Restrictor
Disk
Restrictor
Disk
22
L100001
23
using a maximum of two 90° elbows.
See Figure 25.
Figure 25- Support Straps for Horizontal Runs
VENT INSTALLATION
Figure 26 - Maximum Elbow Usage
•
Up to two 45° elbows may be used within the
horizontal run. For each 45° elbow used on the
horizontal plane, the maximum horizontal length
must be reduced by 18" (450mm).
Example:
Maximum horizontal length
No elbows = 10’ (3m)
1x45
°
elbows = 8.5’ (2.6m)
2x45
°
elbows = 7’ (2.1m)
•
A minimum of an 8' (2.5m) vertical rise is
required.
•
Two sets of 45°elbows offsets may be used within
the vertical sections. From 0 to a maximum of 8'
(2.5 m) of vent pipe can be used between elbows.
See Figure 26.
•
Monterey
Series fireplaces allow for offsets. This
application
will
require
that
you
first
determine
the
roof
pitch
and
use
the
appropriate
starter
kit.
•
The maximum angular variation allowed in the
system is 270°.
See Figure 26.
•
The minimum height of the vent above the high-
est point of penetration through the roof is 2'
(610mm).
8' Minimum Height
10'
Maximum
1
2
3
4
Support Straps
Every 3'
Example:
Elbow 1 = 90
°
Elbow 2 = 45
°
Elbow 3 = 45
°
Elbow 4 = 90
°
Total Angular Variation
= 270
°
Support
Straps
Every
5'Vertical
Restrictor
Disk
RESTRICTOR DISC
NOTE: The restrictor disc
included with the installation
instructions should be used
on vertically terminating
installations only.
Install the restrictor disc into
the
fl
ue collar of the appliance
with the bar horizontal.
2
1
3
4
40' Maximum Height
VERTICAL THROUGH-THE-ROOF APPLICATIONS — RIGID VENTING ONLY
This Gas Fireplace has been approved for
:
•
Vertical installations up to
4
0' (
12
m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system