background image

en

Disposal

34

WILO SE 2020-05

Symbol

Signalling

Cause

Troubleshooting

LED 

lights up.

High water alarm active

Check pump/system operating conditions and level set-
tings.

LED 

flashes.

Switchgear is operated without any
load.

Check mains connection of the switchgear and pump con-
nection.

LED 

lights up.

Set rated current exceeded

Check and, if necessary, correct the setting of DIP switch 1.

LED 

lights up.

Temperature sensor in motor triggered

Check connection, the converter bridge may be missing.

Check the operating conditions of the pump.

All LEDs light up for
2 s.

Key lock active

Deactivate key lock.

All LEDs light up
from right to left.

Incorrect phase sequence at mains con-
nection

Swap over 2 phases at the mains connection of the
switchgear.

All LEDs flash at the
same time.

Sensor fault

Check connection.

Contact customer service to have the faulty sensor re-
placed.

11.5

Fault memory

The last fault is stored retentively in the fault memory. The corresponding LED lights up
when the fault is retrieved.

Function

Buttons

Description

MS-L1...

MS-L2...

Open the fault memory.

Pressing the Stop and automatic mode buttons at the same time.

Delete the fault memory.

Pressing the Stop and manual mode buttons for longer (approx. 1 s) at
the same time (pump 1).

11.6

Further steps for troubleshooting

If the points listed here do not rectify the fault, please contact customer service. Costs
may be incurred if other services are used. For more details, please contact customer
service.

12

Disposal

12.1

Rechargeable battery

Do not dispose of rechargeable batteries in domestic waste and remove them before
product disposal. End consumers are legally obliged to return all used rechargeable bat-
teries. For this purpose, you can return used rechargeable batteries free of charge at
municipal collection points or specialist retailers.

NOTICE
Disposal in domestic waste is prohibited!

Affected rechargeable batteries are marked with this symbol. The identifier for the
heavy metal they contain is displayed beneath the graphic:

Hg

 (mercury)

Pb

 (lead)

Cd

 (cadmium)

12.2

Information on the collection of
used electrical and electronic
products

Proper disposal and appropriate recycling of this product prevents damage to the envi-
ronment and putting your personal health at risk.

NOTICE
Disposal in domestic waste is prohibited!

In the European Union this symbol may be included on the product, the packaging or
the accompanying documentation. It means that the electrical and electronic
products in question must not be disposed of along with domestic waste.

Содержание Control MS-L 2x8A-T4-DOL-X

Страница 1: ...Pioneering for You Wilo Control MS L 2552612 Ed 01 2020 05 en Installation and operating instructions...

Страница 2: ......

Страница 3: ...3 M L N PE N WSK 1 230V 50 60Hz 1 L N ON OFF DrainAlarm ON L N 1 230V 50Hz U V W L N 1 230V 50Hz 120 60 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 8 PE SSM 1 2 3 7 8 9 4 5 6 GL WSK HW T1 1 3 5 13 A1 2 4 6...

Страница 4: ...Hz 3 M PE WSK 1 230V 50 60Hz 1 L N ON OFF DrainAlarm ON L N 1 230V 50Hz U V W L N 1 230V 50Hz 1 2 3 4 1 2 3 4 120 60 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 8 PE SSM 1 2 3 7 8 9 4 5 6 GL WSK HW T1 1 3 5...

Страница 5: ...F NW21 NW22 L N 1 230V 50Hz U bk bn V W N L L1 L2 L3 PE 3 400V 50 60Hz L1 L L2 N PE 1 230V 50 60Hz 1 230V 50Hz 30 15 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 PE SSM 1 2 5 7 8 9 6 WSK T1 1 3 5 13 A1 2 4 6...

Страница 6: ...5 6 7 SSM Alarm GL WSK P2 WSK P1 SL 10 16 15 14 13 12 11 9 8 7 6 5 4 3 2 1 HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO L1 L2 L3 N WSK M 3 WSK M 1 T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO ON DI...

Страница 7: ...conds ON 100 K DIP 1 2 3 4 5 6 7 SSM Alarm GL WSK P2 WSK P1 SL 10 16 15 14 13 12 11 9 8 7 6 5 4 3 2 1 HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO L1 L2 L3 N WSK M 3 WSK M 1 T1 1 3 5 13 A1 2 4 6 14...

Страница 8: ...2 L N 1 230V 50Hz U bk bn V W 30 15 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 SSM Alarm WSK P2 Sensor ln WSK P1 16 15 14 13 12 11 10 9 4 3 2 1 T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO WSK M 3 WSK M 1 U...

Страница 9: ...6 Type key 15 4 7 Operation on electronic start up controllers 16 4 8 Installation in potentially explosive atmospheres 16 4 9 Scope of delivery 16 4 10 Accessories 16 5 Transportation and storage 16...

Страница 10: ...nance tasks 33 11 Faults causes and remedies 33 11 1 Operator responsibilities 33 11 2 Fault indication 33 11 3 Fault acknowledgement 33 11 4 Error messages 33 11 5 Fault memory 34 11 6 Further steps...

Страница 11: ...ny warranty or liability in the following cases Inadequate configuration due to inadequate or incorrect instructions by the operator or the client Non compliance with these instructions Improper use I...

Страница 12: ...st carry out the electrical work Installation dismantling The technician must be trained in the use of the necessary tools and fixation materials for the relevant construction site Operation control O...

Страница 13: ...cturer may be used for maintenance and repairs Use of parts other than the original parts releases the manufacturer from any liabil ity 2 8 Operator responsibilities Provide installation and operating...

Страница 14: ...level is detected by a separate float switch Control MS L LS The level is detected via two switching points by a rod float sensor 4 20 mA signal The high water level is detected by a separate switchin...

Страница 15: ...ad Minimum 12 VDC 10 mA Maximum 250 VAC 1 A 4 5 Functions The switchgear is equipped with the following functions All functions are switched off at the factory The functions must be switched on as req...

Страница 16: ...g instructions 4 10 Accessories Float switch for drainage and sewage Signal lamp Flash light Horn 5 Transportation and storage 5 1 Delivery After receiving the shipment check it immediately for defect...

Страница 17: ...d length for the routing type chosen Seal unused threaded cable glands Ensure that the following ambient conditions are adhered to Ambient operating temperature 30 60 C Relative humidity 40 50 Max rel...

Страница 18: ...cting the high water level No separate float switch is required If there is an alarm a forced switch on of all pumps occurs 6 5 Electrical connection DANGER Risk of death due to electrocution Improper...

Страница 19: ...r 2 Motor contactor 3 Terminal strip Sensors 4 Terminal strip Earth PE 5 Potentiometer for follow up time 6 Slot 9 V rechargeable battery 7 Terminal strip Mains connection 8 DIP switch 1 9 DIP switch...

Страница 20: ...minal strip Earth 7 Terminal strip Mains connection 8 DIP switch 1 NOTICE Install two cable bridges on the mains terminal strip Terminal 1 2 and ter minal 3 4 Cable 3 core Terminals 4 T2 L N N Connect...

Страница 21: ...7 Terminal strip Mains connection 8 DIP switch 1 NOTICE Do not install any cable bridges on the mains terminal strip Cable 5 core Terminals 1 L1 2 L2 3 L3 4 N Connect the protective earth conductor P...

Страница 22: ...the connected pump Set rated current according to rating plate ON DIP 1 2 3 4 5 6 7 8 Fig 9 DIP switch 1 Adjust motor current mon itoring Set rated current via DIPs 1 5 on DIP switch 1 Minimum rated...

Страница 23: ...ol device NOTICE Do not apply external voltage An external voltage which is applied destroys the component GL WSK P2 WSK P1 SL 10 9 8 7 6 5 4 3 2 1 HW HW GL WSK 6 5 4 3 2 1 3 3 Control MS L1 MS L O WS...

Страница 24: ...tage is also present at the terminals when the main switch is switched off There is a risk of fatal injury The power supply must be disconnected from its source before commencing any work Electrical w...

Страница 25: ...s Follow up time Adjustable switching points for pump ON and high water Key available not available The switching points can be selected from eight sets of parameters for the respective lifting unit 6...

Страница 26: ...5 Follow up time The follow up time defines the time between the float switch OFF signal and the pump being deactivated by the switchgear Adjust the follow up time continuously at the potentiometer 12...

Страница 27: ...of pump 1 Bottom row current status of pump 2 Display LED LED colour Description MS L1 MS L2 Mains connection Green LED lights up Mains voltage and control voltage are on Automatic mode Green LED flas...

Страница 28: ...evel has been reached both pumps are switched on forced switch on The high water LED displays an alarm signal Additionally the internal buzzer can emit an audible alarm signal Furthermore the output f...

Страница 29: ...in potentially explosive areas The switchgear does not have its own explosion protection class and must always be installed outside of potentially explosive areas The connection must be made by a qual...

Страница 30: ...argeable battery again or by connecting the power supply By inserting a rechargeable battery a mains independent alarm signal can be issued in the case of a power failure An audible constant tone is e...

Страница 31: ...Automatic mode switched on The Pump operation LED shows the current status of the pump 8 8 During operation Make sure the following points are observed during operation Keep the switchgear closed and...

Страница 32: ...ed so that it is voltage free and safeguarded against being activated by unauthorised persons The power connection for fault and run signals is switched so that it is voltage free and safeguarded agai...

Страница 33: ...locally applicable accident prevention and safety regulations of trade asso ciations Make sure that the personnel has had the corresponding training for the specified work Train the personnel on how t...

Страница 34: ...the Stop and manual mode buttons for longer approx 1 s at the same time pump 1 11 6 Further steps for troubleshooting If the points listed here do not rectify the fault please contact customer servic...

Страница 35: ...ching frequency of the motor must not be exceeded NOTICE Depending on the system impedance and the maximum connections hour of the connected consumers voltage fluctuations and or drops may occur When...

Страница 36: ...en Appendix 36 WILO SE 2020 05 3 400 V 4 pole direct starting Power in kW System impedance in ohm Connections h 3 0 0 2090 6 3 0 0 1380 24 3 0 0 1240 30 4 0 0 1480 6 4 0 0 0830 24 4 0 0 0740 30...

Страница 37: ......

Страница 38: ......

Страница 39: ...ilo it Kazakhstan WILO Central Asia 050002 Almaty T 7 727 312 40 10 info wilo kz Korea WILO Pumps Ltd 20 Gangseo Busan T 82 51 950 8000 wilo wilo co kr Latvia WILO Baltic SIA 1019 Riga T 371 6714 5229...

Страница 40: ...Pioneering for You WILO SE Nortkirchenstr 100 44263 Dortmund Germany T 49 0 231 4102 0 T 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: