The following table contains a list of all fault 
signals.

* Fault must be reset manually

** You can adjust whether the error is reset manually or 

automatically

If the fault cannot be remedied, please contact your nearest 
Wilo customer service point or representative.

Code

Alarm text

Causes

Remedies

E040.0 *

Sensor faulty

Pressure sensor defective

Replace sensor

No electrical connection to the sensor

Repair the electrical connection

E040.2 *

Fault at input 
"Analogue IN"

There is no signal at the input
(wire break or signal source error)

Repair the electrical connection
Check external signal source

E060

Output 
pressure max

The output pressure of the system has risen 
above the set limit value (e.g. due to a 
controller fault)

Check controller function
Check installation

E061

Output 
pressure min

The output pressure of the system has 
dropped below the set limit value (e.g. due 
to a burst pipe)

Check whether the default value corre

-

sponds to local conditions
Check pipe and repair if necessary

E062

Low water

Protection against low water level triggered 

Check inlet/break tank; pumps restart 
automatically

E080.1 – 
E080.6 * 
(CC / CC-FC), ** 
(CCe)

Pump 1...6 
Alarm

Winding excess temperature (WSK/PTC)

Clean cooling fins; motors are designed 
for an ambient temperature of +40°C 
(see also installation and operating 
instructions of the pump)

Motor protection triggered (excess current 
or short-circuit in the supply line)

Check the pump (in accordance with the 
installation and user manual for the 
pump) and the supply line

Collective fault signal for the pump fre

-

quency converter has been activated (CCe 
version only)

Check the pump (in accordance with the 
installation and user manual for the 
pump) and the supply line

E082 **

FC Error

Frequency converter has signalled a fault

Read off fault in the list of alarms or on 
frequency converter and act in accord

-

ance with FC installation and operating 
instructions

Electrical connection disrupted

Check connection to frequency 
converter and repair if necessary

Motor protection of the frequency converter 
has tripped (e.g. short-circuit of the FC 
mains power cable; overload of the con

-

nected pump)

Check mains power cable and repair it if 
necessary; check pump (in accordance 
with the installation and operating 
instructions of the pump)

E100

Battery error

The battery charge has decreased to mini

-

mum level; an additional buffering of the 
real time clock is not guaranteed

Replace battery (see section 9)

E109 **

External error

The fault in an external device is reported to 
the switchgear via a digital input

Check external device and act according 
to its installation and operating instruc

-

tions

Содержание Control Booster CC

Страница 1: ...Pioneering for You 2 552 577 Ed 01 2020 12 Wilo Wilo Control CC Booster CC CC FC CCe en Installation and operating instructions...

Страница 2: ...Fig 1a Comfort Control 6 1 7 8 2 3 1 Fig 1b Comfort Control 6 1 7 8 2 3 1...

Страница 3: ...Fig 1c Comfort Control 4 1 6 8 2 3 1 6 7 5 Fig 1d Comfort Control 4 1 8 2 3 1 6 7 5...

Страница 4: ...Fig 1e Comfort Control 8 1 2 3 6 1 Fig 2 Fig 3...

Страница 5: ...Fig 4a Fig 4b Fig 4c...

Страница 6: ...a 5 5 3 Scope of delivery 5 5 4 Accessories 6 6 Description and function 6 6 1 Description of the product Fig 1 6 6 1 1 Function description 6 6 1 2 Set up of the switchgear 6 6 2 Function and operati...

Страница 7: ...al voltage NOTICE Signal words DANGER Acutely dangerous situation Non observance will result in death or extremely serious injuries WARNING The user could suffer serious injuries Warning implies that...

Страница 8: ...must be put back in position and or recommissioned 2 7 Unauthorised modification and manufacture of spare parts Unauthorised modification and manufacture of spare parts will impair the safety of the p...

Страница 9: ...ing application 4 x Number of pumps 1 6 10 Max rated current per pump in amperes A T Mains connection M alternating current 1 T three phase current 3 34 Rated voltage 2 220 230 V 34 380 400 V DOL Pump...

Страница 10: ...sing voltage peaks only in the CC FC version item 5 Fuse protection for drives and frequency con verter Fuse protection for the pump motors and the frequency converter For devices with P2 4 0 kW Motor...

Страница 11: ...d peak filters can be undertaken in 4 3 5 1 page 2 Normal operation of switchgears without frequency converter CC version see Fig 3 The controlled variable is taken from comparison of the setpoint act...

Страница 12: ...adjustment Remote adjustment of the setpoint is possible using an analogue current signal optional voltage signal by means of the corresponding terminals acc to circuit diagram Constant speed Constant...

Страница 13: ...splay graphics capable shows the operating statuses of the pumps the controller and the frequency converter Additionally all switchgear parameters can be set using the display The relevant operating e...

Страница 14: ...is is done using 4 screws 8 mm Suitable measures should be used to ensure the protection class Floor model BM base mounted The floor model is set up free standing on a level surface with sufficient be...

Страница 15: ...terminal strips in accordance with the circuit diagram the PE is connected to the earth rail Power kW Column 1 System impedance Column 2 Connections per hour Column 3 3 400 V 2 2 0 257 12 2 pole 2 2 0...

Страница 16: ...nnection cables are extended beyond the dimension supplied ex works it is necessary to comply with the EMC note in the operatingmanualofthefrequencyconverter only CC FC version Connection of excess te...

Страница 17: ...means of a potential free contact normally closed contact after removing the converter bridge pre assembled as a factory setting CAUTION Risk of damage to the product Do not connect any external volt...

Страница 18: ...switchgear is pre set at the factory The factory settings can be restored by Wilo Service 8 2 Checking the motor direction of rotation By briefly switching on each pump in the Manual mode operating mo...

Страница 19: ...ntact material The charge level of the real time clock backup battery is registeredbythesystem andreported if necessary In addition we recommend replacing it every 12 months For this purpose change th...

Страница 20: ...ing fins motors are designed for an ambient temperature of 40 C see also installation and operating instructions of the pump Motor protection triggered excess current or short circuit in the supply li...

Страница 21: ...cation Bit 3 6 8 15 are 1 all others are 0 The sum is then 23 26 28 215 8 64 256 32768 33096 It is also possible to do the calculation the other way round Based on the bit with the highest index check...

Страница 22: ...UINT16 0 1 CCe only RW 31 000 40020 19 Pump speed manual 5 UINT16 0 1 CCe only RW 31 000 40021 20 Pump speed manual 6 UINT16 0 1 CCe only RW 31 000 40024 23 FC ON OFF BOOL CC FC only R 31 000 40025 24...

Страница 23: ...40049 48 Pump operating mode ENUM 0 Cascade 1 Vario R 31 000 40050 49 Current speed pump 1 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40051 50 Current speed pump 2 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40052...

Страница 24: ...ating hours of pump 2 UINT32 1h R 31 000 40101 40102 100 101 Total operating hours of pump 3 UINT32 1h R 31 000 40103 40104 102 103 Total operating hours of pump 4 UINT32 1h R 31 000 40105 40106 104 1...

Страница 25: ...l R 31 000 40240 40241 239 240 Fault status 2 BITMAP32 R 31 000 40141 140 Acknowledge BOOL W 31 000 40159 158 System control BITMAP 0 Ext Off 1 Pump cycling 2 Start pump 3 Stop pump 4 Constant speed a...

Страница 26: ...Pioneering for You WILO SE Wilopark 1 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com Local contact at www wilo com contact...

Отзывы: