background image

Manual MRR1 GB 

Woodward 

DOK-TD-MRR1 Rev.A 

19 

6.4.5  Checking the pickup value and reset value  

 
For testing these values a current smaller than the adjusted pickup value has to be injected (ter-
minals B1 - B2). The current is now to be increased until the relay picks up, which is indicated by 
lighting up of LEDs le and le>. At the same time the output relay selected by the parameter setting 
mode (see chapter 5.3.2) trips. The value shown at the ammeter must not vary more than  
2 % from the adjusted pickup value of the MRR1. The resetting value is ascertained by slowly de-
creasing the test current until the output relay re-leases. Check that the resetting current is 0.98 
times smaller than the operating current. This method is also to be used for the insulation  
measuring circuit.  
 

6.4.6  Checking the tripping delay 

 
For checking the tripping delay a timer is to be connected to the trip output relay contact. The timer 
should be started simultaneously with the test current injection in the current input circuit and 
stopped at the instant the relay trips. The test cur-rent should be 1.5 times the operating current. 
The tripping delay measured by the timer should not vary more than 3 % or less than 150ms from 
the adjusted tripping delay. 
 
For checking the insulation measuring circuit the same method can be used. The permissible  
tolerance for this is 3 % or less than 1s from the adjusted tripping delay. 
 

6.5  Real injection test 

 
Generally, a test with real exciter current could be carried out in the similar manner as the injection 
test with current sources above described. Since the cost and potential hazards are very high for 
such a test, especially if staged fault tests are in-tended, these tests are usually limited to very  
important protective relays in the power system. 
Because of its powerful combined indicating and measuring functions, you have still the possibili-
ties to test the MRR1 relay in the manner of a primary injection without extra expenditures and time 
consumption. 
In actual service, for example, the measured cur-rent values may be compared with the ammeter 
on the switch-board panel to verify that the relay works and measures correctly. 
 

6.6 Maintenance 

 
Maintenance testing is generally done on site at regular intervals. These intervals vary among us-
ers depending on many factors: e.g. the type of protective relays employed; the importance of the 
primary equipment being protected; the user's past experience with the relay, etc. 
 
For electromechanical or static relays, maintenance testing will be performed at least once a year 
according to the experiences. For digital re-lays like MRR1, this interval can be substantially longer. 
This is because: 
 

 

The MR-relays are equipped with very wide self-supervision functions, so that many faults 

 

in the relay can be detected and signalized during ser-vice. Important: The self-supervision 

 

output relay must be connected to a central alarm panel! 

 

The combined measuring functions of MR-relays enable supervision the relay functions 

 during 

service. 

 

The combined TRIP test function of the MR-relay allows to test the relay output circuits. 

 
A testing interval of two years for maintenance will, therefore, be recommended. 
During a maintenance test, the relay functions including the operating values and relay tripping 
times should be tested. 
 

 

Содержание MRR1

Страница 1: ...MRR1 Multifunctional Generator Rotor Protection Relay Manual MRR1 Revision A...

Страница 2: ...the right to update any portion of this publication at any time Information provided by Woodward Governor Company is believed to be correct and reliable However no responsibility is as sumed by Woodw...

Страница 3: ...tive functions and assignment of the output relays 15 5 3 1 Blocking of protective functions 15 5 3 2 Assignment of the output relays 16 6 Relay testing and commissioning 17 6 1 Power On 17 6 2 Testin...

Страница 4: ...ver current and ripple detection for diode failure protection 2 Features and characteristics Besides features described in the general MR description MRR1 provides Detection of high impedance earth fa...

Страница 5: ...by relay 5 The relays are allocated to the following contacts Output relay 1 C1 D1 E1 and C2 D2 E2 Output relay 2 C3 D3 E3 and C4 D4 E4 Output relay 3 C5 D5 E5 Output relay 4 C6 D6 E6 Output relay 5 S...

