29
Flow rate too high
Check the pump data and default values
and correct if necessary
Turn-to-turn fault in the motor
Check, if necessary replace motor or have it
repaired
Mains voltage: A phase is missing
Check the fuses, cables and connections
Motor protection switch triggers
Non-return valve defective
Check and replace the non-return valve if
necessary
Flow rate too high
Check the pump data and default values
and correct if necessary
Contactor defective
Check it and replace it if necessary
Turn-to-turn fault in the motor
Check, if necessary replace motor or have it
repaired
Mains voltage: A phase is missing
Check the fuses, cables and connections
Pump generates no or insufficient
power
Major fluctuations of the inlet pressure
Check the inlet pressure and take measures
to stabilise the supply pressure if necessary
(e.g. pressure reducers)
Inlet pipe clogged or shut off
Check the inlet pipe and, if necessary,
remove the clogging or open the shut-off
valve
Nominal diameter of the inlet pipe too
small
Check the inlet pipe and increase the cross-
section of the inlet pipe if necessary
Inlet pipe installed incorrectly
Check the inlet pipe and change the pipe
routing if necessary
Air in the inlet
Check and, if necessary, seal the piping and
vent the pumps
Impellers clogged
Check the pump and replace it or have it
repaired if necessary
Non-return valve leaking
Check and replace the seal or non-return
valve if necessary
Non-return valve clogged
Check and remove the clogging or replace
the non-return valve if necessary
Gate valve in the system closed or not
sufficiently open
Check, fully open the shut-off valve
Low-water level switch has triggered
Check the inlet pressure
Pump generates no or insufficient
power
Incorrect direction of rotation of the
motor
Check the direction of rotation and repair or
replace the frequency converter module if
necessary
Turn-to-turn fault in the motor
Check, if necessary replace motor or have it
repaired
Dry-running protection switches off
although water is present
Major fluctuations of the inlet pressure
Check the inlet pressure and take measures
to stabilise the supply pressure if necessary
(e.g. pressure reducers)
Nominal diameter of the inlet pipe too
small
Check the inlet pipe and increase the cross-
section of the inlet pipe if necessary
Inlet pipe installed incorrectly
Check the inlet pipe and change the pipe
routing if necessary
Flow rate too high
Check the pump data and default values
and correct if necessary
Electrodes connected incorrectly or
supply pressure switch set incorrectly
Check installation and setting and correct
as required
Low-water level switch or pressure
sensor on the inlet side defective
Check and, if necessary, replace the low-
water level switch or pressure sensor
Dry-running protection does not
switch off in spite of low water
Electrodes connected incorrectly or
supply pressure switch set incorrectly
Check installation and setting and correct
as required
Low-water level switch or pressure
sensor on the inlet side defective
Check and, if necessary, replace the low-
water level switch or pressure sensor
Fault
Cause
Remedy
Содержание Comfort-Vario COR-1***-GE Series
Страница 4: ...Fig 1e 53 15 17 56 55 10 9 4 54 1 8 7 12 1 11 1 12 2 5 47 57 A 52 43 B A B 52 12 2...
Страница 6: ...Fig 1h 17 9 10 7 5 12 1 11 1 8 16 13 3 4 1 12 2 15 11 2 34...
Страница 9: ...Fig 3 9 10 C B A N2 Nitrogen OPEN CLOSED...
Страница 10: ...Fig 4...
Страница 11: ...Fig 5a 14a 14b 14 1 14 4 14 5 14 6 14 8 14 7 14 3 14 2 14 9 14 10...
Страница 12: ...Fig 1a Fig 5b 14 1 14 4 14 5 14 6 14 13 14 11 14 12 14 3 14 2...
Страница 14: ...Fig 6a 21 25 29 22 20 23 24 26 29 Fig 6b 21 28 27 25 20 23 24 26 29...
Страница 15: ...Fig 8 RB 31 BW 16 16 32 30 33 30 32 34 31 33...
Страница 16: ...Fig 9a x2 36 38 39 40 35 37 42 41...
Страница 17: ...Fig 9b x4 x6 2 35 41 36 37 40 38 39 42 34 35 x4 x4...
Страница 18: ...Fig 10a 49 50 47 45 43 48 46...
Страница 19: ...Fig 10b 52 53 A B 52 53 C D 52 A 53 C 52 B 53 D 49 49...
Страница 50: ......