5.2.0.0
Sensor settings
–
–
5.2.1.0
Only
Δ
p-c,
Δ
p-v
Selection of the measurement range
2
10
20
40
60
100
160
250
[m]
40 m
5.2.1.0
Only p-c
Selection of the measurement range
0–6
0–10
0–16
0–25
[bar]
0–16 bar
5.2.2.0
Selection of the electrical signal type
Attention!
For a voltage signal, the correspond-
ing jumper setting must be selected
on the printed circuit board.
0–10 V
2–10 V
0–20 mA
4–20 mA
4–20 mA
5.2.3.0
Selection of the system reaction in
the event of a sensor fault
Stop
Var
Stop
5.2.4.0
Only SCe,
SC... FC
Setting of the speed in the event of a
sensor fault
f
min
… 60 … f
max
[%]
60%
5.3.0.0
Only
Δ
p-c,
Δ
p-v,
p-c,
Δ
T-c
External setpoint
–
–
5.3.1.0
Activation of the external setpoint
Attention!
Only a 4-20 mA signal is possible.
OFF
ON
OFF
Menu no./
notes
Display
Description
Parameter range
Factory setting