background image

 
 

PMP-098 

Oil Furnaces

 – 

Furnace Manual

 

4

 

 

11/13

 

Filter 20" x 20" 

Burner position 

Combustible or non-
combustible floor 

1.2.

 

CONFIGURATIONS 

1.2.1.

 

Upflow Installation 

The return air opening may be located on either side of the furnace. 
Care should be taken not to damage the wires inside, while cutting 
the opening. Install the filter rack supplied with the unit according to 
the instructions provided with it. It is also recommended to install the 
blower door before handling or moving the unit. Refer to figure 2 for 
additional details. 

Figure 2: 

Upflow installation 

 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

1.2.2.

 

Downflow Installation 

When the furnace is installed in the downflow position on a 
combustible floor, the clearances from combustibles must be 
adhered to. The downflow base DFB-102 can be used to ensure 
these clearances. Refer to Figure 3 and the installation instructions 
provided with the base. 
The burner must always be installed in the same manner, regardless 
of the discharge position of the furnace. Refer to Figure 3 for 
additional details. 
The protection plate (B03789) must be installed on the plastic cover 
of the Beckett NX burner to protect it from vent. 

Figure 3: Downflow installation 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1.2.3.

 

Horizontal Installation 

When the furnace is installed in the horizontal position, either 
suspended or on a combustible floor with a choice of right or left 
discharge, the clearances from combustible material must be 
adhered to. If the unit is installed on a combustible floor, the 
horizontal floor base HFB-101 can be used to ensure these 
clearances. Refer to the instructions supplied with the base. 
 
The burner must always be installed in the same manner, regardless 
of the discharge position of the furnace. Refer to Figure 4 for 
additional details. 

Figure 4: Horizontal installation 

 
 
 
 
 
 
 
 
 
 
 
 
 

1.3.

 

ELECTRICAL SYSTEM 

The exterior of the unit must have an 
uninterrupted ground to minimize the risk of 
bodily harm, if ever an electrical problem 
develops. A green ground screw is supplied with 
the control box for that purpose. 

 

The appliance must be installed in accordance with the current 
ANSI/NFPA 70 National Electrical Code, CSA C22.1 Canadian 
Electrical Code Part 1 and/or local codes. 
The control system depends on the correct polarity of the power 
supply. Connect “HOT” wire (H) and “NEUTRAL” wire (N) as shown 
in figures 10 and 11. 
A separate line voltage supply should be used, with fused 
disconnect switch or circuit breaker, between the main power panel 
and the unit. 
Only copper wire may be used for the 115V circuit on this unit. If 
wires need to be changed, the replacements must have the same 
temperature resistance as the originals. 

1.4.

 

INSTALLATION OF THE THERMOSTAT 

A thermostat must be installed to control the temperature of the area 
to be heated. Follow the instructions supplied with the thermostat. 
Also refer to the wiring diagrams provided with the heating/air 
conditioning unit. The connections must be made as indicated on the 
following diagrams and the wiring diagrams, figures 10 and 11. 

Filter rack 20" x 

Floor Return Base  

Downflow base is 
required for 
combustible floor

Horizontal floor base  
required for 
combustible floor

Filter rack 20" x 20" 

Burner position 

Содержание PMP-098

Страница 1: ...antial property damage When calling or writing about the furnace Please indicate furnace model number and serial number from rating label You may list the serial number and model number in the space p...

Страница 2: ...ows 20 Always connect and seal a return air duct to the furnace unless the furnace is located in a large space such as an unpartitioned basement Route the return air duct to an adjacent room if no ret...

Страница 3: ...e minimum clearances from combustible material for each of the positions are specified in Table 1 If the furnace is installed in a basement or on a dirt floor in a crawl space for example it is recomm...

Страница 4: ...ase HFB 101 can be used to ensure these clearances Refer to the instructions supplied with the base The burner must always be installed in the same manner regardless of the discharge position of the f...

Страница 5: ...ore starting the burner for the first time adjust the air and turbulator settings to those listed in this manual Table 11 Once the burner becomes operational final adjustments will be required Refer t...

Страница 6: ...led by a qualified service technician A positive pressure venting system Sealed Combustion System or Direct Vent must NOT use the BVSO Follow the instructions supplied with the venting system This dev...

Страница 7: ...om the outside Follow the instructions provided with the burner the fresh air supply kit or the side wall venting kit 1 9 OIL TANK Fire and explosion hazard Use only approved heating type oil in this...

Страница 8: ...k satisfactorily on either heating or cooling 1 10 1 2 Determine duct dimensions Table 3 page 9 and Table 4 page 10 provide typical round and rectangular duct sizes for rectangular and flat oval galva...

Страница 9: ...7 7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 1...

Страница 10: ...2 600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 1...

Страница 11: ...same the RED wire must be moved to UNUSED LEADS on the electronic board and the jumper provided with the BLUE wire must be used between the HEAT and COOL terminals The blower start stop delays can be...

Страница 12: ...lace and the blower rail locking screws are well tightened 3 The Blocked Vent Shut Off BVSO is installed according to instructions for chimney venting 4 The oil supply valve is open 5 The burner Reset...

Страница 13: ...himney installation and 0 03 to 0 15 W C for direct vent installation A high pressure condition may be caused by excessive combustion air due to the air band being too wide open or a lack of flue draf...

Страница 14: ...e unit the heat exchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9...

Страница 15: ...ecked not to exceed 85 F and the blower speed adjusted if necessary 19 Was the thermostat heat anticipator set per wiring diagram Furnace operation continued 20 Was the burner started and tested per b...

Страница 16: ..._____________________________ Date installed ________________________ Installation instructions have been followed Checkout sequence has been performed Above information is certified to be correct Inf...

Страница 17: ...d amps Minimum ampacity for wiring sizing Maximum fuse size amps Ship weight pounds PMP 098 DD 55 85 1 X 20 x 20 115 60 1 12 2 13 7 15 125 PMP 098 VS 55 85 1 X 20 x 20 115 60 1 10 3 12 2 15 125 0 25 W...

Страница 18: ...van Pump pressure PSIG Head Low firing rate baffle Burner tube insertion length Inch ATC Head Air setting 70 000 0 50 86 1 0 40 60W 155 Yes 32229 2 0 84 000 0 60 85 4 0 50 60W 145 Yes 32229 2 5 98 000...

Страница 19: ...air adjustment Head Air 70 000 0 50 86 2 0 50 60H 100 0 50 13 84 000 0 60 85 4 0 50 60H 150 0 50 23 98 000 0 70 83 8 0 55 60H 165 60 65 30 70 000 0 50 86 2 0 50 60H 100 0 50 13 84 000 0 60 85 4 0 50...

Страница 20: ...me Off Delay CFM Level Time A 1 OFF 2 OFF 0 75 13 45 sec 19 30 sec 38 3 min B 1 ON 2 OFF 0 65 13 45 sec 19 60 sec 38 3 min C 1 OFF 2 ON 0 50 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100...

Страница 21: ...PMP 098 Oil Furnaces Furnace Manual 11 13 21 5 DIMENSIONS AND RATINGS continued Figure 12 Wiring diagram 4 speed motor PSC...

Страница 22: ...PMP 098 Oil Furnaces Furnace Manual 22 11 13 5 DIMENSIONS AND RATINGS continued Figure 13 Wiring diagram variable speed motor ECM...

Страница 23: ...PMP 098 Oil Furnaces Furnace Manual 11 13 23 6 Components and replacement parts Figure 14 Parts list with 4 speed motor PSC B50122A...

Страница 24: ...or and capacitor included 27 B03470 FLOOR 28 B03298 01 FILTER RACK FRAME 29 B03426 04 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 30 B03299 01 FILTER RACK ACCESS 31 B03450 02 LATERAL...

Страница 25: ...PMP 098 Oil Furnaces Furnace Manual 11 13 25 6 Components and replacement parts continued Figure 15 Parts list with variable speed motor ECM B50123A...

Страница 26: ...wer motor and capacitor included 26 B03470 FLOOR 27 B03298 01 FILTER RACK FRAME 28 B03426 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 29 B03299 01 FILTER RACK ACCESS 30 B03450 02...

Страница 27: ...f the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary control button NE...

Страница 28: ...PMP 098 Oil Furnaces Furnace Manual X40204 Rev B 11 13...

Отзывы: