background image

 

 

Installation 

Installation should be done by a QUALIFIED SERVICE TECHNICIAN.   

The furnace must be located on an outside wall. 

Wall Installation 

Minimum clearances from combustible materrials: 

 Unit to the top surface of carpeting, tile:  2-inches (50 mm) 

 Unit to back wall (0" to spacers): 0-inch (0 mm). 

 Vent to wall enclosure: 0-inch (0 mm) 

 Unit to sidewalls: 3.15-inches (80 mm) 

 Unit to ceiling: 10-inches (254 mm) 

 
 

See Figure 1 showing clearance for installation of vent cap.   
 
Leave at least three-feet in front of the wall furnace for 
servicing and proper operation. The wall furnace must be  
installed  in  such  a  way  that  the  external  casing  can  be 
completely removed for servicing. 

If there is a shelf above the furnace, it must be non-combustible.  A minimum clearance of 12-inches (300 mm) is recommended 
between the furnace and the non-combustible shelf above it. 

Gas equipment installed in residential garages must be installed so that all burners and burner ignition devices are located not 
less  than  18-inches  (460  mm)  above  the  floor.    Such  equipment  must  be  located,  or  protected,  so  it  is  not  subject  to  physical 
damage by a moving vehicle. 

The  vent  terminal  of  this  direct-vent  furnace  must  be  located  at  least  9-inches  (230  mm) from  any  opening  through  which  flue 
gases  could  enter  a  building.  The  bottom  of  the  vent  terminal  and  the  air  intake  must  be  located  at  least  12-inches  (300mm) 
above grade.   

DO NOT cover the furnace.   
Make sure that the correct gas supply is available.   
The furnace requires a 120 V 60 Hz electrical supply. 

The  appliance,  when  installed,  must  be  electrically  grounded  in 
accordance  with  local  codes,  or  in  the  absence  of  local  codes  with 
the  National  Electrical  Code  ANSI/NFPA  70  (latest  edition)  or  in 
Canada with CAN/CSA-C22.2 No. 3. 

 

 

Installations in the State of Massachusetts 

All  installations  in  the  State  of  Massachusetts  must  use  the  following  requirements  when  installing,  maintaining  or  operating 
direct-vent  propane  or  natural  gas-fired  space  heaters.    For  direct-vent  appliances,  mechanical-vent  heating  appliances  or 
domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade 
the following requirements must be satisfied: 
 
1. 

If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm 
shall be placed in the living area outside the bedroom(s).  The carbon monoxide detector shall comply with NFPA 720 (2005 
Edition). 

2. 

A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall: 

a.  Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services 

both the appliance and the carbon monoxide detector; 

b.  Have battery back-up power; 

c.  Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and 

d.  Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR. 

A carbon monoxide detector shall: 

a.  Be located in the room that houses the appliance or equipment;  

 

WARNING: For the installation of this furnace, the 

following items must be used as a vent air intake 

system: 

 

External Vent Cap 

(Part Number:  

 

WFR–TRM000) 

Flanged Air Inlet Tube 

(Part Number:   

 

WFR–TBO002) 

Flue Outlet Tube 

(Part Number:   

 

WFR–795) 

O-Ring 

(Part Number:   

 

WFN–RNG003) 

 

(All the above items are supplied with the furnace) 

WARNING: The nearest point of the vent cap should 
be  a  minimum  horizontal  distance  of  six  (6)  feet 
(1,830 mm) from any pressure regulator.   In case of 
regulator  malfunction,  the  six  (6)  feet  (1,830  mm) 
distance  will  reduce  the  chance  of  gas  entering  the 
vent cap. 

Содержание 1773511

Страница 1: ...losion may result causing property damage personal injury or loss of life Williams Furnace Co 250 West Laurel Street Colton CA 92324 U S A MODEL Natural Gas Only 1773512 MODEL Propane Gas Only 1773511...

Страница 2: ...d repair should be done by a QUALIFIED SERVICE TECHNICIAN The installation must conform to local codes or in the absence of local codes the installation must conform to the National Fuel Gas Code ANSI...

Страница 3: ...qualified service technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water Safety Information for Users of LP Gas Propane LP Gas i...

Страница 4: ...is a good safety measure under any condition If at any time you do not smell the LP Gas odorant and you should assume you have a leak Then take the same immediate action recommended when you do smell...

Страница 5: ...in Canada with CAN CSA C22 2 No 3 Installations in the State of Massachusetts All installations in the State of Massachusetts must use the following requirements when installing maintaining or operat...

Страница 6: ...e of the terminal 18 inches 46 cm minimum E Clearance to unventilated soffit 12 inches 30 cm minimum clearance to vinyl soffit 36 inches 90 cm minimum F Clearance to outside corner 12 inches 30 cm min...

Страница 7: ...be length wall thickness 1 5 16 inches 7 9 mm 4 Drill the mounting holes A 5 holes in the wall If possible use self tapping screws drill 1 8 inch diameter holes If self tapping screws cannot be used d...

Страница 8: ...end Mark the location of the three holes for the screw anchors Figure 7 The flue grid must be vertical 12 Remove the vent cap and drill all the necessary holes diameter inch for the screw fittings pro...

Страница 9: ...r inserting the screwdriver as indicated by the arrow 3 Remove the nozzle from the support and replace it with the correct one Reassemble the nozzle assembly and the screw indicated at point 1 Set the...

Страница 10: ...l Gas Code that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and fore...

Страница 11: ...the furnace Checking the Gas Manifold Pressure The gas manifold pressure can be measured by connecting a test gauge to the connection provided on the gas valve Figure 8 B The furnace comes set from t...

Страница 12: ...otor Moteur du Ventilateur de Combustion SF Flame View Lamp green lamp Lampe de Presence de Flamme Verte SB Lock Out Lamp red lamp Lampe de Verrouillage Rouge TR Current Transformer 120 24 V Transform...

Страница 13: ...ond attempt is STOP Read the safety information above on this label Set the thermostat to the lowest setting by turning it counterclockwise This appliance is equipped with an ignition device that auto...

Страница 14: ...needs to be refilled after 4 5 days NOTE The use of water low in limestone or distilled is advisable in order to prevent any possible calcareous sedimentation that may be difficult to remove Anticalca...

Страница 15: ...nnect the test gauge and firmly tighten the screw of the gauge connection then check for gas leaks from it The HI and LO pressures must be adjusted as instructed above Never adjust them independently...

Страница 16: ...s 4 Check air flow switch 5 Clean and check exhaust flue pipe and air intake pipe 6 Check for gas leaks on all connections 7 Check and adjust gas pressure Check red O Ring Gasket NRNG003 If it is dama...

Страница 17: ...tion Programmable day blocks 1 2 3 4 5 Monday Friday 1 2 3 4 5 6 Monday Saturday 1 2 3 4 5 6 7 Monday Sunday 6 7 Saturday Sunday KEY A On Off Switch Pos I The appliance is controlled by the room therm...

Страница 18: ...proceeds one day at a time Number 1 stands for Monday number 2 stands for Tuesday etc C To set the time press the Hour Selector button h Figure 10 E to set the hour and the Minutes Selector button m F...

Страница 19: ...button and select the program to be cancelled B Simultaneously press the Program Selector Figure 10 C and SKIP button Figure 10 G for at least 2 seconds The selected program will be cancelled C Verifi...

Страница 20: ...ximum velocity Troubleshooting Step 2 Point 3 Z1 Z1 is down closed but there is no voltage on the fan motor M Check wiring and connections If everything is okay replace the switch Point 4 Z2 Z2 is dow...

Страница 21: ...temperature is cold replace the switch Point 9 M1 M1 is open and fan thermostat temperature is lower than 140 F Check wiring connections gas pressure and fan motor Clean fan blades and air grids If e...

Страница 22: ...control box Point 16 RP8 No flame sensing Check flame sensor wiring and connections SCheck gas pressure and exhaust flue pipe If everything is okay replace the flame control box Point 17 EV2 No voltag...

Страница 23: ...inter Switch Part Number P332630 Z8 Z3 Timer and Manual Program Mode Switch Part Number P332629 Z2 Hi Lo Flame and Fan Speed Switch Part Number P332631 SF SB Green and Red Lamps Part Number P332538 P3...

Страница 24: ...n Blower Motor Part Number P332514 M1 Overheat Thermostat Part Number P332565 M2 Fan Thermostat Part Number P332496 Fan Blades 4 pieces Part Number P332572 Left P332638 Right M Fan Motor 2 Pieces Part...

Отзывы: