background image

15

60706-211/J

TRANSFER SWITCH & ENGINE-GENERATOR

Automatic (remote) Operation

This procedure checks the electrical operation of the 

automatic transfer switch. If the actual operation does not 

follow procedure, consult the trouble-shooting section in 

the transfer switch manual.

  1. Turn on the preferred source (utility) circuit breaker. 

    The Utility Acceptable Light should now come on, as 

    well as the Load on Utility Light. If those lights fail to 

    come on, recheck your incoming power to ensure you 

    have 240 Volts nominal. If not, troubleshoot your utility 

    source before continuing.

  2. Press and release the Auto button on the engine 

    control module (ECM). The auto mode icon will appear 

    on the screen. The unit is now ready to be operated 

    from the Automatic Transfer Switch.

  3. Turn on the alternate source (generator) circuit 

  breaker.

WARNING: PERSONAL INJURY HAZARD

Install front cover in transfer switch before operation. 

An electrical system fault could cause a flash and severe 

personal injury.

The digital controller provides sensing, timing, and control 

functions for the ATS. This micro-processor-based controller 

includes built-in control buttons and status lights for control 

of the ATS and the generator. 

PUSH BUTTONS

On the front control display are the three push buttons that 

control the operation of the generator and the ATS.

CAUTION

Before using the transfer test button, be sure that 

conditions are safe for running the generator and for load 

tester.

TRANSFER TEST

Use this button to test the system. This operation starts 

the generator and transfers the load. The controller is 

shipped with a load transfer set by default. Changing the 

exercise without a load will be discussed later. Be sure that 

conditions are safe to do this operation. 

BYPASS TIME DELAY

Use this button to cancel the active time delay or exercise 

period (stops the generator after cool-down).

SET ENGINE EXERCISER

Use this button to set the automatic exerciser. 

INDICATOR LIGHTS

On the front control display are five lights that indicate the 

status of the sources and the ATS.

UTILITY ACCEPTABLE

This light indicates that the utility voltage is acceptable for 

connection to the loads.

GENERATOR ACCEPTABLE

This light indicates that the generator voltage and 

frequency is acceptable for connection to the load.

LOAD ON UTILITY

This light indicates that the generator voltage is acceptable 

for connection to the load.

AUTOMATIC GENERATOR EXERCISER

This light indicates the status of the generator exerciser:

  • Blinks during the exercise period (including cool down)

  • Stays on when the exerciser has been set.

  • Is off when the exerciser has not been set.

GENERATOR STARTING CONTACTS

Disconnect the generator battery. Connect the generator 

starting wires #1 (battery -) to terminal 4; wire #23 (start) to 

terminal 5 of the TB7 terminal block. This is removable for 

convenient connections.  

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to 

automatically exercise the generator for 20 minutes once 

every week.

In order to set and test the exercise circuit the AUTO button 

on the generator control panel must be on.

EXERCISE WITH OR WITHOUT LOAD

The transfer switch can be set up to exercise the generator 

with or without a load transfer. Normally, WINCO 

generators exercise without a load transfer. This is because 

you may not with to have a momentary interruption of 

power. Turn the exerciser dip switch on. Then set the “with 

load” or “without load”. See the following table.

Содержание PSS8B2F

Страница 1: ...o contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURCHA...

Страница 2: ...WITCH ENGINE GENERATOR SET ENGINE MAINTENANCE MAINTENANCE SCHEDULE TROUBLESHOOTING 22 OUTLINE DRAWING 23 PAD LAYOUT DRAWING 24 AC WIRING SCHEMATIC 24 AC AND DC GENERATOR SCHEMATIC 25 SOLAR CONTROL PAN...

Страница 3: ...t must be mixed with fresh air A Operate only in well ventilated areas B Never operate indoors including attached garages C Never operate the unit in such a way as to allow exhaust gases to seep back...

Страница 4: ...er option derate 30 and note the circuit breaker derates to 25 Amp FUEL CONSUMPTION Natural Gas 1000 BTU FT LP Vapor 2520 BTU FT CF HR 132 63 BTU HR 132 000 158 760 GAL HR N A 1 6 Based on full load o...

Страница 5: ...ment The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 s...

Страница 6: ...crankcase the first time use the dipstick A in following image to ensure that you do not over fill the crankcase The full oil level mark on the dipstick is depicted in the following image as B Oil is...

Страница 7: ...satisfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans WARNING PERSONAL INJURY The enclosures on these units can become very...

Страница 8: ...rimary to the low pressure regulator Consult your local fuel supplier for your exact requirements The appropriate line size from the following table is then installed from the low pressure regulator t...

Страница 9: ...Natural gas Ref 2 3 4 Unit off Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz No load Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 7 11 in 4 6 oz...

Страница 10: ...sh off immediately with water 3 If electrolyte contacts the eyes flush immediately and thoroughly with water Seek immediate medical attention 4 Spilled electrolyte is to be washed down with an acid ne...

Страница 11: ...be fused for 15 Amps Terminal block connections have been provided in the customer connection area of the engine generator set See following diagram NOTICE The battery tender is not intended to recha...

Страница 12: ...als L3 L7 The neutral leads from all three locations are connected to the isolated terminal lugs on the sidewall of the cabinet This terminal block is labeled NEUTRAL and the terminal lugs are mounted...

Страница 13: ...through 9 These terminals will accept 22 14 AWG stranded wire It is recommended that you use 16 AWG for distances up to 200 feet You need to run two 2 wires from the engine generator set to the transf...

Страница 14: ...y Deep Sea Electronics Model 3110 is used on this generator set See following picture and look for more information stated within this manual MANUAL OPERATION Press and release the red Stop Reset butt...

Страница 15: ...hanging the exercise without a load will be discussed later Be sure that conditions are safe to do this operation BYPASS TIME DELAY Use this button to cancel the active time delay or exercise period s...

Страница 16: ...art and run the exerciser must be reset after the power is restored The ASCO 185 has settings that can be changed for various applications The dipswitch options are explained in the ASCO 185 Operator...

Страница 17: ...17 60706 211 J SEQUENCE OF OPERATION UTILITY FAILURE...

Страница 18: ...Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The module has...

Страница 19: ...The fault must be removed and the Stop Reset button pressed to reset the module The icon will appear flashing in the display MODULE DISPLAY TIMER ICON When the module is controlling the engine startin...

Страница 20: ...il level must always be checked before the engine is started Refer to page 7 of this manual for instructions on checking the oil level Take care to remove any dirt or debris from around the oil plug b...

Страница 21: ...ked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Defe...

Страница 22: ...22 60706 211 J 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...

Страница 23: ...23 60706 211 J PAD LAYOUT DRAWING 11075 00 20 60706 211 ENGINE GENERATOR SET PAD LAYOUT...

Страница 24: ...24 60706 211 J AC WIRING SCHEMATIC...

Страница 25: ...25 60706 211 J 11075 00 22 60706 211 AC AND DC GENERATOR SCHEMATIC AC AND DC GENERATOR SCHEMATIC...

Страница 26: ...26 60706 211 J EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...

Страница 27: ...27 60706 211 J SOLAR PANEL ASSEMBLY IF EQUIPPED...

Страница 28: ...does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment WINCO does not warrant engines Engines a...

Отзывы: