background image

 

 

High Altitude Adjustment 

Based on the altitude of the installation site, reduce the manifold pressure specified in the “Technical Data” chart and as shown 
in the table below: 

Altitude 

Manifold Pressure 

Reduction Rate 

0-2,000 ft 

0% 

2,000-3,000 ft 

8% 

3,000-4,000 ft 

16% 

4,000-5,000 ft 

24% 

5,000-5500 ft 

32% 

First Firing the Furnace 

Start the furnace following the instructions given in the “Operating Instructions”. The first lighting may be difficult because of the 
air trapped in the gas lines. During initial firing of the furnace, residual manufacturing grease will bake out and smoke will occur 
which  is  not  a  health  danger.  To  prevent  nuisance  and  operation  of  fire  alarms,  ventilate  the  room  for  the  first  two  hours  of 
operation. 

Checking the Gas Inlet Pressure 

The gas inlet pressure can be measured by connecting a test gauge to the connection provided on the gas valve.  (Figure 8 - A)  
Once  installation  is  complete,  the  gas  inlet  pressure  must  be  checked.  The  minimum  gas  inlet  pressure  must  be  as  shown  in 
“Technical  Data”.  After  checking  the  gas  inlet  pressure,  disconnect  the  test  gauge  and  firmly  tighten  the  screw  of  the  gauge 
connection, then check for gas leaks.  Correct any gas leaks before operating the furnace. 

Checking the Gas Manifold Pressure 

The gas manifold pressure can be measured by connecting a test gauge to the connection provided on the gas valve. (Figure 8 - 
B).  The  furnace  comes  set  from  the  factory  at  the  correct  manifold  gas  pressure.  After  the  installation  is  completed,  the  gas 
manifold  pressure  must  be  checked  both  in  Hi  and  Lo  input.  Turn  the  control  knob  to  switch  the  unit  from  Hi  to  Lo  input.  The 
position of the knob in which this occurs depends on the actual room temperature. The gas manifold pressure must be as shown 
in “Technical Data”. Differences of plus or minus 0.1 in. w.c. are acceptable. If the Hi or Lo gas manifold pressures are different 
from the values given in the “Technical Data” or are more than 0.1 in. w.c., shut off the furnace and contact a qualified service 
technician for correction. 
 
For  instructions  about  adjustment  of  the  manifold  Hi  and  Lo  pressures,  see  the  "Servicing”  section.  After  checking  the  gas 
manifold  pressure,  disconnect  the  test  gauge  and  firmly  tighten  the  screw  of  the  gauge  connection,  then  check  for  gas  leaks 
from it. Correct any gas leaks before operating the furnace. 

 

 

 

 

 

 

 

 

A

 

 

B

 

 

 

D

 

 

F

 

 

E

 

A.  Test gauge connection for gas inlet 

pressure 

B.  Test gauge connection for gas manifold 

pressure 

C.  Nut for Hi pressure adjustment (pressure 

regulator) 

D.  Screw for Lo pressure adjustment (Hi-Lo 

operator) 

E.  Electric clamp connection 
F.  Gas supply inlet 

Figure 8 

11 

Содержание 1773511

Страница 1: ...losion may result causing property damage personal injury or loss of life Williams Furnace Co 250 West Laurel Street Colton CA 92324 U S A MODEL Natural Gas Only 1773512 MODEL Propane Gas Only 1773511...

Страница 2: ...d repair should be done by a QUALIFIED SERVICE TECHNICIAN The installation must conform to local codes or in the absence of local codes the installation must conform to the National Fuel Gas Code ANSI...

Страница 3: ...qualified service technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water Safety Information for Users of LP Gas Propane LP Gas i...

Страница 4: ...is a good safety measure under any condition If at any time you do not smell the LP Gas odorant and you should assume you have a leak Then take the same immediate action recommended when you do smell...

Страница 5: ...in Canada with CAN CSA C22 2 No 3 Installations in the State of Massachusetts All installations in the State of Massachusetts must use the following requirements when installing maintaining or operat...

Страница 6: ...e of the terminal 18 inches 46 cm minimum E Clearance to unventilated soffit 12 inches 30 cm minimum clearance to vinyl soffit 36 inches 90 cm minimum F Clearance to outside corner 12 inches 30 cm min...

Страница 7: ...be length wall thickness 1 5 16 inches 7 9 mm 4 Drill the mounting holes A 5 holes in the wall If possible use self tapping screws drill 1 8 inch diameter holes If self tapping screws cannot be used d...

Страница 8: ...end Mark the location of the three holes for the screw anchors Figure 7 The flue grid must be vertical 12 Remove the vent cap and drill all the necessary holes diameter inch for the screw fittings pro...

Страница 9: ...r inserting the screwdriver as indicated by the arrow 3 Remove the nozzle from the support and replace it with the correct one Reassemble the nozzle assembly and the screw indicated at point 1 Set the...

Страница 10: ...l Gas Code that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and fore...

Страница 11: ...the furnace Checking the Gas Manifold Pressure The gas manifold pressure can be measured by connecting a test gauge to the connection provided on the gas valve Figure 8 B The furnace comes set from t...

Страница 12: ...otor Moteur du Ventilateur de Combustion SF Flame View Lamp green lamp Lampe de Presence de Flamme Verte SB Lock Out Lamp red lamp Lampe de Verrouillage Rouge TR Current Transformer 120 24 V Transform...

Страница 13: ...ond attempt is STOP Read the safety information above on this label Set the thermostat to the lowest setting by turning it counterclockwise This appliance is equipped with an ignition device that auto...

Страница 14: ...needs to be refilled after 4 5 days NOTE The use of water low in limestone or distilled is advisable in order to prevent any possible calcareous sedimentation that may be difficult to remove Anticalca...

Страница 15: ...nnect the test gauge and firmly tighten the screw of the gauge connection then check for gas leaks from it The HI and LO pressures must be adjusted as instructed above Never adjust them independently...

Страница 16: ...s 4 Check air flow switch 5 Clean and check exhaust flue pipe and air intake pipe 6 Check for gas leaks on all connections 7 Check and adjust gas pressure Check red O Ring Gasket NRNG003 If it is dama...

Страница 17: ...tion Programmable day blocks 1 2 3 4 5 Monday Friday 1 2 3 4 5 6 Monday Saturday 1 2 3 4 5 6 7 Monday Sunday 6 7 Saturday Sunday KEY A On Off Switch Pos I The appliance is controlled by the room therm...

Страница 18: ...proceeds one day at a time Number 1 stands for Monday number 2 stands for Tuesday etc C To set the time press the Hour Selector button h Figure 10 E to set the hour and the Minutes Selector button m F...

Страница 19: ...button and select the program to be cancelled B Simultaneously press the Program Selector Figure 10 C and SKIP button Figure 10 G for at least 2 seconds The selected program will be cancelled C Verifi...

Страница 20: ...ximum velocity Troubleshooting Step 2 Point 3 Z1 Z1 is down closed but there is no voltage on the fan motor M Check wiring and connections If everything is okay replace the switch Point 4 Z2 Z2 is dow...

Страница 21: ...temperature is cold replace the switch Point 9 M1 M1 is open and fan thermostat temperature is lower than 140 F Check wiring connections gas pressure and fan motor Clean fan blades and air grids If e...

Страница 22: ...control box Point 16 RP8 No flame sensing Check flame sensor wiring and connections SCheck gas pressure and exhaust flue pipe If everything is okay replace the flame control box Point 17 EV2 No voltag...

Страница 23: ...inter Switch Part Number P332630 Z8 Z3 Timer and Manual Program Mode Switch Part Number P332629 Z2 Hi Lo Flame and Fan Speed Switch Part Number P332631 SF SB Green and Red Lamps Part Number P332538 P3...

Страница 24: ...n Blower Motor Part Number P332514 M1 Overheat Thermostat Part Number P332565 M2 Fan Thermostat Part Number P332496 Fan Blades 4 pieces Part Number P332572 Left P332638 Right M Fan Motor 2 Pieces Part...

Отзывы: