Installation and operating instructions Wilo-SC/SCe-HVAC
65
1.2.1.4
Only
Δ
p-v
Setting of the minimum permissible
delivery head for the second setpoint
0.0 ... 5.0 ...
Sensor measure-
ment range [m]
5.0 m
1.2.1.5
Only
Δ
p-v
Setting of the zero-delivery head of
the pump
0.0 ... 30.0 ...
Sensor measure-
ment range [m]
30.0 m
1.2.2.0
Only SC,
SCe... FC
Thresholds
–
–
1.2.2.3
Setting of the activation threshold of
the 1
st
peak-load pump (in % of the
active setpoint)
75 … 90 …100
[%]
90%
1.2.2.3
Only
Δ
p-c,
Δ
p-v
Activation threshold
1
st
peak-load pump
–
–
1.2.2.3
Only p-c
Activation threshold
1
st
peak-load pump
–
–
1.2.2.3
Only
Δ
T-c
Activation threshold
1
st
peak-load pump
–
–
1.2.2.4
Setting of the deactivation threshold
of the 1
st
peak-load pump (in % of
the active setpoint)
100 ... 115 ... 125
[%]
115%
1.2.2.4
Only
Δ
p-c,
Δ
p-v
Deactivation threshold
1
st
peak-load pump
–
–
Menu no./
notes
Display
Description
Parameter range
Factory setting