background image

20

Part Number 550-110-832/1014

OWB & OWT

  Series 2 

Oil-Fired Water Boilers – 

Boiler Manual

11 Service and maintenance 

continued

Fill the system:

Annual service

1.  Close manual and automatic air vents and drain cock.
2.  Fill to correct system pressure. Correct pressure will vary 

with  each  installation.  Normal  cold  water  fill  pressure  for 

residential systems is 12 psig. Boiler water pH 7.0 to 8.5 is 

recommended.

  Failure to maintain recommended pH level can cause 

section  failure  and  leaks,  resulting  in  potential  of 

severe personal injury, death or substantial property 

damage.

3.  Open automatic air vent (if installed) one turn.

4.  Starting on the lowest floor, open manual air vents one at a time 

until water squirts out. Close vent. Repeat with remaining vents.

5.  Refill to correct pressure.

  Follow information below to prevent severe personal 

injury, death or substantial property damage:

•  Do not use crankcase drainings or any oil containing 

gasoline. See burner manual for proper fuel oil.

•  Do not attempt to start burner when excess oil has 

accumulated in combustion chamber, when unit is 

full of vapor, or when combustion chamber is very 

hot.

•  Do not start burner unless collector hood, breeching 

and burner mounting door are secured in place. 

Never burn garbage or paper in the boiler.

•  Never leave combustible material around boiler.

1.  Verify boiler is filled with water.
2.  Open burner door and verify rear target wall,floor and burner 

door insulations are in proper condition and position.

3.  Verify burner mounting door is closed and bolted tightly and 

burner plug is connected.

4.  Refer to burner manual for burner start-up, adjustment and 

checkout procedures. Factory burner adjustment and settings 

may not be suitable for specific job conditions.

  Make  final  burner  adjustments  using  combustion 

test equipment to assure proper operation. Do not 

fire boiler without water. Sections will overheat, 

damaging boiler and resulting in substantial property 

damage.

5.  Check boiler and system piping for leaks. 
6.  Inspect breeching and venting for proper operation.

Boiler relief valve

1.  Inspect the relief valve and lift the lever to verify flow as in the 

following warnings, excerpted from a relief valve manufacturer’s 

warning label. Before operating any relief valve, ensure that it 

is piped with its discharge in a safe area to avoid severe scald 

potential. Read manual Section 4, page 7, before proceeding 

further.

  Safety relief valves should be reinspected AT LEAST 

ONCE EVERY THREE YEARS, by a licensed plumb

-

ing contractor or authorized inspection agency, to 

ensure that the product has not been affected by 

corrosive water conditions and to ensure that the 

valve and discharge line have not been altered or 

tampered with illegally. Certain naturally occurring 

conditions may corrode the valve or its components 

over time, rendering the valve inoperative. Such 

conditions are not detectable unless the valve and its 

components are physically removed and inspected. 

This inspection must only be conducted by a  plumb-

ing contractor or authorized inspection agency — 

not by the owner. Failure to reinspect the boiler relief 

valve  as  directed  could  result  in  unsafe  pressure 

buildup, which can result in severe personal injury, 

death or substantial property damage.

2.  After following the above warning directions, if the relief valve 

weeps or will not seat properly, replace the relief valve. Ensure 

that the reason for relief valve weeping is the valve and not 

over-pressurization  of  the  system  due  to  expansion  tank 

waterlogging or undersizing.

  Following installation, the valve lever must be 

operated AT LEAST ONCE A YEAR to ensure that 

waterways are clear. Certain naturally occurring 

mineral deposits may adhere to the valve, rendering 

it inoperative. When manually operating the lever, 

water will discharge and precautions must be taken 

to avoid contact with hot water and to avoid water 

damage. Before operating lever, check to see that 

a discharge line is connected to this valve directing 

the  flow  of  hot  water  from  the  valve  to  a  proper 

place of disposal otherwise severe personal injury 

may result. If no water flows, valve is inoperative. 

Shut down boiler until a new relief valve has been 

installed.

Oiled-bearing circulators

1.  The circulator shipped with the OWB and OWT boilers are 

water-lubricated. No oiling is required.

2.  Check  other  circulators  in  the  system.  Oil  any  circulators 

requiring oil, following circulator manufacturer’s instructions. 

Over-oiling will damage the circulator.

Oiled-bearing burner motors

1.  The burner may need to be lubricated if motor is equipped 

with oiling cups. Apply a few drops only of SAE 20 detergent 

oil (never use household oils). Do not attempt to “fill up” the 

oil cup. Over-oiling can damage the motor.

Verify component operation

1.  Perform the checkout sequence on page 16 to verify system 

and components are operating correctly.

To place boiler in operation:

Содержание OWB Series 2

Страница 1: ...be installed and serviced only by a qualified heating installer service technician Failure to comply could result in severe personal injury death or substantial property damage When calling or writin...

Страница 2: ...air to boiler 4 Should overheating occur do not turn off or disconnect electrical supply to circulator Instead shut off the oil supply at a location external to the appliance if possible 5 Do not use...

Страница 3: ...r be installed on carpeting Do not install boiler on carpeting even if foundation is used Fire can result causing severe personal injury death or substantial property damage Foundation 1 Provide a sol...

Страница 4: ...east 140 sq in per 1 GPH input 1 sq in per 1000 Btu input of all fuel burning appliances plus requirements for any equipment that can pull air from room including clothes dryer and fireplace When outs...

Страница 5: ...ndensation in chimney Place boiler The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on page 21 of this manual Failure to comply could...

Страница 6: ...ize Minimum chimney height Rectangle Note 2 Round OWB OWT 3 5 8 x 8 6 15 OWB OWT 4 6 8 x 8 6 15 OWB OWT 5 6 8 x 8 7 15 OWB OWT 6 7 8 x 8 7 15 Notes 1 Flue collar on boiler is 7 00 diameter 2 6 3 4 x 6...

Страница 7: ...burns should the valve discharge Discharge line must be as short as possible and be the same size as the valve discharge connection throughout its entire length Discharge line must pitch downward from...

Страница 8: ...lation and Piping Guides If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air use flow control valves or other automatic means to prevent...

Страница 9: ...t systems such as converted gravity systems 2 The bypass arrangement shown protects the boiler from damage caused by condensate corrosion due to low return water temperature This method does not provi...

Страница 10: ...andard Plumbing Code provided that Boiler water including additives is practically nontoxic having toxicity rating or class of 1 as listed in Clinical Toxicology of Commercial Products Boiler water pr...

Страница 11: ...ams shown in this manual give settings for standard equipment Burner wiring Burner harness incorporates a disconnect plug providing a convenient way to disconnect wiring when burner mounting door is o...

Страница 12: ...12 Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual NOTES This page left intentionally blank...

Страница 13: ...13 Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual Figure 10 Wiring diagram OWB and OWT boilers 6 Connect wiring continued 4...

Страница 14: ...Do not use Teflon tape as an oil pipe sealant It can cause valves to fail creating hazards Use only flare fittings Do not use compression fittings Failure to comply could result in severe personal in...

Страница 15: ...When using antifreeze Do not use automotive ethylene glycol undiluted or petroleum based antifreeze Severe personal injury death or substantial property damage can result Use antifreeze especially mad...

Страница 16: ...t 7 Test limit control While burner is operating move indicator on limit control below actual boiler water temperature Burner should go off while circulator continues to operate Raise setting on limit...

Страница 17: ...earances described above 2 Install barometric control 18 to 20 inches from boiler in breeching 3 Attach manual reset temperature switch near upper surface of enclosed area See Figure 12 4 Wire switch...

Страница 18: ...t a m s d i u q i l 2 o t n o i t c u r t s b o y n a e v o m e r d n a r o f k c e h C r e l i o b o t w o l f r i a n o i t a l i t n e v d n a n o i t s u b m o c 3 r o f t n e v r o y e n m i h c...

Страница 19: ...ler use a wire flue brush to thoroughly clean between all pins at all angles Be careful not to damage side walls of rear refractory 6 Move to the bottom of the flueways and clean up between the sectio...

Страница 20: ...Read manual Section 4 page 7 before proceeding further Safety relief valves should be reinspected AT LEAST ONCE EVERYTHREEYEARS by a licensed plumb ing contractor or authorized inspection agency to en...

Страница 21: ...h potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh air REMOVAL OF FIBERGLASS WOOL OR INST...

Страница 22: ...22 Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual 12 Replacement parts Figure 16 Boiler section assembly refractories collector hood and burner door assembly...

Страница 23: ...let includes rope and hardware for installation OWB OWT 3 386 700 241WT OWB OWT 4 386 700 242WT OWB OWT 5 386 700 243WT OWB OWT 6 386 700 244WT G Tie rod x 10 OWB OWT 3 560 234 491WT Tie rod x 14 OWB...

Страница 24: ...2 1 4 x 1 2 self tapping screws 1 Start upper screw in boiler section Do not tighten 2 Slip keyhole opening in back panels behind screw 3 Install lower screw and tighten both screws c Install top pan...

Страница 25: ...07 511 405 113WT 5 Circulator gasket universal 2 per boiler 590 317 535WT Circulator hardware kit includes 2 flanges 4 nuts 4 bolts 1 nipple 1 ell 1 NPT OWB OWT 3 OWB OWT 4 1 NPT OWB OWT 5 OWB OWT 6 3...

Страница 26: ...Dimensional drawing ALL DIMENSIONS IN INCHES Boiler model number Supply tapping inches NPT Return tapping inches NPT B Combustion chamber depth inches D Jacket depth inches OWB OWT 3 1 1 2 1 1 2 10 1...

Страница 27: ...10 OWB OWT5 T S2 1 45 203 175 85 0 152 15 9 7 8 x 8 7 15 0 015 OWB OWT6 T S2 1 40 196 171 86 0 149 18 4 7 8 x 8 7 15 0 010 OWB OWT6 T S2 1 75 245 212 85 0 184 18 4 7 8 x 8 7 15 0 015 Notes 1 MBH refer...

Страница 28: ...Part Number 550 110 832 1014 OWB OWT Series 2 Oil Fired Water Boilers Boiler Manual W T 8201 W Calumet Rd Milwaukee WI 53223 28...

Отзывы: