4 Intended use (Application)
Wilo-Stratos ECO circulating pumps are intended for use in conjunction with
hot water heating or similar water circulating systems with variable volume
characteristics. The pump-integrated electronic differential pressure control
provides infinitely-variable speed control to match pump capacity to actual
load demand.
The standard cast iron Wilo-Stratos ECO circulating pumps are not suitable for
handling potable water and food related liquids. For these applications the
Wilo-Stratos ECO bronze version, model “B” is required.
5 Product Data
CAUTION! Risk of damage to the pump!
Risk of damage due to improper handling during transport or storage.
• The pump is to be protected against moisture and mechanical damage due to
impact/shock.
• The pumps must not be exposed to ambient temperatures outside the range
-14 °F to +122 °F (-10 °C to +50 °C).
WARNING! Health hazard!
The pump must not be used for pumping liquids in the fields of service/
drinking water and food related liquids.
5.1
Technical data
Stratos ECO 16F/FX/BFX
115 V
Stratos ECO 16F/FX/BFX
230 V
Power supply & frequency
1~115 V ± 10%
60 Hz ± 5%
1~230 V ± 10%
60 Hz ± 5%
Power consumption
See name plate
See name plate
Enclosure type
2
2
Water temperature range
60 °F to 230 °F /
15 °C to 110 °C
60 °F to 230 °F /
15 °C to 110 °C
Max. working pressure
145 psi (10 bar)
145 psi (10 bar)
Max. ambient temperature
104 °F / 40 °C
104 °F / 40 °C
Inf. variable head control
4 – 16 feet
4 – 16 feet
Minimum inlet pressure
1.0 / 4.3 / 14.0 psi
1.0 / 4.3 / 14.0 psi
For maximum temperature
122 / 203 / 230 °F
122 / 203 / 230 °F
Flange to flange dimensions
6 ½
inch flange to flange
6 ½
inch flange to flange
Содержание Stratos ECO Series