5

OPM-108/B

The DR175, DR250, DR300 and the DR350 use a 

combination of four different Stamford generator ends, 

depending on your operating voltage. 

Review the Stamford Newage nameplate on your 

generator before selecting the correct information below. 

Some custom applications use other models. Check the 

generator nameplate for actual model number. 

Stamford Newage Model# UCI274H

(Single phase 4 lead generator)

Voltage Regulator    

AS440

Rotor Resistance  

 

0.82 ohms

Stator Resistance  

 

0.004 ohms

Excitor Stator Resistance  20.0 ohms

Excitor Rotor Resistance  0.182 ohms

Stamford Newage Model# UCI274H

(Three phase 12 lead reconnectable generator)

Voltage Regulator    

AS440

Rotor Resistance  

 

0.82 ohms

Stator Resistance  

 

0.008 ohms

Excitor Stator Resistance  20.0 ohms

Excitor Rotor Resistance  0.182 ohms

Stamford Newage Model# HCI434C

(Three phase 12 lead reconnectable generator)

Voltage Regulator    

MX341

Rotor Resistance  

 

0.92 ohms

Stator Resistance  

 

0.0083 ohms

Excitor Stator Resistance  18.0 ohms

Excitor Rotor Resistance  0.136 ohms

PMG Stator L-L    

 

2.6 ohms

Stamford Newage Model# HCI434D

(Three phase 12 lead reconnectable generator)

Voltage Regulator    

MX341

Rotor Resistance  

 

1.05 ohms

Stator Resistance  

 

0.0062 ohms

Excitor Stator Resistance  18.0 ohms

Excitor Rotor Resistance  0.136 ohms

PMG Stator L-L    

 

2.6 ohms

Stamford Newage Model# HCI434E

(Three phase 12 lead reconnectable generator)

Voltage Regulator    

MX341

Rotor Resistance  

 

1.19 ohms

Stator Resistance  

 

0.0045 ohms

Excitor Stator Resistance  18.0 ohms

Excitor Rotor Resistance  0.136 ohms

PMG Stator L-L    

 

2.6 ohms

Stamford Newage Model# HCI424F

(Three phase 12 lead reconnectable generator)

Voltage Regulator    

MX341

Rotor Resistance  

 

1.37 ohms

Stator Resistance  

 

0.0037 ohms

Excitor Stator Resistance  18.0 ohms

Excitor Rotor Resistance  0.136 ohms

INTRODUCTION

PRODUCT DESCRIPTION

This engine-generator set is designed for unattended 

remote start operation. It can be operated as part of a 

fully automatic standby power system or independently 

as a local start unit in a prime power system. The engine-

generator set is fully tested at the factory prior to shipment 

to insure proper operation of each individual component as 

well as the total system’s performance and reliability.

The engine generator set consists of a multi-cylinder, liquid 

cooled engine nominally operating at 1800 rpm. The 

generator frequency regulation is maintained by the engine 

governor to /- 1.5 Hz (cps), from no load to rated 

load for standard mechanical governors and to /- .5 

Hz or better for units equipped with an electronic governor. 

The generator is a single bearing, direct drive, rotating field 

design.  The generator is connected to the engine flywheel 

via flexible drive disks. Generator set is skid mounted with 

isolation mounts between the engine and base on all units.

A customer supplied 12 Volt battery is required to complete 

the installation. Battery requirements are listed later under 

the battery installation section. 

Unit Orientation Note: All references used in this manual 

for unit familiarization, access and component locations on 

the Generator Set are oriented from a TOP (plan) VIEW with 

engine at the FRONT and generator to the REAR.

WINCO uses a common junction box for all customer 

control and power connections (both AC output and DC 

control). The common electrical junction box is always on 

the left side at the generator end of the machine.

The engine is controlled and Generator Set operation 

is monitored for safe operation by a programmable 

microprocessor based electronic Engine Control Module 

(ECM) with an LCD digital display. The generator set ECM 

control is mounted on a vertical pedestal on the right side 

of the generator. The ECM is programmed with a cycle 

cranking sequence - 3 cycles of 15 seconds on/15 seconds 

off, and 5 minute cool-down delay. The cool-down delay 

can be changed in the field from 0 to 30 minutes by your 

installer. Other features, timing cycles, set points, and 

signal output capabilities are possible. Consult factory for 

procedure and passwords.

NOTICE:

These units will automatically transfer if a power outage 

occurs while running in exercise mode.

GENERATOR SET

Every WINCO generator set has its own unique identity 

data plate. This data plate identifies the complete unit 

model number, the system serial number, and has links to 

the individual components that form the generator set in 

our factory records. Several of the major components also 

have their own individual data plates providing additional 

information to document build data for warranty and 

replacement parts. 

Содержание DR175F4

Страница 1: ...s unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE __________________...

Страница 2: ...s loaded to its full capacity and the voltage current and frequency are carefully checked Rated output of generator is based on engineering tests of typical units and is subject to and limited by the...

Страница 3: ...ion or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings on the unit labels and...

Страница 4: ...ns Fuel ASTM D 975 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 29 6 Quarts Cooling System 50 50 mix DR300F4 Generator Wattage 300 000 300 000 300 000 Volts 120 208 120 2...

Страница 5: ...otal system s performance and reliability The engine generator set consists of a multi cylinder liquid cooled engine nominally operating at 1800 rpm The generator frequency regulation is maintained by...

Страница 6: ...dash mark The base component of the model numbering system identifies an engine type engine starting method fuel type kilowatt rating engine manufacturer and number of generator poles Following the s...

Страница 7: ...dling equipment i e a forklift CAUTION Do not attempt to lift the generator set by the means of the lifting eyes on the engine or generator end These lifting points are only for the use during the man...

Страница 8: ...t of the enclosure In addition to a hot air discharge you must plan a fresh air intake opposite the radiator discharge Their fresh air inlets should be 1 to 2 times larger than the radiator face The e...

Страница 9: ...ircuit the battery charging system on the engine CAUTION A battery presents a risk of electrical shock and high short circuit current The following precautions must be observed when working with batte...

Страница 10: ...er The generator power feeds have already been wired into the upper lugs Please refer to the circuit breaker installed on your unit for breaker lug capacities and proper torque speci cations To select...

Страница 11: ...operating switch is in the OFF position WARNING EQUIPMENT DAMAGE When installing a three phase 240 Volt system be sure you know which lead is the high voltage wild leg 208 Volt line to neutral The ge...

Страница 12: ...s present the common alarm LED if configures will illuminate The LCD display will show an icon to indicate the failure WARNINGS Warnings are non critical alarm conditions and do not affect the operati...

Страница 13: ...he line power should fail or be turned off the transfer switch during manual operation the load may be applied to the generator With the engine running smoothly check the no load voltage and frequency...

Страница 14: ...of the cylinder block Discharge the coolant inside the engine 4 Close the drain cock and the water drain plug Refill radiator with coolant MAINTENANCE CHANGING THE OIL CAUTION PERSONAL INJURY Only cha...

Страница 15: ...the fluid until only fuel comes out 4 Fully hand tighten the plug 5 Dispose of liquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will...

Страница 16: ...the injection pump channels 4 Connect the fuel circuit to a tank containing CFB protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine for approx 2 min...

Страница 17: ...fective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water...

Страница 18: ...he red Light Emitting Diode LED is illuminated refer to the Under Frequency Roll Off UFRO adjustment 7 Carefully turn VOLTS control clockwise until rated voltage is reached 8 If instability is present...

Страница 19: ...N THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 202...

Страница 20: ...20 OPM 108 B ENGINE HARNESS SCHEMATIC DR175F4...

Страница 21: ...21 OPM 108 B ENGINE HARNESS SCHEMATIC DR250F4...

Страница 22: ...8 2 2 9 4958 36 9 8 89 9 8 77 77 67 57 1 6723 6723 6 5 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 4 25 46 53354 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 9 5 92 7 8670 17 5 267 7 9...

Страница 23: ...EE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THRE...

Страница 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: