Installation and operating instructions Wilo-SC/SCe-HVAC
69
1.2.5.2
Setting of the activation delay of the
peak-load pump
0 … 30 … 120
[s]
Only p–c:
0 … 3 … 120
[s]
30 s
3 s
1.2.5.3
Setting of the deactivation delay of
the peak-load pump
0 … 30 … 120
[s]
Only p–c:
0 … 3 … 120
[s]
120 s
3 s
1.2.5.4
Only p-c
Setting of the follow-up time for dry-
running protection
0 … 15 … 180
[s]
15 s
1.2.5.5
Only p-c
Setting of the restart delay after dry
run
0 … 5 … 10
[s]
5 s
1.2.6.0
Only SCe,
SC... FC
Frequency converter parameters
–
–
1.2.6.1
Setting of the maximum speed
80 … 100
[%]
100%
1.2.6.2
Setting of the minimum speed
SCe:
15 … 30 … 50
[%]
SC... FC:
40 … 90
[%]
30%
40%
1.2.6.3
Setting of the acceleration ramp time 0.0 … 3.0 … 10.0
[s]
3.0 s
1.2.6.4
Setting of the deceleration ramp time 0.0 … 3.0 … 10.0
[s]
3.0 s
Menu no./
notes
Display
Description
Parameter range
Factory setting