background image

 
 

PMP-098 

Oil Furnaces

 – 

Furnace Manual

 

14

 

 

11/13

 

3.

 

MAINTENANCE 

Electrical shocks hazard. 
Turn OFF power and fuel to the furnace before 
any disassembly or servicing. 
Failure to do so can result in death, bodily injury 
and/or property damage. 

Preventive maintenance is the best way to avoid unnecessary 
expense and inconvenience. Have your heating system and burner 
inspected by a qualified service technician at regular intervals. 
To maintain the reliability and optimal performance of the furnace, 
have a complete combustion check done after the annual 
maintenance call. Do not attempt to repair the furnace or its controls. 
Call a qualified service technician. 
Before calling for repair service check the following points: 
1. 

Check the oil tank gauge and make sure the valve is open; 

2. 

Check fuses and the circuit breaker; 

3. 

Check if the main disconnect switch is ON ; 

4. 

Set the thermostat above room temperature; 

5. 

If ignition does not occur, turn off the disconnect switch and call 
a qualified service technician. 

When ordering replacement parts, please specify the complete 
furnace model number and serial number, see page 16. 

 

3.1.

 

CLEANING THE HEAT EXCHANGER 

It is not generally necessary to clean the heat exchanger or flue pipe 
every year, but it is advisable to have the oil burner service 
technician check the unit before each heating season to determine 
whether the cleaning or replacement of parts is necessary.  
If a cleaning is necessary, the following steps should be performed: 

1. 

Turn OFF all utilities upstream from the furnace; 

2. 

Disconnect the flue pipe; 

3. 

Remove the flue collar panel located at the front of the furnace; 

4. 

Remove the heat exchanger baffles; 

5. 

Disconnect the oil line and remove the oil burner; 

6.  Clean the secondary tubes and the primary cylinder with a stiff 

brush and a vacuum cleaner; 

7.  Before re-assembling the unit, the heat exchanger and 

combustion chamber should be inspected to determine if 
replacement is required; 

8.  After the cleaning replace the heat exchanger baffles, flue 

collar plate and oil burner; 

9. 

Readjust the burner for proper operation. 

3.2.

 

CLEANING THE BLOCKED VENT 

SHUT-OFF DEVICE (BVSO) (IF 

INSTALLED) 

For continuous safe operation, the Blocked Vent Shut-off device 
(BVSO) must be inspected and maintained annually by a qualified 
service technician. 

1. 

Disconnect power to the appliance; 

2.  Remove the two screws holding on the BVSO assembly cover 

and remove the cover; 

3.  Remove the two screws holding the control box to the heat 

transfer tube assembly. Sliding the control box in the 
appropriate direction will unlock it from the heat transfer tube 
assembly; 

4. 

Carefully remove any build-up from the thermal switch surface; 

Do not dent or scratch the surface of the thermal 
switch. If the thermal switch is damaged it MUST 
be replaced. 

5.  Clean and remove any build-up or obstruction inside the heat 

transfer tube; 

6.  Re-mount, lock and fasten the control box with the 2 screws 

removed in step 4; 

7.  Re-attach the assembly cover with the screws removed in step 

2; 

8. 

Re-establish power to the unit. 

3.3.

 

CLEANING OF THE BURNER HEAD 

Once annually, remove the retention head and electrodes from the 
drawer assembly and remove all foreign matter, if necessary. Also 
clean the extremity of the burner tube, if necessary. 

3.4.

 

CHANGING THE NOZZLE 

Change the nozzle once a year with the one specified in Table 10. 

3.5.

 

CHANGING THE OIL FILTER 

Tank Filter 

The tank filter should be changed as required. Follow the 
manufacturer’s instructions. 

Secondary Filter 

The 10 micron, or finer, filter cartridge should be changed annually. 
Follow the manufacturer’s instructions. 

3.6.

 

CHANGING THE AIR FILTER 

Dirty filters have an impact on the efficiency of the furnace and 
increase fuel consumption. Air filters should be changed at least 
once a year. Very dusty conditions, the presence of animal hair and 
the like will require more frequent changing or cleaning. 
 

Содержание PMP-098

Страница 1: ...antial property damage When calling or writing about the furnace Please indicate furnace model number and serial number from rating label You may list the serial number and model number in the space p...

Страница 2: ...ows 20 Always connect and seal a return air duct to the furnace unless the furnace is located in a large space such as an unpartitioned basement Route the return air duct to an adjacent room if no ret...

Страница 3: ...e minimum clearances from combustible material for each of the positions are specified in Table 1 If the furnace is installed in a basement or on a dirt floor in a crawl space for example it is recomm...

Страница 4: ...ase HFB 101 can be used to ensure these clearances Refer to the instructions supplied with the base The burner must always be installed in the same manner regardless of the discharge position of the f...

Страница 5: ...ore starting the burner for the first time adjust the air and turbulator settings to those listed in this manual Table 11 Once the burner becomes operational final adjustments will be required Refer t...

Страница 6: ...led by a qualified service technician A positive pressure venting system Sealed Combustion System or Direct Vent must NOT use the BVSO Follow the instructions supplied with the venting system This dev...

Страница 7: ...om the outside Follow the instructions provided with the burner the fresh air supply kit or the side wall venting kit 1 9 OIL TANK Fire and explosion hazard Use only approved heating type oil in this...

Страница 8: ...k satisfactorily on either heating or cooling 1 10 1 2 Determine duct dimensions Table 3 page 9 and Table 4 page 10 provide typical round and rectangular duct sizes for rectangular and flat oval galva...

Страница 9: ...7 7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 1...

Страница 10: ...2 600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 1...

Страница 11: ...same the RED wire must be moved to UNUSED LEADS on the electronic board and the jumper provided with the BLUE wire must be used between the HEAT and COOL terminals The blower start stop delays can be...

Страница 12: ...lace and the blower rail locking screws are well tightened 3 The Blocked Vent Shut Off BVSO is installed according to instructions for chimney venting 4 The oil supply valve is open 5 The burner Reset...

Страница 13: ...himney installation and 0 03 to 0 15 W C for direct vent installation A high pressure condition may be caused by excessive combustion air due to the air band being too wide open or a lack of flue draf...

Страница 14: ...e unit the heat exchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9...

Страница 15: ...ecked not to exceed 85 F and the blower speed adjusted if necessary 19 Was the thermostat heat anticipator set per wiring diagram Furnace operation continued 20 Was the burner started and tested per b...

Страница 16: ..._____________________________ Date installed ________________________ Installation instructions have been followed Checkout sequence has been performed Above information is certified to be correct Inf...

Страница 17: ...d amps Minimum ampacity for wiring sizing Maximum fuse size amps Ship weight pounds PMP 098 DD 55 85 1 X 20 x 20 115 60 1 12 2 13 7 15 125 PMP 098 VS 55 85 1 X 20 x 20 115 60 1 10 3 12 2 15 125 0 25 W...

Страница 18: ...van Pump pressure PSIG Head Low firing rate baffle Burner tube insertion length Inch ATC Head Air setting 70 000 0 50 86 1 0 40 60W 155 Yes 32229 2 0 84 000 0 60 85 4 0 50 60W 145 Yes 32229 2 5 98 000...

Страница 19: ...air adjustment Head Air 70 000 0 50 86 2 0 50 60H 100 0 50 13 84 000 0 60 85 4 0 50 60H 150 0 50 23 98 000 0 70 83 8 0 55 60H 165 60 65 30 70 000 0 50 86 2 0 50 60H 100 0 50 13 84 000 0 60 85 4 0 50...

Страница 20: ...me Off Delay CFM Level Time A 1 OFF 2 OFF 0 75 13 45 sec 19 30 sec 38 3 min B 1 ON 2 OFF 0 65 13 45 sec 19 60 sec 38 3 min C 1 OFF 2 ON 0 50 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100...

Страница 21: ...PMP 098 Oil Furnaces Furnace Manual 11 13 21 5 DIMENSIONS AND RATINGS continued Figure 12 Wiring diagram 4 speed motor PSC...

Страница 22: ...PMP 098 Oil Furnaces Furnace Manual 22 11 13 5 DIMENSIONS AND RATINGS continued Figure 13 Wiring diagram variable speed motor ECM...

Страница 23: ...PMP 098 Oil Furnaces Furnace Manual 11 13 23 6 Components and replacement parts Figure 14 Parts list with 4 speed motor PSC B50122A...

Страница 24: ...or and capacitor included 27 B03470 FLOOR 28 B03298 01 FILTER RACK FRAME 29 B03426 04 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 30 B03299 01 FILTER RACK ACCESS 31 B03450 02 LATERAL...

Страница 25: ...PMP 098 Oil Furnaces Furnace Manual 11 13 25 6 Components and replacement parts continued Figure 15 Parts list with variable speed motor ECM B50123A...

Страница 26: ...wer motor and capacitor included 26 B03470 FLOOR 27 B03298 01 FILTER RACK FRAME 28 B03426 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 29 B03299 01 FILTER RACK ACCESS 30 B03450 02...

Страница 27: ...f the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary control button NE...

Страница 28: ...PMP 098 Oil Furnaces Furnace Manual X40204 Rev B 11 13...

Отзывы: