Woodward 

Manual MRR1 GB 

DOK-TD-MRR1 Rev.A 

1. Introduction  and  application 

 
The generator rotor protection relay MRR1 com-bines rotor earth fault protection, excitation over- 
and undercurrent protection as well as rotating diode failure protection. 
Thus providing a powerful protection regarding the rotor of synchronous generators, covering the 
following ANSI codes: 
 
 

37 

DC undercurrent relay 

 40 

Field 

relay 

 58 

Rectification 

failure 

relay 

 

64 

Ground detector relay 

 

76 

DC over current relay 

 
The MRR1 is recommended for synchronous generators and motors above 1 MVA rating. 
 
The rotor earth fault element detects high- and low resistance earth faults of the rotor winding. It is 
equipped with two stages, one for alarm, one for trip. 
 
The excitation current protection element super-vises the DC excitation current of brushless excitor 
machines. The protective functions are: Undercurrent, over current and ripple detection for diode 
failure protection. 
 

2. Features and characteristics 

 
Besides features described in the general MR-description, MRR1 provides: 
 

 

Detection of high impedance earth faults with a test frequency of 0.5 Hz 

 

Short circuit and overvoltage proof measuring input for the earth fault protection 

 

Excitor current measurement galvanically isolated via Hall-transducer, measuring range  

 

0 to 20 A 

 

Display of insulation resistance 

 

Display of the excitation current 

 

Excitation current over- and undercurrent protection with independent settings for current 

 

and delay time 

 

Detection of diode failures by supervision of the ripple component of the excitation current 

 

Two stage supervision of the rotor insulation resistance with independent settings for  

 

resistance and time delay 

 

Two trip relays, one for excitation under- and over current, one for diode failure detection 

 

Digital inputs for blocking and for remote reset 

 

Programmable function of the blocking input 

 

Programmable assignment of protective functions to output relays 

 

Remote interfacing via RS485 

  

 

Содержание MRR1

Страница 1: ...MRR1 Multifunctional Generator Rotor Protection Relay Manual MRR1 Revision A...

Страница 2: ...the right to update any portion of this publication at any time Information provided by Woodward Governor Company is believed to be correct and reliable However no responsibility is as sumed by Woodw...

Страница 3: ...tive functions and assignment of the output relays 15 5 3 1 Blocking of protective functions 15 5 3 2 Assignment of the output relays 16 6 Relay testing and commissioning 17 6 1 Power On 17 6 2 Testin...

Страница 4: ...ver current and ripple detection for diode failure protection 2 Features and characteristics Besides features described in the general MR description MRR1 provides Detection of high impedance earth fa...

Страница 5: ...by relay 5 The relays are allocated to the following contacts Output relay 1 C1 D1 E1 and C2 D2 E2 Output relay 2 C3 D3 E3 and C4 D4 E4 Output relay 3 C5 D5 E5 Output relay 4 C6 D6 E6 Output relay 5 S...

Страница 6: ...Tripping time for insulation resistance trip element s tR red Setting for excitation undercurrent element A Ie green Delay time setting for excitation undercurrent element s tIe red Setting for excita...

Страница 7: ...e LEDs beyond the push button SELECT RESET are lit green during setting and inquiry pro cedure of the setting values which are printed on the left side next to the LEDs The LEDs will light up red afte...

Страница 8: ...or earth ref to connection diagram The low frequency of the test voltage is used to avoid malfunction due to the field to earth capacitance CE which can reach values up to 1 F on large generators The...

Страница 9: ...Manual MRR1 GB Woodward DOK TD MRR1 Rev A 9 Figure 4 2 explains the measuring principle Figure 4 2 Measuring principle...

Страница 10: ...system Table 4 1 Effects of different failures Excitation current supervision The excitation current supervision comprises of three elements under and over current and ripple component measurement Th...

Страница 11: ...ula 100 Typical values for Ir All diodes all right Ir 15 20 One diode open Ir 110 One diode short Ir 200 The setting of Ir should be chosen at about 40 to 50 The tripping time tIr should be instanta n...

Страница 12: ...the display WW appears again Measuring value LED R Insulation resistance green Ie Exciter current green Ir Ripple component of the exciter current green Table 5 1 Measuring values Setting values LED...

Страница 13: ...the pickup value and tripping de lay can be adjusted When the set pickup value is either exceeded or falls below the corresponding LED flashes After elaps of the tripping delay trip of the relay is in...

Страница 14: ...button SELECT RESET for some time approx 3 seconds Electrical reset by applying aux voltage to C8 D8 Software reset software reset has the same effect as the SELECT RESET push button Please also refer...

Страница 15: ...de failure protection By repeatedly pressing the SELECT RESET push button the functions to be blocked are selected one after another The corresponding LED lights up simultaneously The display shows BL...

Страница 16: ...element When the display shows _ _ _ _ no alarm relay is assigned to this element The assignment of output relays 1 4 can be changed by pressing and push buttons The selected assignment can be stored...

Страница 17: ...shows the first part of the software version of the relay e g D08 By pressing the push button TRIP twice the display shows the second part of the software version of the relay e g 4 01 The software ve...

Страница 18: ...t circuit For checking the measuring values a current must be injected terminals B1 B2 which is below the set pickup current of the MRR1 After renewed pressing the SELECT RESET push button measuring v...

Страница 19: ...ources above described Since the cost and potential hazards are very high for such a test especially if staged fault tests are in tended these tests are usually limited to very important protective re...

Страница 20: ...nuous current 20 A DC Nominal current IN 10 A DC measuring range up to 25A DC Power consumption in current circuit 1 VA 7 2 Common data Dropout to pickup ratio 98 Returning time 30ms Minimum operating...

Страница 21: ...value Tripping delay for R tR 1 50 sec EXIT 0 1 0 2 0 5 1 0 3 or 0 2 2 s Pickup value of ex citer undercurrent element Ie EXIT 0 2 20 A 0 05 0 1 0 2 0 5 2 of setting value or 0 01A Tripping delay for...

Страница 22: ...Woodward Manual MRR1 GB 22 DOK TD MRR1 Rev A 7 5 Order Form Rotor earth fault relay MRR1 Housing 12TE 19 rack Flush mounting A D Technical data subject to change without notice...

Страница 23: ...ercurrent element A 0 50 tIe Tripping delay for I s 0 10 Ie Pickup value exciter over current element A 5 00 tIe Tripping delay for I s 0 1 Ir Pickup value for ripple voltage supervision 50 tIr Trippi...