COMMISSIONING
6 720 648 726 (2011/07)
56
B
Connect the multimeter in series. Select the
μ
A DC
range on the multimeter. The multimeter must have a
resolution of at least 1
μ
A.
Fig. 93 Measuring the ionisation current
B
Switch on the heating system by pressing the mains
switch of the BC10 basic controller (
Æ
B
Activate the Service mode in accordance with the
"Service mode" menu (
Æ
B
Set the capacity to minimum (part load) according to
the "Service mode" menu (
Æ
B
After the "Burner" LED (
Æ
fig. 90, [6]) has lit up wait
for one minute until the boiler is burning at part load.
B
Measure the ionisation current. The ionisation current
must be > 5
μ
A DC at part load operation.
B
Enter the result in the commissioning log book
(
Æ
section 10.5 "Commissioning record log book",
B
If the result is not as it should be, check the gas/air
ratio (
Æ
section 10.2.7, page 52) or check the
ionisation electrode (
Æ
section 13.2.4, page 66).
B
Press and hold the "Chimney sweep" button
(
Æ
fig. 90, [3]) (approx. two seconds), until the dot in
the right-hand bottom corner of the display
(
Æ
fig. 90, [9]) appears. See also table 10, "Flue gas
test", page 42.
B
Switch off the heating system by pressing the mains
switch of the BC10 basic controller
Æ
fig. 90, [1]).
B
Remove the multimeter and reconnect the monitoring
cable.
B
Switch on the heating system by pressing the mains
switch of the BC10 basic controller (
Æ
B
Check that the boiler performance is still at the
required value. See the "Service mode" menu
(
Æ
table 11, page 43).
10.3 BOILER SETTINGS
10.3.1 SETTING THE HEATING CAPACITY
B
Set the required heating capacity on the BC10
according to the "Settings" menu (
Æ
page 45). See table 16 when making these settings.
6 720 648 726-093.1TD
Display
indication
[%]
Rated heating capacity at 40/30 °C [kW]
GB162-65
GB162-80
GB162-100
L20
15.6
–
21.1
L25
18.7
21.1
26.0
L30
21.8
25.3
30.9
L35
24.9
29.6
35.8
L40
28.0
33.8
40.7
L45
31.1
38.0
45.8
L50
34.2
42.2
50.5
L55
37.3
46.5
55.4
L60
40.4
50.7
60.3
L65
43.5
54.9
65.2
L70
46.6
59.1
70.1
L75
49.7
63.4
75.0
L80
52.8 (
1)
50)
1) Capacity at BC10 basic controller with removed jumper
67.6
79.9
L85
50)
71.8
84.8
L90
50)
76.0
89.7
L95
50)
80.3
94.6
L--
50)
84.5
99.5
Table 16 Heating capacity in kW (as a percentage)