background image

16

L100001

17

���� �������

���� �������

� � �����������

12

��

305

���

�������������� �

2

��

305

���

����������� �
��������������
� �

12

� �

305

���

� � ��� �������

� � ������� ����� �� ��� ��������

��� ������ ��������

� � ������� ����� ��� ���� ���� ��

������ ��������
����������� � ��� �������
�������������� � ��� �������

� � ��������� ���� ������ �� ������

��������
����������� �

6

� ��

52

���

�������������� � �� ������

������ ������

������ ��������

������� ������

������� ���� �� ���� ����

������� ���� �������������

���� ����

VENT INSTALLATION 

TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE 
AND NONCOMBUSTIBLE EXTERIORS 

Figure 9 - Allowable Venting Chart 

HOW TO USE THE VENT GRAPH

The Vent Graph should be read in conjunction with the following 
vent installation instructions to determine the relationship between 
the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe exit-

ing through the outer wall. Using this dimension on the Sidewall
Vent Graph below, locate the point intersecting with the slanted
graph line.

2. From the point of this intersection, draw a vertical line to the

bottom of the graph.

3. Select  the  indicated  dimension,  and  position  the  fireplace  in

accordance with same.

Example: If the vertical dimension from the floor of the
fireplace is 11' (3.4m) the horizontal run to the face of the
outer wall must not exceed 1

8

' (

5.5

m).

Example: If the vertical dimension from the floor of the unit
is 7’ (2.14m), the horizontal run to the face of the outer
wall must not exceed 

1 6

' (

4.9

m).

Sidewall Vent Graph showing the relationship between vertical and 
horizontal dimensions for a Direct Vent flue system.

Figure 10 - Rear Wall Venting Graph

Horizontal Dimension

 (Ft) 

From the Outside of 

Termination to the Back of the Fireplace

V

ertical Dimension

 (Ft) 

From the Floor of Unit to the Center of 

the Horizontal 

V

ent Pipe

50
48
46
44
42
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2

2 4 6 8

16

   18   20 (ft)

14

12

10

Содержание MONTEREY-(N

Страница 1: ...SION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not touch any electrical switch do not use any phone in your building Do not try to lig...

Страница 2: ...Type 25 Installing Gas Piping to Fireplace Burner System Location 25 Checking Gas Pressure 27 Electrical Installation 28 Electrical Wiring 28 Wall Switch 28 Glass Removal 29 Final Installation 30 Medi...

Страница 3: ...d and sealed If this unit is not properly installed by a qualified service person with glass panel properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carb...

Страница 4: ...ace to give off some odor the first time it is burned This is due to the manufacturing process Please ensure that your room is well ventilated during burn off open all windows It is recommended that y...

Страница 5: ...Remote Control Receiver optional 4 Blower Speed Control 5 Blower 6 Duplex Outlet for Blower located against lower right outside wall 6 Figure 1 Fireplace controls TESTED TO ANSI Z21 88 2014 CSA 2 33 2...

Страница 6: ...damage and immediately inform the distributor if any damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have be...

Страница 7: ...rial over the facing are 60 x 34 1 2 see Figure 2 3 The inner opening in covering material must be minimum 49 1 4 wide 14 1 4 tall and centered over the fireplace opening to allow for or glass door re...

Страница 8: ...RMATION Figure 3 Fireplace Dimensions Right side view Front view Top view Flue collar Electric access both sides Gas line access both sides 28 34 25 23 25 48 75 13 75 59 25 34 25 28 7 125 7 125 8 5 22...

Страница 9: ...t the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section found in this manual for allowable ven...

Страница 10: ...ecure fireplace to the floor Use four 4 screws to attach fireplace to framing The side brackets are adjustable from 1 2 to 5 8 to accommodate different thickness of material SECURING FIREPLACE TO FLOO...

Страница 11: ...l flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING The fireplace face may be covered with any non comb...

Страница 12: ...NFORMATION VENT INSTALLATION Never obstruct or modify the air inlet or outlet This may create a fire hazard WARNING Read all instructions completely and thoroughly before attempting installation Failu...

Страница 13: ...be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNING Horizontal sections of this vent sys...

Страница 14: ...s firestops are required at each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exteri...

Страница 15: ...n air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved driveway located on public property 7 2133...

Страница 16: ...cal line to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the...

Страница 17: ...ired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have three locking lugs i...

Страница 18: ...re 15 5 Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and inse...

Страница 19: ...dations less than 20 below siding outcrop the vent pipe must flush up with the sid ing It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length...

