WIKA operating instructions model TC52-M
14502900.01 12/2021 EN/DE/FR/ES
EN
5.2 Electrical mounting
■
Only connect cables and lines in an unpowered state!
■
Fine-stranded leads must be finished with end splices.
■
Cables used must comply with the respective requirements in terms of stability and
temperature, strain and mobility. Over-working the cable may cause fraying of the wire.
■
Connection cables must be run so that any mechanical damage is prevented. This
includes areas where wear may occur resulting in fraying of the wire.
■
When bending connection cables it cannot be bent within 25 mm [1 in] of the transition
region.
■
Connection cables are not to be in contact with hot surfaces (i. e. hot manifolds). Where
this cannot be achieved proper selection of electrical wire, transition or high-temperature
sleeve shall be used.
Colour coding of thermocouple cable
Thermocouple
Standard
Positive
Negative
Type J
IEC 60584
Black
White
ASTM E230
White
Red
DIN 43714
Red
Blue
Type K
IEC 60584
Green
White
ASTM E230
Yellow
Red
Type E
IEC 60584
Violet
White
ASTM E230
Violet
Red
Type T
IEC 60584
Brown
White
ASTM E230
Blue
Red
Type N
IEC 60584
Pink
White
ASTM E230
Orange
Red
5. Commissioning, operation