English

Installation and operating instructions Wilo-Control CC-Booster

9

sponding pump and activation of the SSM. After 
the cause of the fault has been rectified, it is nec

-

essary to acknowledge the fault.
The motor protection is also active in emergency 
operation, and leads to deactivation of the corre

-

sponding pump.
In the CCe version, the pump motors protect 
themselves by mechanisms integrated in the fre

-

quency converters. The error messages from the 
frequency converters are handled in the switch

-

gear as described above.

6.2.3 Operation of the switchgear

Operating elements

Main switch

 on/off (lockable in "Off" position)

• The 

touch display

 (graphics-capable)

 

shows the 

operating statuses of the pumps, the controller, 
and the frequency converter. Additionally, all 
switchgear parameters can be set using the 
display.
The relevant operating elements appear context-
related on the touch display and can be selected 
directly. Input fields for parameters are marked 
with a line at the bottom.

The basic layout of the user interface is shown 
below: 

1 - Current user status display; access to login 
page

2 - Navigation bar: Current screen display; press 
for direct navigation

3 - Quicklinks/main menu:
a - Home (return to main menu screen)
b - Control (e.g. setpoints)
c - Interaction (e.g. HMI, BMS)
d - System (e.g. pump data, sensors)
e - Current alarms
f - Help (e.g. online manual)

4 - Pressing an arrow leads to the next operation 
level

More information on operation can be found in the 
online manual on the user interface

Содержание Control Booster CC

Страница 1: ...Pioneering for You 2 552 577 Ed 01 2020 12 Wilo Wilo Control CC Booster CC CC FC CCe en Installation and operating instructions...

Страница 2: ...Fig 1a Comfort Control 6 1 7 8 2 3 1 Fig 1b Comfort Control 6 1 7 8 2 3 1...

Страница 3: ...Fig 1c Comfort Control 4 1 6 8 2 3 1 6 7 5 Fig 1d Comfort Control 4 1 8 2 3 1 6 7 5...

Страница 4: ...Fig 1e Comfort Control 8 1 2 3 6 1 Fig 2 Fig 3...

Страница 5: ...Fig 4a Fig 4b Fig 4c...

Страница 6: ...a 5 5 3 Scope of delivery 5 5 4 Accessories 6 6 Description and function 6 6 1 Description of the product Fig 1 6 6 1 1 Function description 6 6 1 2 Set up of the switchgear 6 6 2 Function and operati...

Страница 7: ...al voltage NOTICE Signal words DANGER Acutely dangerous situation Non observance will result in death or extremely serious injuries WARNING The user could suffer serious injuries Warning implies that...

Страница 8: ...must be put back in position and or recommissioned 2 7 Unauthorised modification and manufacture of spare parts Unauthorised modification and manufacture of spare parts will impair the safety of the p...

Страница 9: ...ing application 4 x Number of pumps 1 6 10 Max rated current per pump in amperes A T Mains connection M alternating current 1 T three phase current 3 34 Rated voltage 2 220 230 V 34 380 400 V DOL Pump...

Страница 10: ...sing voltage peaks only in the CC FC version item 5 Fuse protection for drives and frequency con verter Fuse protection for the pump motors and the frequency converter For devices with P2 4 0 kW Motor...

Страница 11: ...d peak filters can be undertaken in 4 3 5 1 page 2 Normal operation of switchgears without frequency converter CC version see Fig 3 The controlled variable is taken from comparison of the setpoint act...

Страница 12: ...adjustment Remote adjustment of the setpoint is possible using an analogue current signal optional voltage signal by means of the corresponding terminals acc to circuit diagram Constant speed Constant...

Страница 13: ...splay graphics capable shows the operating statuses of the pumps the controller and the frequency converter Additionally all switchgear parameters can be set using the display The relevant operating e...

Страница 14: ...is is done using 4 screws 8 mm Suitable measures should be used to ensure the protection class Floor model BM base mounted The floor model is set up free standing on a level surface with sufficient be...

Страница 15: ...terminal strips in accordance with the circuit diagram the PE is connected to the earth rail Power kW Column 1 System impedance Column 2 Connections per hour Column 3 3 400 V 2 2 0 257 12 2 pole 2 2 0...

Страница 16: ...nnection cables are extended beyond the dimension supplied ex works it is necessary to comply with the EMC note in the operatingmanualofthefrequencyconverter only CC FC version Connection of excess te...

Страница 17: ...means of a potential free contact normally closed contact after removing the converter bridge pre assembled as a factory setting CAUTION Risk of damage to the product Do not connect any external volt...

Страница 18: ...switchgear is pre set at the factory The factory settings can be restored by Wilo Service 8 2 Checking the motor direction of rotation By briefly switching on each pump in the Manual mode operating mo...

Страница 19: ...ntact material The charge level of the real time clock backup battery is registeredbythesystem andreported if necessary In addition we recommend replacing it every 12 months For this purpose change th...

Страница 20: ...ing fins motors are designed for an ambient temperature of 40 C see also installation and operating instructions of the pump Motor protection triggered excess current or short circuit in the supply li...

Страница 21: ...cation Bit 3 6 8 15 are 1 all others are 0 The sum is then 23 26 28 215 8 64 256 32768 33096 It is also possible to do the calculation the other way round Based on the bit with the highest index check...

Страница 22: ...UINT16 0 1 CCe only RW 31 000 40020 19 Pump speed manual 5 UINT16 0 1 CCe only RW 31 000 40021 20 Pump speed manual 6 UINT16 0 1 CCe only RW 31 000 40024 23 FC ON OFF BOOL CC FC only R 31 000 40025 24...

Страница 23: ...40049 48 Pump operating mode ENUM 0 Cascade 1 Vario R 31 000 40050 49 Current speed pump 1 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40051 50 Current speed pump 2 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40052...

Страница 24: ...ating hours of pump 2 UINT32 1h R 31 000 40101 40102 100 101 Total operating hours of pump 3 UINT32 1h R 31 000 40103 40104 102 103 Total operating hours of pump 4 UINT32 1h R 31 000 40105 40106 104 1...

Страница 25: ...l R 31 000 40240 40241 239 240 Fault status 2 BITMAP32 R 31 000 40141 140 Acknowledge BOOL W 31 000 40159 158 System control BITMAP 0 Ext Off 1 Pump cycling 2 Start pump 3 Stop pump 4 Constant speed a...

Страница 26: ...Pioneering for You WILO SE Wilopark 1 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com Local contact at www wilo com contact...

Отзывы: