Shower control
WimTec PROOF P6
23
EN
PROOF P6
C. Time control
set to safety flow arrest after
10 min (configurable from
10 s to 10 min).
Manual program mode: confi-
gurable from 10–60 s.
After the configured maximum
flow time has elapsed, the
water stops automatically to
prevent unintentional conti-
nuous activation.
D. Interval control
for stagnation rinse, default
setting 48 h (configurable
from 3–48 h).
If the fitting has not been
used for the set period, the
device will automatically
perform a 10-s rinse to clear
stagnation water from the
pipes.
C. Range control
User detection range preset
to 50 cm (configurable from
15–50 cm).
Sets the infrared sensor range
from 15–50 cm.
Regulator controls:
Configuring the programs & functions
Program activation – DIP switches 1 and 2:
Program
DIP switch 1
DIP switch 2
Description
Semi automatic mode
1)
OFF
ON
Page 30
Fully automatic mode
ON
ON
Page 31
Manual mode
OFF
OFF
Page 32
Function activation – DIP switches 3–6:
DIP switch
Function
Description
3
Shut-off delay ON = 5 s /
OFF
1)
= 2 s
4
Warm water rinse
1)
Page 33
5
Shower monitoring
1)
Page 34
6
Stagnation rinse
Page 35
DIP switches:
1)
Program or functions already configured
ex factory.