Страница 20: ...lbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizonta...

Страница 21: ...leaving a clearance of approximately 4 below snorkel See Figure 21 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealan...

Страница 22: ...at you first determine the roof pitch and use the appropriate starter kit The maximum angular variation allowed in the system is 270 See Figure 26 The minimum height of the vent above the high est poi...

Страница 23: ...x101 2 267mm x 267mm inside dimensions as shown in Figure 12 page 17 using framing lumber the same size as the ceiling joist If the area above the ceiling is an insulated ceiling or a room nail fires...

Страница 24: ...eiling Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Cat...

Страница 25: ...l regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could...

Страница 26: ...raps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure...

Страница 27: ...aking pressure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks Figure 34 Gas Pressure Check at Gas Valve Pressure Test IN Pressure...

Страница 28: ...without any electrical supply Electricity is only needed to operate blower NOTE If installed in mobile home fireplace must be bolted securely to floor Electrical connections should only be performed...

Страница 29: ...lifting up and moving to the center Figure 36 Removing Glass Frame and tilting out the upper right corner Front air panel Right side panel 4 Remove upper door bracket NOTE Avoid contacting the glass t...

Страница 30: ...37 on the support brackets as shown on figure 38 Figure 37 One piece media tray Figure 38 Placing media tray Figure 39 Filling the tray with media 2 Fill the tray with media supplied Do not place medi...

Страница 31: ...LOG SET 31...

Страница 32: ...Figure 41 Log set placement LOG SETT contunue 32...

Страница 33: ...the screen in place Using the nuts provided attach the screen firmly 33 WARNING A barrier safety screen designed to reduce the risk of burns from the hot viewing glass is provided with this appliance...

Страница 34: ...the face and slide downward Make sure the side panel is secured properly Repeat Steps 5 and 6 for the Left Side Panel STEP 7 Angle the Air Front Panel beneath the bottom of the screen Support the Air...

Страница 35: ...air may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to replace any par...

Страница 36: ...gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field made joints gas shutoff valve Pilot Factory made joints Each joint or c...

Страница 37: ...alve knob Make sure the switch is in the ON position to light the main burner LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON position See Figure 42 It will take less than fou...

Страница 38: ...ore See Figure 47 Figure 46 Burner Flame Appearance CLEANING AND MAINTENANCE BURNER PILOT AND CONTROL COMPARTMENT Keep the control compartment and burner areas clean by vacuuming or brushing at least...

Страница 39: ...LOG SET Replace logs or add media as required following unstallation instructions in the Final Installation section of this manual BLOWER FAN ASSEMBLY The fan assembly has an automatic temperature co...

Страница 40: ...9 Pipe Length 58DVA 09 3 4 12 Pipe Length 58DVA 12 3 4 24 Pipe Length 58DVA 24 3 4 36 Pipe Length 58DVA 36 3 4 48 Pipe Length 58DVA 48 4 4 8 1 2 Pipe Extension 58DVA 08A 4 4 16 Pipe Extension 58DVA 1...

Страница 41: ...ILLUSTRATED PARTS LISTS BURNER COMPARTMENT 9 3 10 11 12 FIREBOX ACCESS AND MEDIA COMPONENTS CONTROL COMPARTMENT 13 1 3 4 2 5 6 7 6 6 8 14 22 41 18 21 20 19 23 22...

Страница 42: ...ORIFICE 1 10 W400071 W400071 BURNER 1 11 C100003 C100004 PILOT ASSEMBLY 1 12 D100019 D100019 PILOT BRACKET 1 13 F200100 F200100 3 8 NPT X 5 16 COMPRESSION CONNECTOR 1 14 F200064 F200064 3 8 NPT X 3 8...

Страница 43: ...safety to drop out A Inner vent pipe leaking exhaust gases back into system B Horizontal vent improperly pitched C Improper vent cap installation A Check switch and wire for proper connection Place ju...

Страница 44: ...127 6...

Страница 45: ...127 6...

Страница 46: ...127 6...

Страница 47: ...0 Elbows Quantity 45 Elbows ALTITUDE Feet Above Sea Level Was Stove Derated Yes No If Yes To What Orifice Size Unusual Structure Near Vent Inside Corner Trees Shrubs Other Termination Please Describe...

Страница 48: ...stallation or transportation of defective parts on the appliance or 3 incidental or consequential damage All service work must be performed by an authorized service representative This warranty is exp...

Отзывы: