres 8 mm inside dia pipe 10 mm inside dia pipe 10 mm O D copper 12 mm O D copper 0 35 100 0 5 30 100 1 0 25 100 1 5 20 8...

Страница 12: ...Expansion System The feed and expansion pipes must rise continuously from the appliance and must be of the minimum diameter shown in fig 12 The cistern must be arranged to provide a minimum static he...

Страница 13: ...t Domestic hot water cylinder Pressure gauge Safety valve To system filling device see fig 14 Fig 14 System filling and make up Heating return Non return valve Non return valve Test cock Temporary hos...

Страница 14: ...tor circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water cir cul...

Страница 15: ...w green yellow brown brown brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 green yellow brown orange brown brown green yellow blue white grey Time clock white connector brown orange violet 7 8 9...

Страница 16: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Страница 17: ...rmostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 brown E N N 1 10 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No 42002116 001 Wall mounting duct Control box earth rivet...

Страница 18: ...E E N 1 1 2 3 4 5 6 7 8 9 10 C 1 Boiler frost thermostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 orange E N 1 N 6 4 10 7 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No...

Страница 19: ...mount ed programmer do not wire in this time con troller Wire as shown in Fig 18 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 2 C white V4073A Mid position zone valve 1 N...

Страница 20: ...thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of the fa...

Страница 21: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Страница 22: ...time con troller Wire as shown in Fig 21 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 C V4043H Hot water zone valve 1 N E 4 5 6 7 8 9 10 L N HTG HW Optional frost thermo...

Страница 23: ...l box and wall mounting duct See fig 25 13 Remove the internal control box by undoing the two screws holding the facia to the internal control box and pivot the facia down 14 There is an earth loom th...

Страница 24: ...to pre vent oil or combustion gases entering the wall cavity in the event of a leakage 11 Slide the internal control box back into position ensuring the wall mounting duct earth lead is connected back...

Страница 25: ...n the wall mounting duct to the external duct 2 No 6 locking screws 3 Completely seal the joint on all four sides between the wall mounting duct and the external duct with the sealant provided 4 Exter...

Страница 26: ...en the main oil supply valve at the tank and check for any leaks 4 Remove the flexible oil line from the inlet of the oil pump and place in a suitable container Open the isolating valve between the oi...

Страница 27: ...equence is theninitiated Repeattheprocedureuntilaflameisestablished Note Persistent lockout when running indicates a fault and a Service Engineer should be consulted 12 12 Run the boiler for approxima...

Страница 28: ...alve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Reassemble in reverse order 7 It is strongly recommended th...

Страница 29: ...the inlet to the oil pump goes to the inlet on the connection block and the flexible oil line on the return of the oil pump goes to the return on the connection block 2 With the sponge O shaped gasket...

Страница 30: ...cal shut off valve Fig 29 Service switch positions Service Off Run Note Always set the switch to run after servicing Fig 30 Hanging of burner during commissioning service Fire valve clips Burner hangi...

Страница 31: ...nsformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical shut off valve 1 8 716 156 658 0 Flexible oil line kit Worcester 1 8 716 157 033 0 Main harness service switch assembly Worces...

Страница 32: ...ats Programmer open circuit Check by linking 7 and 9 on the connector Faulty control box Replace if necessary Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace...

Страница 33: ...33...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 114 741a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Wo...

Страница 37: ...37...

Отзывы: