Wilo Comfort-Vario COR-1***-GE Series Скачать руководство пользователя страница 32

English

14

WILO SE 11/2020

6.3 Function of the system

Systems from the Wilo-SiBoost Smart 1 and 
Wilo-Comfort-Vario COR-1 and COR/T-1 series 
are fitted with a non self-priming, horizontal or 
vertical high-pressure multistage centrifugal 
pump with a three-phase current motor (17) and 
an integrated frequency converter (15) as 
standard. The pump is supplied with water via the 
inlet connection (4).
For suction mode (SiBoost Smart 1 and COR-1…) 
from lower-lying tanks, a separate, vacuum-proof 
and pressure-resistant suction line with a foot 
valve should be installed. It must be positioned at 
a constant upward inclination from the tank to the 
pump connection.
The pump increases the pressure and pumps the 
water to the consumer through the pressure pipe 
(5). To do this, it is switched on and off and 
controlled according to the pressure. One or two 
pressure sensors (12-1 and 12-2) are intended to 
monitor the pressure depending on the type of 
system (Fig. 2a and 2b). The pressure sensor or 
sensors continuously measure(s) the actual 
pressure value, convert(s) it into an analogue 
current signal and transmit(s) it to the frequency 
converter (15) of the pump (or if available the 
control device (2)). Depending on the demand and 
the control mode, the frequency converter (or the 
control device) switches the pump on or off or 
changes the speed of the pump until the set 
control parameters are reached. A more precise 
description of the control mode, control process 
and setting options can be found in the 
installation and operating instructions for the 
pump and the control device.
SiBoost Smart 1 HELIX VE…/MVISE... and 
COR-1 MVIE…GE type systems with frequency 
control on the pump and an installed pressure 
sensor on the inlet side (pump housing or suction 
line) can operate in p-v mode. For this purpose, 
special settings are possible and required on the 
frequency converter of the pump.
A more precise description of the control method 
and the setting possibilities can be found in 
the “p-v mode” section and in the separate 
documentation for the pump/frequency 
converter!

The diaphragm pressure vessel installed (9) (total 
capacity of approx. 8 litres) exercises a certain 
buffer effect on the pressure sensor and prevents 
oscillation of the control when switching the 
pump on and off. However, it also guarantees low 
water extraction (e.g. due to tiny leakages) from 
the available storage volume without switching on 
the pump. This reduces the switching frequency 
and stabilises the operating state of the system.

CAUTION! Risk of damage!
To protect the mechanical seal and plain 
bearings, do not allow the pumps to run dry. Dry 
running can lead to the pump developing 
leakages!

On SiBoost Smart 1 HELIX VE…/MVISE... and 
COR-1 MVIE…GE type systems, the supply 
pressure is continuously monitored by the 
pressure sensor on the inlet side and transmitted 
to the frequency converter as a current signal. If 
the supply pressure is too low, the system detects 
a fault and the pump is stopped.
On COR-1 MHIE…GE and SiBoost Smart 1 
HELIX VE…EM2 type systems, a low-water 
protection device (WMS) (14) (Fig. 5a and 5b) is 
provided as an accessory for direct connection to 
the public water supply network. It monitors the 
available supply pressure and sends a switching 
signal which is processed by the frequency 
converter and control device. The WMS kit is 
installed on the pump's drainage opening (WMS 
connection kit (Fig. 5a, 14b) from the accessories 
range required) or at an installation point to be 
provided in the inlet pipe.
In the case of an indirect connection (system 
separation by non-pressurised break tank), 
provide a level-dependent signal transmitter 
installed in the break tank as a dry-running 
protection device. When using a Wilo break tank, a 
float switch (Fig. 10b item 52) is included in the 
scope of delivery.
COR/T-1 series systems that are fitted with an 
unpressurised break tank for system separation 
also have a float switch (Fig. 1e item 52), which is 
installed as a low-water signal transmitter in the 
tank.
For tanks provided by the customer, you can 
find various signal transmitters for subsequent 
installation in the Wilo range (e.g. WA65 float 
switch or low-water electrodes with level relay).

WARNING! Health hazard!
Use materials that do not adversely affect the 
quality of the water for drinking water systems!

An additional main switch is optionally provided, 
which can be retrofitted on all COR-1... GE and 
SiBoost Smart 1... series systems (Fig. 1a-1h and 
Fig. 8 item 16). It is used to disconnect the mains 
supply for maintenance and repair work on the 
system.

6.3.1 P-v mode

“p-v control” operating mode

Alongside the operating modes “Speed control”; 
“Constant pressure: p-c”; “Constant differential 
pressure Δp-c”; “PID control” and “Variable 
differential pressure Δp-v” described in more 
detail in the installation and operating instructions 
for the pump, a control mode “Variable pressure 
p-v” (hereinafter referred to as just p-v control), 
described in more detail below, can be set via the 
user interface of the frequency converter in the 
menu (see Section 6.3.2).

Содержание Comfort-Vario COR-1***-GE Series

Страница 1: ...Wilo SiBoost Smart 1 Wilo Comfort Vario COR 1 GE Wilo Comfort Vario COR T 1 GE Pioneering for You 2 535 459 Ed 03 2020 11 Wilo en Installation and operating instructions...

Страница 2: ...Fig 1a 17 16 13 9 10 5 11 1 1 12 2 11 2 4 3 34 8 7 12 1 15 Fig 1b 16 13 9 10 5 11 1 1 12 2 6 11 2 4 3 34 8 7 12 1 15 17...

Страница 3: ...Fig 1c 16 13 9 10 5 11 1 1 4 14 3 34 8 7 12 1 15 17 Fig 1d 16 13 15 11 1 12 1 10 9 14 8 6 4 7 5 34 17 1 3...

Страница 4: ...Fig 1e 53 15 17 56 55 10 9 4 54 1 8 7 12 1 11 1 12 2 5 47 57 A 52 43 B A B 52 12 2...

Страница 5: ...Fig 1f 10 7 8 5 12 1 11 1 3 4 12 2 11 2 1 17 9 16 13 15 34 Fig 1g 17 9 10 7 5 12 1 11 1 8 16 13 3 4 12 2 11 2 1 15 34...

Страница 6: ...Fig 1h 17 9 10 7 5 12 1 11 1 8 16 13 3 4 1 12 2 15 11 2 34...

Страница 7: ...Fig 2a GND 4 20mA PIN3 IN OUT p I 0 16bar 4 20mA PIN1 9 10 19 18 11 1 12 1b 12 1a 12 1b PIN1 PIN1 PIN3 PIN3 12 1a 12 1b 12 1a...

Страница 8: ...Fig 2b GND 4 20mA PIN3 IN OUT p I 0 9bar 4 20mA PIN1 12 2b PIN1 PIN1 PIN3 PIN3 12 2a 12 2b 12 2a 14a 12 2b 12 2a 14 10 14 9 14 8 14 7 11 2 19 18...

Страница 9: ...Fig 3 9 10 C B A N2 Nitrogen OPEN CLOSED...

Страница 10: ...Fig 4...

Страница 11: ...Fig 5a 14a 14b 14 1 14 4 14 5 14 6 14 8 14 7 14 3 14 2 14 9 14 10...

Страница 12: ...Fig 1a Fig 5b 14 1 14 4 14 5 14 6 14 13 14 11 14 12 14 3 14 2...

Страница 13: ...Fig 5c 14 2 14 1 p 1 2 4 p 1 2 4 p 2 1 4 p 1 2 4 BN BU PS3 4xx PS3 Nxx BN BU BU BN BN BN BU BK BK p 1 3bar p 1 3bar p 1 0bar p 1 0bar BN BU BK BU 14 2a 14 2b...

Страница 14: ...Fig 6a 21 25 29 22 20 23 24 26 29 Fig 6b 21 28 27 25 20 23 24 26 29...

Страница 15: ...Fig 8 RB 31 BW 16 16 32 30 33 30 32 34 31 33...

Страница 16: ...Fig 9a x2 36 38 39 40 35 37 42 41...

Страница 17: ...Fig 9b x4 x6 2 35 41 36 37 40 38 39 42 34 35 x4 x4...

Страница 18: ...Fig 10a 49 50 47 45 43 48 46...

Страница 19: ...Fig 10b 52 53 A B 52 53 C D 52 A 53 C 52 B 53 D 49 49...

Страница 20: ...rain 52 Low water signal transmitter float switch A Tank full contact closed water not low B Tank empty contact open low water Core colours BN BROWN BU BLUE BK BLACK 53 Break tank COR T 54 Inspection...

Страница 21: ...a direct connection hydraulic diagram Fig 6b Example of an indirect connection hydraulic diagram 20 SiBoost Smart1 COR 1 system 21 Consumer connections upstream of the system 22 Diaphragm pressure ves...

Страница 22: ...vessel counter flanges vibration absorbers etc Fig 10a Break tank accessory example 43 Inlet with float valve accessory 45 Inspection opening 46 Overflow Ensure adequate drainage Provide siphon or va...

Страница 23: ...English Installation and operating instructions Wilo SiBoost Smart 1 Wilo Comfort Vario COR 1 GE Wilo Comfort Vario COR T 1 GE 5...

Страница 24: ...tup installation 21 7 1 Installation site 21 7 2 Installation 21 7 2 1 Foundation bearing surface 21 7 2 2 Hydraulic connection and pipes 21 7 2 3 Hygiene TrinkwV 2001 21 7 2 4 Protection against dry...

Страница 25: ...NING The user could suffer serious injuries Warning implies that serious injury to persons is probable if this information is disregarded CAUTION There is a risk of damaging the product system Caution...

Страница 26: ...instructions The limit values must not fall below or exceed those values specified in the catalogue data sheet 3 Transport and temporary storage The pressure boosting system is supplied on one or mor...

Страница 27: ...ode the materials used in the system either chemically or mechanically and that it does not contain any abrasive or long fibre constituents The COR 1 and SiBoost Smart 1 type automatically controlled...

Страница 28: ...series designation see attached pump documentation VE Pump design vertical electronic version 4 Rated flow rate of pump Q m3 h 10 Number of pump stages GE Basic unit i e without an additional control...

Страница 29: ...15 18 5 22 dB A tolerance 3dB A 66 68 70 70 70 71 71 72 72 78 78 81 81 Sound pressure level Pumps with glandless motors Rated power kW 1 1 2 0 dB A tolerance 3dB A 53 55 Nominal diameters Connection S...

Страница 30: ...eral description The system with its non self priming vertically Helix VE MVIE or MVISE or horizontally MHIE mounted high pressure multistage centrifugal pumpwith frequencyconverter issupplied withall...

Страница 31: ...ed frequency converter 15 with a shut off valve 7 and a connection pipe 5 installed on the discharge side There is an assembly which can be shut off with a pressure sensor 12 1 and pressure gauge 11 1...

Страница 32: ...reduces the switching frequency and stabilises the operating state of the system CAUTION Risk of damage To protect the mechanical seal and plain bearings do not allow the pumps to run dry Dry running...

Страница 33: ...menu item 1 0 0 0 The value for Qset is set manually via menu item 2 3 3 0 The value for the zero flow rate Pset Q 0 is set manually via menu item 2 3 4 0 See Section 6 3 2 for the settings In the p...

Страница 34: ...eak tank i e indirect connection Fig 6b it can be expedient to set the deactivation limit value Ps to 0 6 bar and the restart value Pr to 0 0 bar pressure value The use of an additional float switch t...

Страница 35: ...menus see also installation and operating instructions for the pump 6HWWLQJV LQ WKH RQVWDQW SUHVVXUH RSHUDWLQJ PRGH VZLWFK 2 LQ 23 5 7 21 SRVLWLRQ 6HWWLQJV LQ WKH 6SHHG VWDJH FRQWURO RSHUDWLQJ PRGH VZ...

Страница 36: ...w 1 0 0 0 rated volume flow Qset 2 3 3 0 and setpoint at zero flow Pset Q 0 2 3 4 0 have to be adjusted during commissioning Further information on the pump menu can be found in the attached installat...

Страница 37: ...DWLYH SUHVVXUH DEVROXWH SUHVVXUH 6HOHFWLRQ RI WKH VLJQDO W SH 9 P 9 P 1 H WHUQDO LQSXW 21 2 6HOHFWLRQ RI WKH VLJQDO W SH 9 9 P P 6HOHFWLRQ RI WKH VLJQDO W SH 9 9 P P 7KH WKUHVKROG IRU GHWHFWLQJ D GU U...

Страница 38: ...acteristic curve and the maximum volume flow of the system here 18 m h is used to determine the relative setpoint at zero flow here 87 5 which corresponds to a setpoint at zero flow of 4 4 bar 5 bar x...

Страница 39: ...t adjustable vibration absorbers as means of insulation against structure borne noise NOTICE Fortransportreasons the vibrationabsorbersmay not be installed upon delivery Before installing the system c...

Страница 40: ...r No additional accessories are necessary In the event of an indirect connection using a Wilo break tank a float switch for level monitoring is providedas standard as a means of dry running protection...

Страница 41: ...stem when the positive operating pressure is 1 1 times the permissible level dimensioning data is given in the data sheets characteristic curves of the system Securely drain off the outflowing water f...

Страница 42: ...displacement of the pipes fix the system tothefloor taking intoaccount suitablemeasures for reducing the structure borne noise The flexible connection pipes in the system must be accessible for inspe...

Страница 43: ...en break tank and pump the pump and the suction line must be filled via the opening in the venting screw use a funnel If a diaphragm pressure vessel optional or accessory is installed check that it is...

Страница 44: ...at the throughflow fitting and drain it Drain the system completely if necessary 9 Maintenance To guarantee maximum operational reliability at the lowest possible operating costs we recommend that th...

Страница 45: ...correct it if necessary Fuse defective Check fuses and replace if necessary Motor protection has triggered Check the default values against the pump andmotor data measure the current values and corre...

Страница 46: ...ir in the inlet Check and if necessary seal the piping and vent the pumps Air in the pump Vent the pump check the impermeability of the suction line and seal it if necessary Impellers clogged Check th...

Страница 47: ...seal or non return valve if necessary Non return valve clogged Check and remove the clogging or replace the non return valve if necessary Gate valve in the system closed or not sufficiently open Chec...

Страница 48: ...duct prevents damage to the environment and risks to personal health NOTICE Disposal in domestic waste is forbidden In the European Union this symbol can appear on the product the packaging or the acc...

Страница 49: ...are legally obliged to return all used batteries and rechargeable batteries For this purpose you can return used batteries and rechargeable batteries free of charge at municipal collection points or...

Страница 50: ......

Страница 51: ...DWH 0 7 ZLOR LWDOLD ZLOR LW D DNKVWDQ 2 HQWUDO VLD OPDW 7 LQIR ZLOR N RUHD 2 3XPSV WG DQJVHR XVDQ 7 ZLOR ZLOR FR NU DWYLD 2 DOWLF 6 5LJD 7 LQIR ZLOR OY HEDQRQ 2 121 6 5 GHLGHK HEDQRQ 7 LQIR ZLOR FRP O...

Страница 52: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: