GMG-B Operation manual
Page 27 of 45
B0743
7. Operation
7.1 Control "C" (option)
The control serves to trigger and monitor the pump unit. It is
capable of switching the pump on and off depending on time
and load. Furthermore, the control can be used to monitor the
filling level and functioning of the progressive distributors. In
case of fault, a corresponding message can be submitted to a
superior system. The control needs to be started by way of
an external "release".
Control version "C3":
Control with distributor monitoring
for flanged-on or externally mounted
progressive distributor.
When voltage supply is switched on, the control displays "ON" or "OFF", where "ON"
indicates readiness for operation (external release = 24 V on Pin 2).
On the control, you can adjust various menu items and parameters. The meanings of the
various menu items are as follows:
CODE Menu release
P1
Selection between time mode (001) and pulse mode (002)
P2
Setting of cycle time in hours (0
… 255) in time mode
P3
Setting of cycle time in minutes (0
… 59) in time mode
P4
Setting of external machine pulses (1
… 9999) in pulse mode
P5
Pump delivery switch-off via number of distributor pulses
(ON = 001/OFF = 000)
P6
Number of distributor pulses until pump delivery switch-off (1-999)
P7
Distributor monitoring ON = 001/OFF = 000
P8
Setting of delivery time in minutes (0
… 255)
P9
Setting of delivery time in seconds (0
… 59)
P10
Selection of stirring function (yes = 001/no = 000)
P11
Setting of off-duty time between two stirring processes in hours (1
… 100)
P21
Setting the monitoring time for a distributor circulation in seconds
(0 … 255)