Страница 6: ...Tripping time for insulation resistance trip element s tR red Setting for excitation undercurrent element A Ie green Delay time setting for excitation undercurrent element s tIe red Setting for excita...

Страница 7: ...e LEDs beyond the push button SELECT RESET are lit green during setting and inquiry pro cedure of the setting values which are printed on the left side next to the LEDs The LEDs will light up red afte...

Страница 8: ...or earth ref to connection diagram The low frequency of the test voltage is used to avoid malfunction due to the field to earth capacitance CE which can reach values up to 1 F on large generators The...

Страница 9: ...Manual MRR1 GB Woodward DOK TD MRR1 Rev A 9 Figure 4 2 explains the measuring principle Figure 4 2 Measuring principle...

Страница 10: ...system Table 4 1 Effects of different failures Excitation current supervision The excitation current supervision comprises of three elements under and over current and ripple component measurement Th...

Страница 11: ...ula 100 Typical values for Ir All diodes all right Ir 15 20 One diode open Ir 110 One diode short Ir 200 The setting of Ir should be chosen at about 40 to 50 The tripping time tIr should be instanta n...

Страница 12: ...the display WW appears again Measuring value LED R Insulation resistance green Ie Exciter current green Ir Ripple component of the exciter current green Table 5 1 Measuring values Setting values LED...

Страница 13: ...the pickup value and tripping de lay can be adjusted When the set pickup value is either exceeded or falls below the corresponding LED flashes After elaps of the tripping delay trip of the relay is in...

Страница 14: ...button SELECT RESET for some time approx 3 seconds Electrical reset by applying aux voltage to C8 D8 Software reset software reset has the same effect as the SELECT RESET push button Please also refer...

Страница 15: ...de failure protection By repeatedly pressing the SELECT RESET push button the functions to be blocked are selected one after another The corresponding LED lights up simultaneously The display shows BL...

Страница 16: ...element When the display shows _ _ _ _ no alarm relay is assigned to this element The assignment of output relays 1 4 can be changed by pressing and push buttons The selected assignment can be stored...

Страница 17: ...shows the first part of the software version of the relay e g D08 By pressing the push button TRIP twice the display shows the second part of the software version of the relay e g 4 01 The software ve...

Страница 18: ...t circuit For checking the measuring values a current must be injected terminals B1 B2 which is below the set pickup current of the MRR1 After renewed pressing the SELECT RESET push button measuring v...

Страница 19: ...ources above described Since the cost and potential hazards are very high for such a test especially if staged fault tests are in tended these tests are usually limited to very important protective re...

Страница 20: ...nuous current 20 A DC Nominal current IN 10 A DC measuring range up to 25A DC Power consumption in current circuit 1 VA 7 2 Common data Dropout to pickup ratio 98 Returning time 30ms Minimum operating...

Страница 21: ...value Tripping delay for R tR 1 50 sec EXIT 0 1 0 2 0 5 1 0 3 or 0 2 2 s Pickup value of ex citer undercurrent element Ie EXIT 0 2 20 A 0 05 0 1 0 2 0 5 2 of setting value or 0 01A Tripping delay for...

Страница 22: ...Woodward Manual MRR1 GB 22 DOK TD MRR1 Rev A 7 5 Order Form Rotor earth fault relay MRR1 Housing 12TE 19 rack Flush mounting A D Technical data subject to change without notice...

Страница 23: ...ercurrent element A 0 50 tIe Tripping delay for I s 0 10 Ie Pickup value exciter over current element A 5 00 tIe Tripping delay for I s 0 1 Ir Pickup value for ripple voltage supervision 50 tIr Trippi...

Страница 24: ...ermany Postfach 10 07 55 P O Box D 47884 Kempen Germany Phone 49 0 21 52 145 1 Internet www woodward com Sales Phone 49 0 21 52 145 216 or 342 Telefax 49 0 21 52 145 354 e mail salesEMEA_PGD woodward...

Отзывы: