English
68
WILO SE 02/2014
1.2.3.0
Only SCe,
SC... FC
Speeds
–
–
1.2.3.1
Setting of the peak-load pump acti-
vation threshold in relation to the
speed of the base-load pump
78… 98… f
max
–2
[%]
98%
1.2.3.2
Setting of the peak-load pump deac-
tivation threshold in relation to the
speed of the base-load pump
SCe:
f
min
+2 … 32 … 52
[%]
SC... FC:
f
min
+2 … 42 … 92
[%]
32%
42%
1.2.4.0
Only SCe,
SC... FC
PID controller parameter menu
–
–
1.2.4.1
Setting of the proportional factor
0 … 0.5… 100.0
0.5
1.2.4.2
Setting of the integral factor
0.0 … 2.0… 300.0
[s]
2.0 s
1.2.4.3
Setting of the differential factor
0.0 … 300.0
[s]
0.0 s
1.2.4.4
Only
n= f(RT)
n= f(FT)
Setting of the controller curve
(rising or falling)
Raise
Fall
Raise
1.2.5.0
Delay times
–
–
Menu no./
notes
Display
Description
Parameter range
Factory setting