background image

 

 

b.  Be either hard-wired or battery powered or both; and 

c.  Shall comply with NFPA 720 (2005 Edition). 

3. 

A product-approved vent terminal must be used, and if applicable, a product-approved air intake must be used.  Installation 
shall be in the strict compliance with the manufacturer’s instructions.  A copy of the installation instructions shall remain with 
the appliance or equipment at the completion of the installation. 

4. 

A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of 
vent terminal.  The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent 
Directly Below”. 

 

 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 

A.  Clearance  above  grade,  veranda,  porch,  deck  or 

balcony 12-inches (30 cm) minimum. 

(3)

 

B.  Clearance  to  window  or  door  that  may  be  opened  12-

inches (30 cm) minimum. 

(3)

 

C.  Clearance to permanently closed window (minimum 12-

inches  (30  cm)  recommended  to  prevent  condensation 
on window. 

D.  Vertical  clearance  to  ventilated  soffit  located  above  the 

terminal  within  a  horizontal  distance  of  2  feet  (60  cm) 
from  the  centerline  of  the  terminal  18-inches  (46  cm) 
minimum. 

E.  Clearance  to  unventilated  soffit  12-inches  (30  cm) 

minimum  clearance  to  vinyl  soffit  36-inches  (90  cm) 
minimum. 

F.  Clearance  to  outside  corner  12-inches  (30  cm) 

minimum.  

G.  Clearance to inside corner 18-inches (46 cm) minimum. 

H.  Not  to  be  installed  above  a  meter/regulator  assembly 

within  3  feet  (90  cm)  horizontally  from  the  centreline  of 
the regulator. 

(3)

 

I. 

Clearance to service regulator vent outlet 6 feet (1.8 m) 
minimum. 

(3)

 

J.  Clearance to non-mechanical air supply inlet to building 

or  the  combustion  air  inlet  to  any  other  furnace  12-
inches (30 cm) minimum. 

(3)

  

K.  Clearance to a mechanical air supply inlet 6 feet (1.8 m) 

minimum. 

(3)

 

L.  Clearance 

(1)

 above paved sidewalk or a paved driveway 

located on public property 7 feet (2.1 m) minimum. 

(3)

 

M.  Clearance  under  veranda,  porch,  deck  or  balcony  12-

inches (30 cm) minimum. 

(2),

 

(3)

 

 

Notes: 

(1)

 

A vent shall not terminate directly above a sidewalk 
or  paved  driveway  which  is  located  between  two 
single family dwellings and serves both dwellings. 

(2)

 

Only permitted if veranda, porch, deck or balcony is 
fully  open  on  a  minimum  of  two  sides  beneath  the 
floor. 

(3)

 

As specified in CGA B149 installation codes (1991). 
 

Note:    Local  codes  or  regulations  may  require  different 
clearances. 

Figure 1 

1 = Fixed/Closed 

 

2 = Openable   

V = Vent Terminal 

A = Air 

Supply 

Содержание 1773511

Страница 1: ...losion may result causing property damage personal injury or loss of life Williams Furnace Co 250 West Laurel Street Colton CA 92324 U S A MODEL Natural Gas Only 1773512 MODEL Propane Gas Only 1773511...

Страница 2: ...d repair should be done by a QUALIFIED SERVICE TECHNICIAN The installation must conform to local codes or in the absence of local codes the installation must conform to the National Fuel Gas Code ANSI...

Страница 3: ...qualified service technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water Safety Information for Users of LP Gas Propane LP Gas i...

Страница 4: ...is a good safety measure under any condition If at any time you do not smell the LP Gas odorant and you should assume you have a leak Then take the same immediate action recommended when you do smell...

Страница 5: ...in Canada with CAN CSA C22 2 No 3 Installations in the State of Massachusetts All installations in the State of Massachusetts must use the following requirements when installing maintaining or operat...

Страница 6: ...e of the terminal 18 inches 46 cm minimum E Clearance to unventilated soffit 12 inches 30 cm minimum clearance to vinyl soffit 36 inches 90 cm minimum F Clearance to outside corner 12 inches 30 cm min...

Страница 7: ...be length wall thickness 1 5 16 inches 7 9 mm 4 Drill the mounting holes A 5 holes in the wall If possible use self tapping screws drill 1 8 inch diameter holes If self tapping screws cannot be used d...

Страница 8: ...end Mark the location of the three holes for the screw anchors Figure 7 The flue grid must be vertical 12 Remove the vent cap and drill all the necessary holes diameter inch for the screw fittings pro...

Страница 9: ...r inserting the screwdriver as indicated by the arrow 3 Remove the nozzle from the support and replace it with the correct one Reassemble the nozzle assembly and the screw indicated at point 1 Set the...

Страница 10: ...l Gas Code that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and fore...

Страница 11: ...the furnace Checking the Gas Manifold Pressure The gas manifold pressure can be measured by connecting a test gauge to the connection provided on the gas valve Figure 8 B The furnace comes set from t...

Страница 12: ...otor Moteur du Ventilateur de Combustion SF Flame View Lamp green lamp Lampe de Presence de Flamme Verte SB Lock Out Lamp red lamp Lampe de Verrouillage Rouge TR Current Transformer 120 24 V Transform...

Страница 13: ...ond attempt is STOP Read the safety information above on this label Set the thermostat to the lowest setting by turning it counterclockwise This appliance is equipped with an ignition device that auto...

Страница 14: ...needs to be refilled after 4 5 days NOTE The use of water low in limestone or distilled is advisable in order to prevent any possible calcareous sedimentation that may be difficult to remove Anticalca...

Страница 15: ...nnect the test gauge and firmly tighten the screw of the gauge connection then check for gas leaks from it The HI and LO pressures must be adjusted as instructed above Never adjust them independently...

Страница 16: ...s 4 Check air flow switch 5 Clean and check exhaust flue pipe and air intake pipe 6 Check for gas leaks on all connections 7 Check and adjust gas pressure Check red O Ring Gasket NRNG003 If it is dama...

Страница 17: ...tion Programmable day blocks 1 2 3 4 5 Monday Friday 1 2 3 4 5 6 Monday Saturday 1 2 3 4 5 6 7 Monday Sunday 6 7 Saturday Sunday KEY A On Off Switch Pos I The appliance is controlled by the room therm...

Страница 18: ...proceeds one day at a time Number 1 stands for Monday number 2 stands for Tuesday etc C To set the time press the Hour Selector button h Figure 10 E to set the hour and the Minutes Selector button m F...

Страница 19: ...button and select the program to be cancelled B Simultaneously press the Program Selector Figure 10 C and SKIP button Figure 10 G for at least 2 seconds The selected program will be cancelled C Verifi...

Страница 20: ...ximum velocity Troubleshooting Step 2 Point 3 Z1 Z1 is down closed but there is no voltage on the fan motor M Check wiring and connections If everything is okay replace the switch Point 4 Z2 Z2 is dow...

Страница 21: ...temperature is cold replace the switch Point 9 M1 M1 is open and fan thermostat temperature is lower than 140 F Check wiring connections gas pressure and fan motor Clean fan blades and air grids If e...

Страница 22: ...control box Point 16 RP8 No flame sensing Check flame sensor wiring and connections SCheck gas pressure and exhaust flue pipe If everything is okay replace the flame control box Point 17 EV2 No voltag...

Страница 23: ...inter Switch Part Number P332630 Z8 Z3 Timer and Manual Program Mode Switch Part Number P332629 Z2 Hi Lo Flame and Fan Speed Switch Part Number P332631 SF SB Green and Red Lamps Part Number P332538 P3...

Страница 24: ...n Blower Motor Part Number P332514 M1 Overheat Thermostat Part Number P332565 M2 Fan Thermostat Part Number P332496 Fan Blades 4 pieces Part Number P332572 Left P332638 Right M Fan Motor 2 Pieces Part...

Отзывы: