The Wood Stone Gas ovens are equipped with a 3/4" NPT gas connection
located at the rear left of the oven. Have a licensed gas installer provide
the hook-up and test all fittings and pipe connections for leaks. Use
approved gas leak detectors (soap solutions or equivalent) over and around
the fittings and pipe connections. DO NOT USE FLAME TO TEST FOR
LEAKS!
SV-2 is the gas control valve that operates the interior radiant burner. SV-2 is
located under the oven to the rear left.
The manifold pressure test port for the radiant burner is a 1/8" NPT
plugged tapping located at the base of the T-junction between the SV-2
and the radiant/interior burner.
The burner manifold pressure has been adjusted and tested at the factory. A
variety of factors can influence this pressure, so be sure to test the burner
manifold pressure and adjust the valve as necessary to achieve the specified
pressure. Note: The gas valve is shipped in the 'on' position.
Factory specified individual burner manifold pressures for RFG
models equipped to burn Natural Gas.
MODEL
SV-2
WS-MS-4-RFG-NG
5"
WS-MS-5-RFG-NG
4.75"
WS-MS-6-RFG-NG
4.75"
WS-MS-7-RFG-NG
4.6"
Factory specified individual burner manifold pressures for RFG
models equipped to burn Propane (LP).
MODEL
SV-2
WS-MS 4-RFG-LP
7"
WS-MS-5-RFG-LP
8"
WS-MS-6-RFG-LP
8"
WS-MS-7-RFG-LP
9.5"