Installation and operating instructions Wilo-IL/-DL/-BL

35

9.2

Maintenance work

DANGER! Risk of fatal injury!
Falling pumps or pump parts may result in life-threatening injuries.

• When performing maintenance work, protect the pump compo-

nents against falling.

9.2.1

Replacing the mechanical seal

During operation, there may be a slight amount of drip leakage. A vis-
ual inspection should be performed from time to time, however. 
If there is clearly detectable leakage, the seal must be changed. Wilo 
offers a repair kit which contains the necessary parts for replacement.

Replacement

• Disconnect the system from the power supply and secure it against 

being switched back on again

• Close the check valves in front of and behind the pump.
• Depressurise the pump by opening the bleed valve (Fig. 1/2/3, 

Item 1.31).

DANGER! Risk of scalding!
Due to high fluid temperatures there is a risk of scalding.

• If the fluid is hot, allow it to cool down before performing any work.

NOTE
When tightening screw connections in conjunction with the work 
described in the following: Observe the screw tightening torque for 
the thread type (see section  “Screw tightening torques” on page 37).

• Disconnect the motor or power cables if the cable for dismantling the 

drive is too short.

• Dismantle the coupling protection (Fig. 1/2/3, Item 1.32).
• Loosen the coupling screws (Fig. 1/2/3, Item 1.5) on the coupling unit.
• Loosen the motor fastening screws (Fig. 1/2/3, Item 5) on the motor 

flange and lift the drive off the pump with suitable hoisting gear. 
On BL pumps, the adapter ring comes loose (Fig. 3, Item 8).

• By loosening the lantern fastening screws (Fig. 1/2/3, Item 4), dis-

mantle the lantern unit with coupling, shaft, mechanical seal and 
impeller from the pump housing.

• Loosen the impeller fastening nut (Fig. 1/2/3, Item 1.11), remove the 

washer underneath (Fig. 1/2/3, Item 1.12) and pull the impeller 
(Fig. 1/2/3, Item 1.13) off the pump shaft.

• Pull the mechanical seal (Fig. 1/2/3, Item 1.21) off the shaft.
• Pull the coupling (Fig. 1/2/3, Item 1.5) with the pump shaft out of the 

lantern.

• Thoroughly clean the sliding/mating surfaces of the shaft. If the shaft 

is damaged, it must be replaced.

• Remove the counter ring of the mechanical seal with the sealing collar 

from the lantern flange, as well as the O-ring (Fig. 1/2/3, Item 1.14) 
and clean the seal seats.

• Press a new mechanical seal counter ring with sealing collar into the 

seal seat of the lantern flange. A commercially available dishwashing 
liquid can be used as a lubricant.

• Install a new O-ring in the O-ring seat groove on the lantern.
• Check the coupling sliding surfaces. If necessary, clean and lightly oil 

them.

• Pre-install coupling shells on the pump shaft with spacer discs 

inserted in between and insert the pre-mounted coupling/shaft unit 
carefully into the lantern.

• Pull a new mechanical seal onto the shaft. A commercially available 

dishwashing liquid can be used as a lubricant.

• Install the impeller with washer and nut, countering at the impeller's 

outer diameter while doing so. Avoid damage to the mechanical seal 
due to jamming.

Содержание Wilo-CronoBloc-BL

Страница 1: ...Twin DL Wilo CronoBloc BL Pioneering for You 2 136 319 Ed 02 2013 11 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbou...

Страница 2: ......

Страница 3: ...Fig 1 IL Fig 2 DL...

Страница 4: ...Fig 3 BL...

Страница 5: ...de Einbau und Betriebsanleitung 3 en Installation and operating instructions 22 fr Notice de montage et de mise en service 41 nl Inbouw en bedieningsvoorschriften 60...

Страница 6: ...Shipping 24 3 2 Attachment 24 4 Intended use 25 5 Product information 25 5 1 Type key 25 5 2 Technical data 26 5 3 Scope of delivery 27 5 4 Accessories 27 6 Description and function 27 6 1 Description...

Страница 7: ...oses its validity 2 Safety These operating instructions contain basic information which must be adhered to during installation and operation For this reason these operating instructions must without f...

Страница 8: ...lack of expe rience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Childrenshould be supervised to ensur...

Страница 9: ...proper transport can lead to personal injury The pump must be transported using approved load bearing equip ment This is to be attached to the pump flanges and if necessary to the outer motor diameter...

Страница 10: ...on is only possible with the corre sponding special versions motor with standby heating and fan cover protective roof see section 7 3 on page 32 CAUTION Risk of damage Impermissible substances in the...

Страница 11: ...class F Protection class 55 Pipe and pressure measurement connec tions Flange PN 16 in accordance with DIN EN 1092 2 with pressure measure ment connections Rp 1 8 in accordance with DIN 3858 Approved...

Страница 12: ...p operation IL The pump housing has an INLINE construction i e the flanges on the suction and pressure sides lie along a centre line Fig 6 All pump housings are provided with a pump base Mounting on a...

Страница 13: ...rallel operation 0 55 51 54 54 57 0 5 51 54 60 63 1 1 53 56 60 63 1 5 55 58 67 70 2 2 59 62 67 70 3 59 62 67 70 4 59 62 67 70 5 5 63 66 71 74 7 5 63 66 71 74 11 65 68 74 77 15 65 68 74 77 18 5 71 74 7...

Страница 14: ...y 10 of the maximum flow rate must be ensured at all times 7 1 Installation The motor terminal box must not face downward If necessary the motor or motor impeller unit can be rotated once the hexagon...

Страница 15: ...r support is not necessary Only the installation position with vertical motor shaft is intended for a motor power 15 kW BL series monobloc pumps are to be mounted on a sufficiently strong base or moun...

Страница 16: ...Position the threaded cable connec tion or lay the cables accordingly to ensure that no drips can run into the module Non assigned threaded cable connections must remain sealed with the plugs provided...

Страница 17: ...used to protect the motor windings against con densation water inside the motor The standby heating is connected to the terminals HE HE in the ter minal boxes connection voltage 1 230 V 50 Hz NOTE Th...

Страница 18: ...en opening the vent screw WARNING Risk of burns or freezing to the pump when body parts come into contact with the pump Depending on the pump or system operating conditions fluid tem perature the enti...

Страница 19: ...be reinstalled WARNING Risk of injury due to the weight of the pump The pump itself and the parts of pump can be extremely heavy Falling parts pose a risk of cuts crush injuries bruises or impacts wh...

Страница 20: ...3 Item 5 on the motor flange and lift the drive off the pump with suitable hoisting gear On BL pumps the adapter ring comes loose Fig 3 Item 8 By loosening the lantern fastening screws Fig 1 2 3 Item...

Страница 21: ...opening the vent screw Fig 1 2 3 Item 1 31 DANGER Risk of scalding Due to high fluid temperatures there is a risk of scalding If the fluid is hot allow it to cool down before performing any work NOTE...

Страница 22: ...m 10 Installation instructions Impeller Shaft M10 M12 M16 30 60 100 Pump housing Lantern M16 100 Tighten evenly and diagonally Lantern Motor M10 M12 M16 35 60 100 Coupling M6 10 9 M8 10 9 M10 10 9 M12...

Страница 23: ...o customer service or a spe cialised service centre and serviced if necessary Motor protection switch has triggered Throttle the pump to the rated volume flow on the pressure side Motor protection swi...

Страница 24: ...No Part Details No Part Details 1 Exchange set complete 1 1 Impeller set with 1 5 Coupling complete 1 11 Nut 2 Motor 1 12 Spring washer 3 Pump housing set with 1 13 Impeller 1 14 O ring 1 14 O ring 3...

Страница 25: ......

Страница 26: ......

Страница 27: ...chkeit Richtlinie 2004 108 EG Electromagnetic compatibility directive Directive compatibilit lectromagn tique Richtlinie energieverbrauchsrelevanter Produkte 2009 125 EG Energy related products direct...

Страница 28: ...dla produkt w zwi zanych z energi 2009 125 WE 2009 125 Pou it 50Hz t f zov induk n motory s klecov m rotorem jednostupJov vyhovuj po adavkQm na ekodesign dle na zen 640 2009 Stosowane elektryczne sil...

Страница 29: ...20 27442100 Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 Ireland WILO Ireland T 353 61 227566 Italy Borromeo Milano T 39 25538351 Kazakhstan WILO Central Asia 050002 Almaty T 7...

Страница 30: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: