Installation
en
Installation and operating instructions Wilo-Control MS-L
25
3
Control MS-L2...
SSM
Alarm
16
15
14
13
12
11
Fig. 15:
Terminal strip sensors: external alarm
signal for high water
An external alarm signal (horn, flashing light, etc.) can be connected for the high water
alarm:
ƒ
Contact type: potential-free changeover contact
ƒ
Contact load:
–
Minimum: 12 VDC, 10 mA
–
Maximum: 250 VAC, 1 A
Insert the connection cables laid by the customer through the threaded cable glands
and secure. Connect the wires to the terminal strip according to the connection dia-
gram.
Switchgear
Normally open contact
(NO)
Normally closed contact
(NC)
Control MS-L1...
−
−
Control MS-L2...
Terminal 15/16
Terminal 14/15
6.6
Functions
The switchgear is equipped with the following functions. All functions are switched off
at the factory. The functions must be switched on as required.
Inputs/outputs
Control MS-L 1...
Control MS-L 1...-O
Control MS-L 1...-LS
Control MS-L 2...
Control MS-L 2...-O
Control MS-L 2...-LS
Internal buzzer
•
•
•
•
•
•
Pump kick
•
•
•
•
•
•
Service interval indicator
−
−
−
•
•
•
Monitoring operating parameters
−
−
−
•
•
•
Follow-up time
•
•
•
•
•
•
Adjustable switching points for pump ON and high water*
−
−
•
−
−
•
Key
• = available, − = not available
* The switching points can be selected from eight sets of parameters for the respective
lifting unit.
6.6.1
Internal buzzer
ON
DIP
1 2 3 4 5 6 7
8
Fig. 16:
DIP switch 1: internal buzzer
The internal buzzer can also issue audible warning messages in addition to the visual in-
dicator. Switch the internal buzzer on/off via DIP 7 on DIP switch 1:
ƒ
“ON” position: Buzzer on
ƒ
“OFF” position: Buzzer off
6.6.2
Pump kick
ON
DIP
1 2 3 4 5 6 7
8
Fig. 17:
DIP switch 1: Pump kick
To prevent prolonged standstill periods for the connected pumps, a periodic test run
can be performed (pump kick function). A 2 s test run takes place after a standstill
period of 24 h for the respective pump.
Switch the pump kick on/off via DIP 6 on DIP switch 1:
ƒ
“ON” position: Pump kick on
ƒ
“OFF” position: Pump kick off
6.6.3
Service interval indicator
A service interval indicator can be switched on to increase operational reliability. The
time is recorded continuously when the mains voltage is switched on. After the interval
has elapsed, a visual signal is emitted by means of the yellow LED on the front.
NO-
TICE! There is no audible signal and the collective fault signal is not activated!