VERSION 3
05/01/2021
I
NSTALLATION AND
U
SAGE
G
UIDE
WINESP40DUPRO
Page 14
3.2.2
AIR FLOW
3.3
PUTTING IN PLACE THE INDOOR UNIT
Because of the diversity of locations, each fitter must adapt to the constraints of the particular installation.
Leave space for the refrigeration and electrical connections and the condensate drain pipe.
The intake and discharge openings must not be obstructed, even in part.
The discharge and intake must be separated in order to avoid taking back discharged air, even in
part (as a test, the intake temperature must be identical to the temperature in the room when
the device is cooling it).
Make the electrical connections before fastening the indoor unit to the ceiling if permitted by the
cable lengths (see section 3.6.2, p 19).
3.3.1
INSTALLATION
-
Use insulated ducts,
Ø125mm
-
Make sure you select the ideal location so that the duct length is
as short as possible (14 m max in all/reduce by 1 m per number
of bends)
-
Bend radius ≥ 175
mm
-
Do not reduce the duct section
Two finishing grilles are supplied with the device. They are adapted for the air flow of the air conditioner.
INTAKE
DISCHARGE