Reference numbers 1 through 3 in the diagram above are 

system parts supplied by the customer. Reference number 4 

is on the generator.

The following diagram is of a natural gas (NG) installation.

Reference numbers 2 through 4 in the previous diagram 

are system parts supplied by the customer. Reference 

number 4 is on the generator.

FUEL PRESSURE TABLES

The following tables are the fuel pressure readings at each 

reference in the system.

Single low pressure regulator (LP vapor only)

Ref#

1

3

4

Unit off

Line PSI

7-11 in
4-6 oz

7-11 in 
4-6 oz

Starting

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Two regulator system (LP vapor only)

Ref#

1

2

3

4

Unit off

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Starting

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Natural gas

Ref#

2

3

4

Unit off

Line PSI

7-11 in
4-6 oz

7-11 in 
4-6 oz

Starting

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

NG/LP FUEL CONVERSION

These generator sets are factory tested on Natural Gas 

and will require no modifications for normal operation on 

Natural Gas. The carburation system has been preset and 

anti-tamper plugs have been installed in the carburetor as 

required by the EPA.

If you are operating on LP fuel you will have to make the 

following modifications: On the left side of the engine, 

above the starter there is a small two wire white connector 

lying loose. The wires will be labeled 1 and 21. This 

connector has to be plugged into the mating two-wire 

white connector coming out of the carburetor area on the 

left side of the unit. This connection will engage an orifice 

in the carburetor allowing the unit to operate on Liquid 

Propane vapor fuel. NO other adjustments are required.

If you are reinstalling a unit that has been operating

on Liquid Propane vapor and you now want to operate

it on Natural Gas all that you will need to do is

unplug this connector.

Содержание PSS8B2F

Страница 1: ...o contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURCHA...

Страница 2: ...WITCH ENGINE GENERATOR SET ENGINE MAINTENANCE MAINTENANCE SCHEDULE TROUBLESHOOTING 22 OUTLINE DRAWING 23 PAD LAYOUT DRAWING 24 AC WIRING SCHEMATIC 24 AC AND DC GENERATOR SCHEMATIC 25 SOLAR CONTROL PAN...

Страница 3: ...t must be mixed with fresh air A Operate only in well ventilated areas B Never operate indoors including attached garages C Never operate the unit in such a way as to allow exhaust gases to seep back...

Страница 4: ...er option derate 30 and note the circuit breaker derates to 25 Amp FUEL CONSUMPTION Natural Gas 1000 BTU FT LP Vapor 2520 BTU FT CF HR 132 63 BTU HR 132 000 158 760 GAL HR N A 1 6 Based on full load o...

Страница 5: ...ment The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 s...

Страница 6: ...crankcase the first time use the dipstick A in following image to ensure that you do not over fill the crankcase The full oil level mark on the dipstick is depicted in the following image as B Oil is...

Страница 7: ...satisfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans WARNING PERSONAL INJURY The enclosures on these units can become very...

Страница 8: ...rimary to the low pressure regulator Consult your local fuel supplier for your exact requirements The appropriate line size from the following table is then installed from the low pressure regulator t...

Страница 9: ...Natural gas Ref 2 3 4 Unit off Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz No load Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 7 11 in 4 6 oz...

Страница 10: ...sh off immediately with water 3 If electrolyte contacts the eyes flush immediately and thoroughly with water Seek immediate medical attention 4 Spilled electrolyte is to be washed down with an acid ne...

Страница 11: ...be fused for 15 Amps Terminal block connections have been provided in the customer connection area of the engine generator set See following diagram NOTICE The battery tender is not intended to recha...

Страница 12: ...als L3 L7 The neutral leads from all three locations are connected to the isolated terminal lugs on the sidewall of the cabinet This terminal block is labeled NEUTRAL and the terminal lugs are mounted...

Страница 13: ...through 9 These terminals will accept 22 14 AWG stranded wire It is recommended that you use 16 AWG for distances up to 200 feet You need to run two 2 wires from the engine generator set to the transf...

Страница 14: ...y Deep Sea Electronics Model 3110 is used on this generator set See following picture and look for more information stated within this manual MANUAL OPERATION Press and release the red Stop Reset butt...

Страница 15: ...hanging the exercise without a load will be discussed later Be sure that conditions are safe to do this operation BYPASS TIME DELAY Use this button to cancel the active time delay or exercise period s...

Страница 16: ...art and run the exerciser must be reset after the power is restored The ASCO 185 has settings that can be changed for various applications The dipswitch options are explained in the ASCO 185 Operator...

Страница 17: ...17 60706 211 J SEQUENCE OF OPERATION UTILITY FAILURE...

Страница 18: ...Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The module has...

Страница 19: ...The fault must be removed and the Stop Reset button pressed to reset the module The icon will appear flashing in the display MODULE DISPLAY TIMER ICON When the module is controlling the engine startin...

Страница 20: ...il level must always be checked before the engine is started Refer to page 7 of this manual for instructions on checking the oil level Take care to remove any dirt or debris from around the oil plug b...

Страница 21: ...ked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Defe...

Страница 22: ...22 60706 211 J 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...

Страница 23: ...23 60706 211 J PAD LAYOUT DRAWING 11075 00 20 60706 211 ENGINE GENERATOR SET PAD LAYOUT...

Страница 24: ...24 60706 211 J AC WIRING SCHEMATIC...

Страница 25: ...25 60706 211 J 11075 00 22 60706 211 AC AND DC GENERATOR SCHEMATIC AC AND DC GENERATOR SCHEMATIC...

Страница 26: ...26 60706 211 J EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...

Страница 27: ...27 60706 211 J SOLAR PANEL ASSEMBLY IF EQUIPPED...

Страница 28: ...does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment WINCO does not warrant engines Engines a...

Отзывы: