6

OPM-108/B

ENGINE

Refer to the engine operators manual for more detailed 

operation and maintenance information.

CAUTION: EQUIPMENT DAMAGE:

Be sure to check the engine oil level frequently as specified 

in the engine manual.

The engine manufacturer has established an excellent 

worldwide engine service organization; engine service is 

available from a nearby authorized dealer or distributor. 

The rated power of each engine-generator is limited by 

the temperature, altitude, and all other ambient conditions 

specified by the engine manufacturer. Engine power may 

decrease 3½% for each 1000 feet above sea level, and will 

decrease an additional 1% for each 10 degrees Fahrenheit 

above 60° Fahrenheit. Units should not be operated in 

ambient temperature greater than 125° Fahrenheit.

GENERATOR

WINCO generator sets use brushless, AVR (Auto-Voltage 

Regulator) controlled broad-range generator ends. The 

generator converts rotational mechanical energy into 

electrical energy. These WINCO units are equipped 

with generators manufactured by Cummins Generator 

Technology. Each generator ‘end’ has its own data tag. A 

unique serial number is on the data plate.

MODEL NUMBER STRUCTURE

The WINCO alpha-numerical numbering consists of a 

base model designation, followed by an options section, 

separated by a dash mark. The base component of the 

model numbering system identifies an engine type, 

engine starting method, fuel type, kilowatt rating, engine 

manufacturer, and number of generator poles. Following 

the separation dash mark is the voltage connection and 

optional installed equipment. Options include features like, 

weather enclosures (housing), base mounted fuel tank 

sizes, and trailer options. 

Please note that some features or packages, such as 

NFPA level I & II, do not have an indication place in 

this numbering system. They are issued and built with 

an M-Spec (i.e. M-10372) number which can be found 

on the WINCO data tag. When the M-Spec is present, 

supplemental inserts will accompany this standard manual 

providing information about the special equipment and 

features installed. The standard model numbering key that 

can be used along with the data tag information and/

or M-Spec supplements to determine the generator set’s 

ratings and specifications.

D

D = Diesel

R

R = Remote Start

175

Generator Output Rating in kW

F

Engine Manufacturer: F = FPT

4

Number of Generator Poles

-

Base Unit - Options Separator

A

Voltage
A (3) = Single Phase 120/240V
D (4) = Three Phase 120/208V
J (17) = Three Phase 120/240V
L (18) = Three Phase 277/480V

A

HOUSING TYPE
A = Sound Attenuated/Weather Protective
* = No Housing

M

Fuel Tank Size: S = Small; M = Medium; L = Large;
      * 

None

T

T = Trailer; * = None

D

Battery Charger Options
A = 12V/.75A; B = 12V/3.5A; C = 12V/6A; D = 
12V/10A;
E = 12V/6A NFPA; F = 12V/10A NFPA; G = 
24V/3.5A;
H = 24V/10A; I = 24V/10A NFPA; J = 12V/2A

Содержание DR175F4

Страница 1: ...s unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE __________________...

Страница 2: ...s loaded to its full capacity and the voltage current and frequency are carefully checked Rated output of generator is based on engineering tests of typical units and is subject to and limited by the...

Страница 3: ...ion or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings on the unit labels and...

Страница 4: ...ns Fuel ASTM D 975 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 29 6 Quarts Cooling System 50 50 mix DR300F4 Generator Wattage 300 000 300 000 300 000 Volts 120 208 120 2...

Страница 5: ...otal system s performance and reliability The engine generator set consists of a multi cylinder liquid cooled engine nominally operating at 1800 rpm The generator frequency regulation is maintained by...

Страница 6: ...dash mark The base component of the model numbering system identifies an engine type engine starting method fuel type kilowatt rating engine manufacturer and number of generator poles Following the s...

Страница 7: ...dling equipment i e a forklift CAUTION Do not attempt to lift the generator set by the means of the lifting eyes on the engine or generator end These lifting points are only for the use during the man...

Страница 8: ...t of the enclosure In addition to a hot air discharge you must plan a fresh air intake opposite the radiator discharge Their fresh air inlets should be 1 to 2 times larger than the radiator face The e...

Страница 9: ...ircuit the battery charging system on the engine CAUTION A battery presents a risk of electrical shock and high short circuit current The following precautions must be observed when working with batte...

Страница 10: ...er The generator power feeds have already been wired into the upper lugs Please refer to the circuit breaker installed on your unit for breaker lug capacities and proper torque speci cations To select...

Страница 11: ...operating switch is in the OFF position WARNING EQUIPMENT DAMAGE When installing a three phase 240 Volt system be sure you know which lead is the high voltage wild leg 208 Volt line to neutral The ge...

Страница 12: ...s present the common alarm LED if configures will illuminate The LCD display will show an icon to indicate the failure WARNINGS Warnings are non critical alarm conditions and do not affect the operati...

Страница 13: ...he line power should fail or be turned off the transfer switch during manual operation the load may be applied to the generator With the engine running smoothly check the no load voltage and frequency...

Страница 14: ...of the cylinder block Discharge the coolant inside the engine 4 Close the drain cock and the water drain plug Refill radiator with coolant MAINTENANCE CHANGING THE OIL CAUTION PERSONAL INJURY Only cha...

Страница 15: ...the fluid until only fuel comes out 4 Fully hand tighten the plug 5 Dispose of liquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will...

Страница 16: ...the injection pump channels 4 Connect the fuel circuit to a tank containing CFB protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine for approx 2 min...

Страница 17: ...fective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water...

Страница 18: ...he red Light Emitting Diode LED is illuminated refer to the Under Frequency Roll Off UFRO adjustment 7 Carefully turn VOLTS control clockwise until rated voltage is reached 8 If instability is present...

Страница 19: ...N THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 202...

Страница 20: ...20 OPM 108 B ENGINE HARNESS SCHEMATIC DR175F4...

Страница 21: ...21 OPM 108 B ENGINE HARNESS SCHEMATIC DR250F4...

Страница 22: ...8 2 2 9 4958 36 9 8 89 9 8 77 77 67 57 1 6723 6723 6 5 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 4 25 46 53354 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 9 5 92 7 8670 17 5 267 7 9...

Страница 23: ...EE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THRE...

Страница 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: