Product description
en
Installation and operating instructions Wilo-EMU KS
217
EMU KS… Ex
The system is driven by surface-cooled submersible motors in three-phase current ver-
sion. The motor is cooled by the fluid around it. The waste heat is transferred directly to
the fluid via the motor housing. The motor may emerge during operation. The connec-
tion cable is longitudinally sealed watertight and has bare cable ends or is equipped
with a CEE plug.
4.1.3
Seal
The seal for the fluid and the motor compartment is made via two mechanical seals. The
sealing chamber between the mechanical seals is filled with medical white oil.
4.1.4
Material
EMU KS…
▪ Pump housing: EN-GJL-250 (ASTM A48 Class 35/40B)
▪ Impeller: EN-GJL-250 (ASTM A48 Class 35/40B) or EN-GJS-500-7
(ASTM A536 70-50-05)
▪ Motor housing: G-AlSi12
▪ Cooling jacket (from size 24): G-AlSi12
▪ Seal on the motor side: C/Al
2
O
3
▪ Seal on the fluid side: SiC/SiC
▪ Seal, static: FPM (FKM)
NOTICE! In the “GG” version, the motor housing is also made from EN-GJL-250
(ASTM A48 Class 35/40B).
EMU KS… Ex
▪ Pump housing: EN-GJL-250 (ASTM A48 Class 35/40B)
▪ Impeller: EN-GJL-250 (ASTM A48 Class 35/40B) or EN-GJS-500-7
(ASTM A536 70-50-05)
▪ Motor housing: EN-GJL-250 (ASTM A48 Class 35/40B)
▪ Seal on the motor side: SiC/SiC
▪ Seal on the fluid side: SiC/SiC
▪ Seal, static: FPM (FKM)
4.1.5
Fitted accessories
Float switch
In the “S” version and “DMS” version, the pump is equipped with a float switch. De-
pending on the fill level, it is possible to switch the pump on and off automatically, by
using the float switch.
Plug
In the “E” version, a shockproof plug is attached and the “D” version has a CEE plug. The
plug is designed for use in commercially available shock-proof or CEE sockets and is
not
overflow-proof.
4.2
Monitoring devices
Overview of monitoring devices:
KS...
KS...Ex
Motor compartment
-
•
Motor winding
-
•
Motor bearings
-
-
Sealing chamber
Internal electrode
-
-
External electrode
o
o
Key: - = not available/possible, o = optional, • = as standard
All the monitoring devices fitted must always be connected!
Monitoring of motor winding
The thermal motor monitoring protects the motor winding from overheating. Temper-
ature limiter with bimetallic strip is fitted as standard.
Sealing chamber monitoring
The sealing chamber can be equipped with an external pencil electrode. The electrode
registers fluid ingress through the mechanical seal on the fluid side. An alarm or deac-
tivation of the pump can therefore take place through pump control.