background image

8

Part Number 550-110-832/1014

OWB & OWT

  Series 2 

Oil-Fired Water Boilers – 

Boiler Manual

Water piping — refrigeration systems

Prevent chilled water from entering boiler

Install boiler so that chilled medium is piped in parallel with the 

heating boiler. Use appropriate valves to prevent chilled medium 

from  entering  boiler.    See  Figure  5  for  typical  installation  of 

balancing valve and check valve.

Figure 3 

Diaphragm- or bladder-type expansion 

tank:  

Piping to single-zone system using 

diaphragm-type or bladder-type expansion 

tank. See Table 4, page 7, for piping sizes.

Figure 4 

Closed-type expansion tank:  Piping to

 

 single-zone system using closed-type 

expansion tank. See Table 4, page 7, for 

piping sizes.

Figure 5 

Piping refrigeration systems

  Install  boiler  so  that  chilled  medium  is  piped  in 

parallel with heating boiler. Use appropriate valves to 

prevent chilled medium from entering boiler. Consult 

I=B=R Installation and Piping Guides.

 

If  boiler  is  connected  to  heating  coils  located  in 

air handling units where they can be exposed to 

refrigerated  air,  use  flow  control  valves  or  other 

automatic means to prevent gravity circulation 

during  cooling  cycle.  Circulation  of  cold  water 

through the boiler could result in damage to the heat 

exchanger, causing possible severe personal injury, 

death or substantial property damage.

  If system includes radiant heating circuits, provide 

piping and controls to regulate the temperature 

supplying the radiant circuits. Failure to comply could 

result in substantial property damage. 

  Use Figure 3 or Figure 4 only for systems designed 

for return water at least 130 °F. For systems with 

low return water temperature possible, such as 

converted gravity systems and radiant heating 

systems,  install  by-pass  piping  (see  page  9)  to 

protect boiler against condensation. Failure to 

prevent low return water temperature to the boiler 

could  cause  corrosion  of  the  boiler  sections  or 

burners, resulting in severe personal injury, death 

or substantial property damage.

4  Connect water piping 

continued

Содержание OWB Series 2

Страница 1: ...be installed and serviced only by a qualified heating installer service technician Failure to comply could result in severe personal injury death or substantial property damage When calling or writin...

Страница 2: ...air to boiler 4 Should overheating occur do not turn off or disconnect electrical supply to circulator Instead shut off the oil supply at a location external to the appliance if possible 5 Do not use...

Страница 3: ...r be installed on carpeting Do not install boiler on carpeting even if foundation is used Fire can result causing severe personal injury death or substantial property damage Foundation 1 Provide a sol...

Страница 4: ...east 140 sq in per 1 GPH input 1 sq in per 1000 Btu input of all fuel burning appliances plus requirements for any equipment that can pull air from room including clothes dryer and fireplace When outs...

Страница 5: ...ndensation in chimney Place boiler The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on page 21 of this manual Failure to comply could...

Страница 6: ...ize Minimum chimney height Rectangle Note 2 Round OWB OWT 3 5 8 x 8 6 15 OWB OWT 4 6 8 x 8 6 15 OWB OWT 5 6 8 x 8 7 15 OWB OWT 6 7 8 x 8 7 15 Notes 1 Flue collar on boiler is 7 00 diameter 2 6 3 4 x 6...

Страница 7: ...burns should the valve discharge Discharge line must be as short as possible and be the same size as the valve discharge connection throughout its entire length Discharge line must pitch downward from...

Страница 8: ...lation and Piping Guides If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air use flow control valves or other automatic means to prevent...

Страница 9: ...t systems such as converted gravity systems 2 The bypass arrangement shown protects the boiler from damage caused by condensate corrosion due to low return water temperature This method does not provi...

Страница 10: ...andard Plumbing Code provided that Boiler water including additives is practically nontoxic having toxicity rating or class of 1 as listed in Clinical Toxicology of Commercial Products Boiler water pr...

Страница 11: ...ams shown in this manual give settings for standard equipment Burner wiring Burner harness incorporates a disconnect plug providing a convenient way to disconnect wiring when burner mounting door is o...

Страница 12: ...12 Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual NOTES This page left intentionally blank...

Страница 13: ...13 Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual Figure 10 Wiring diagram OWB and OWT boilers 6 Connect wiring continued 4...

Страница 14: ...Do not use Teflon tape as an oil pipe sealant It can cause valves to fail creating hazards Use only flare fittings Do not use compression fittings Failure to comply could result in severe personal in...

Страница 15: ...When using antifreeze Do not use automotive ethylene glycol undiluted or petroleum based antifreeze Severe personal injury death or substantial property damage can result Use antifreeze especially mad...

Страница 16: ...t 7 Test limit control While burner is operating move indicator on limit control below actual boiler water temperature Burner should go off while circulator continues to operate Raise setting on limit...

Страница 17: ...earances described above 2 Install barometric control 18 to 20 inches from boiler in breeching 3 Attach manual reset temperature switch near upper surface of enclosed area See Figure 12 4 Wire switch...

Страница 18: ...t a m s d i u q i l 2 o t n o i t c u r t s b o y n a e v o m e r d n a r o f k c e h C r e l i o b o t w o l f r i a n o i t a l i t n e v d n a n o i t s u b m o c 3 r o f t n e v r o y e n m i h c...

Страница 19: ...ler use a wire flue brush to thoroughly clean between all pins at all angles Be careful not to damage side walls of rear refractory 6 Move to the bottom of the flueways and clean up between the sectio...

Страница 20: ...Read manual Section 4 page 7 before proceeding further Safety relief valves should be reinspected AT LEAST ONCE EVERYTHREEYEARS by a licensed plumb ing contractor or authorized inspection agency to en...

Страница 21: ...h potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh air REMOVAL OF FIBERGLASS WOOL OR INST...

Страница 22: ...22 Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual 12 Replacement parts Figure 16 Boiler section assembly refractories collector hood and burner door assembly...

Страница 23: ...let includes rope and hardware for installation OWB OWT 3 386 700 241WT OWB OWT 4 386 700 242WT OWB OWT 5 386 700 243WT OWB OWT 6 386 700 244WT G Tie rod x 10 OWB OWT 3 560 234 491WT Tie rod x 14 OWB...

Страница 24: ...2 1 4 x 1 2 self tapping screws 1 Start upper screw in boiler section Do not tighten 2 Slip keyhole opening in back panels behind screw 3 Install lower screw and tighten both screws c Install top pan...

Страница 25: ...07 511 405 113WT 5 Circulator gasket universal 2 per boiler 590 317 535WT Circulator hardware kit includes 2 flanges 4 nuts 4 bolts 1 nipple 1 ell 1 NPT OWB OWT 3 OWB OWT 4 1 NPT OWB OWT 5 OWB OWT 6 3...

Страница 26: ...Dimensional drawing ALL DIMENSIONS IN INCHES Boiler model number Supply tapping inches NPT Return tapping inches NPT B Combustion chamber depth inches D Jacket depth inches OWB OWT 3 1 1 2 1 1 2 10 1...

Страница 27: ...10 OWB OWT5 T S2 1 45 203 175 85 0 152 15 9 7 8 x 8 7 15 0 015 OWB OWT6 T S2 1 40 196 171 86 0 149 18 4 7 8 x 8 7 15 0 010 OWB OWT6 T S2 1 75 245 212 85 0 184 18 4 7 8 x 8 7 15 0 015 Notes 1 MBH refer...

Страница 28: ...Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual W T 8201 W Calumet Rd Milwaukee WI 53223 28...

Отзывы: